Third Notice | | 2/8/2014 | 2/10/2014 | | DONE |
|
|
|
|
Third Notice | | 1/5/2014 | 2/3/2014 | | DONE |
|
|
|
mailed
|
Second Notice | | 1/2/2014 | 12/23/2013 | | DONE |
|
|
|
|
First Notice | | 11/16/2013 | 12/23/2013 | | DONE |
|
|
|
|
BLD-Final | 11/6/2013 | 11/6/2013 | 11/6/2013 | A | PASS |
Tom Arcoraci
|
|
|
|
Permanent Occupancy | | | 11/6/2013 | | DONE |
Christina Prado
|
|
|
|
FIRE-Final Inspection | 11/1/2013 | 11/4/2013 | 11/4/2013 | A | PASS |
Forrest France
|
|
|
Fire life safety okayed for final. C/N item completed.
|
FIRE-Final Inspection | 10/24/2013 | 10/25/2013 | 10/25/2013 | A | PART |
Forrest France
|
|
|
Fire life safety final pending a current annual inspection for the existing overhead fire sprinkler system. Last recorded certification tag on the riser dated 2010.
|
BLD-Framing/Rough-in | 10/22/2013 | 10/23/2013 | 10/23/2013 | P | PASS |
Mike Jordan
|
|
|
Rick stair landing only Phone #: ###-####. Exterior stairs on west side of building ok.
|
BLD-Conference | 9/25/2013 | 9/26/2013 | 9/26/2013 | P | DONE |
Mike Jordan
|
|
|
rick Phone #: ###-####. Questions regarding exterior stairs.
|
OVERRIDE | | | 8/30/2013 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 8/30/2013 | | DONE |
Tisha Gallop
|
|
|
|
Print Occupancy Form | | | 8/30/2013 | | DONE |
Tisha Gallop
|
|
|
|
Permit Ready to Issue | | | 8/30/2013 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (SRZ) | 7/11/2013 | 7/11/2013 | 8/9/2013 | | PASS |
Sam Zahorka
|
|
|
1st review completed. Reassigned - (20 days - July 19) ePlanReview - NXEDGE TI - Racking attached to case also
|
Routing - PLAN CHECK | 8/9/2013 | | 8/9/2013 | | FAIL |
Sam Zahorka
|
|
|
Need City approval Stamp Box on Cover Sheet.
|
Telephone call | | | 8/9/2013 | | DONE |
Sam Zahorka
|
|
|
Called the architect Joe Thompson and requested a stamp box on the cover sheet for the city approval stamp prior to issuance.
|
Routing - PLAN CHECK | 8/9/2013 | | 8/9/2013 | | PASS |
Sam Zahorka
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/9/2013 | | DONE |
Sam Zahorka
|
|
|
|
Routing - FIRE | 7/25/2013 | 7/25/2013 | 7/25/2013 | | PASS |
Scott Arellano
|
|
|
Attached updated comments to case.
|
Routing - Design Review | 7/24/2013 | | 7/24/2013 | | PASS |
Josh Wilson
|
|
|
OK per CZC13-00168.
|
1st review completed | | | 7/16/2013 | | DONE |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 7/16/2013 | | 7/16/2013 | | FAIL |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 6/24/2013 | | 7/16/2013 | | FAIL |
Sam Zahorka
|
|
|
Revised plans submitted.
|
Plan assigned to (CJW) | 6/24/2013 | 6/24/2013 | 7/11/2013 | | DEFR |
Carl Westfall
|
|
|
Reassigned to Sam Zahorka (20 days - July 19) ePlanReview - NXEDGE TI - Racking attached to case also
|
Routing - FIRE | 6/24/2013 | 6/24/2013 | 7/3/2013 | | FAIL |
Scott Arellano
|
|
|
Emailed resubmittal item and Fire Code plan review report to architect.
|
Routing - Design Review | 6/24/2013 | | 6/26/2013 | | FAIL |
Josh Wilson
|
|
|
Needs Zoning Certificate for new doors and stairs on rear of building.
|
Routing - Erosion and Sediment | 6/24/2013 | | 6/25/2013 | | PASS |
Kimberly M. Johnson
|
|
|
No Permit Required
|
Routing PW Sewer Rating | 6/25/2013 | | 6/25/2013 | | PASS |
Connie Baumgartner
|
|
|
|
Routing - PLUMBING | 6/24/2013 | | 6/25/2013 | | PASS |
Bill VanDegrift
|
|
|
Grid strainers and tempered water required at public lavatories.
|
Routing - Addressing | 6/24/2013 | | 6/25/2013 | | PASS |
Jason C. Taylor
|
|
|
|
Routing - PUBLIC WORKS | 6/24/2013 | | 6/25/2013 | | PASS |
Beverly Mountain
|
|
|
|
Intake Approval | | | 6/24/2013 | | PASS |
Jason Blais
|
|
|
Prescreen approved by Tim Woodard on 6/20/13. Plan Review Fees paid on 6/24/13.
|
Pending Assignment by JCB | 6/24/2013 | | 6/24/2013 | | DONE |
Jason Blais
|
|
|
|
Application received | | | 6/10/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 10 2013 3:00PM
|