Third Notice | | 9/3/2014 | 10/9/2014 | | DONE |
|
|
|
This permit finaled on the web by Adam Johnson
|
Third Notice | | 6/14/2014 | 8/29/2014 | | DONE |
|
|
|
e-mailed to Adam Johnson
|
Third Notice | | 5/10/2014 | 6/9/2014 | | DONE |
|
|
|
e-mailed to Adam Johnson
|
Third Notice | | 4/5/2014 | 5/5/2014 | | DONE |
|
|
|
e-mailed to Adam Johnson
|
Second Notice | | 3/16/2014 | 3/31/2014 | | DONE |
|
|
|
|
First Notice | | 2/2/2014 | 3/6/2014 | | DONE |
|
|
|
|
BLD-Final | 1/23/2014 | 1/23/2014 | 1/23/2014 | P | PASS |
Tony Young
|
|
|
Request for final inspection sign off of Ruth''s Chris restaurant. Electrical will be signed off by Noon. Please contact Adam when available, ###-####. Thanks. Phone #: ###-#### >> Inspection requested via web by Adam Johnson,,, ok for perm c of o
|
FIRE-Final Inspection | 1/21/2014 | 1/22/2014 | 1/23/2014 | P | PASS |
Craig D. Hanson
|
|
|
emergency lighting and generator pass
|
Permanent Occupancy | | | 1/23/2014 | | DONE |
|
|
|
|
BLD-Conference | 1/21/2014 | 1/22/2014 | 1/22/2014 | A | PASS |
Dave Hannah
|
|
|
Meeting on site with Dave H. requested in ESI field office, followed by site visit if necessary. Please call Adam with any questions. ###-#### Phone #: ###-#### >> Inspection requested via web by Adam Johnson
|
FIRE-Final Inspection | 1/21/2014 | 1/21/2014 | 1/22/2014 | P | FAIL |
Craig D. Hanson
|
|
|
Emergency generator failure, Emergency lighting failure.
|
CHANGE STATUS TO (ISS) | | | 1/21/2014 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/21/2014 | | DONE |
Tim L. Woodard
|
|
|
|
Permit Ready to Issue | | | 1/21/2014 | | DONE |
|
|
|
|
Plan assigned to (TLW) | 1/13/2014 | | 1/21/2014 | | PASS |
Tim L. Woodard
|
|
|
|
Routing - PLAN CHECK | 1/13/2014 | | 1/21/2014 | | PASS |
Tim L. Woodard
|
|
|
|
Routing - MECHANICAL | 1/13/2014 | | 1/15/2014 | | PASS |
Troy James
|
|
|
|
Routing - PLUMBING | 1/13/2014 | | 1/14/2014 | | PASS |
Daryl Spivey
|
|
|
Per plan and ISPC.
|
Plan Modification Accepted | | | 1/13/2014 | | DONE |
Tim L. Woodard
|
|
|
Grease hood fan modification, modern fold door, and miisc lighting, plumbing and architectural details.
|
BLD-Ceiling Grid Inspection | 1/7/2014 | 1/8/2014 | 1/9/2014 | A | PASS |
Dave Hannah
|
|
|
Ceiling Grid Inspection, AM Wednesday, Ruths Chris, Per Mike Beeson. Thanks AKJ Phone #: ###-#### >> Inspection requested via web by Adam Johnson
|
Print Occupancy Form | | | 1/9/2014 | | DONE |
Christina Prado
|
|
|
|
BLD-Framing/Rough-in | 12/6/2013 | 12/9/2013 | 12/9/2013 | A | PASS |
Dave Hannah
|
|
|
Follow up documentation to Fridays inspection of Ruths Chris w/Mike Beeson. Thanks. akj Phone #: ###-#### >> Inspection requested via web by Adam Johnson ok to cover the rest of the hard ceilings
|
BLD-Framing/Rough-in | 11/22/2013 | 11/25/2013 | 11/25/2013 | A | PASS |
Dave Hannah
|
|
|
Framing inspection of Ruths Chris, 1st Floor. Per Mike Beeson, thanks. akj Phone #: ###-#### >> Inspection requested via web by Adam Johnson
|
BLD-Framing/Rough-in | 11/6/2013 | 11/6/2013 | 11/7/2013 | P | PART |
Dave Hannah
|
|
|
Framing inspection of Ruths Chris, 8th and Main 1st Floor, Mike Beeson, Thanks. ###-#### Phone #: ###-#### >> Inspection requested via web by Adam Johnson ok to cover walls servce area
|
BLD-Conference | 10/31/2013 | 11/1/2013 | 11/1/2013 | A | PART |
Dave Hannah
|
|
|
Permit was Pulled 10-31, Plans sent to print shop, if you could do a framing inspection around 10-10:30 please. Call Adam to confirm Plans on site to coordinate. ###-#### Phone #: ###-#### >> Inspection requested via web by Adam Johnson ok to cover walls inkitchen area.
|
Issue PAID IN FULL permit | | | 10/31/2013 | | DONE |
Barbara Stitt
|
|
|
|
Print Occupancy Form | | | 10/31/2013 | | DONE |
Barbara Stitt
|
|
|
|
Print Occupancy Form | | | 10/25/2013 | | DONE |
Barbara Stitt
|
|
|
|
Permit Ready to Issue | | | 10/25/2013 | | DONE |
Barbara Stitt
|
|
|
|
Routing - MECHANICAL | 10/9/2013 | | 10/9/2013 | | PASS |
Troy James
|
|
|
Mechanical items to be deferred.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/9/2013 | | PASS |
Jason Blais
|
|
|
|
Plan assigned to (TLW) | 7/30/2013 | | 10/9/2013 | | PASS |
Tim L. Woodard
|
|
|
1st Review Completed Ruth's Chris
|
Routing - PLAN CHECK | 10/8/2013 | | 10/8/2013 | | PASS |
Tim L. Woodard
|
|
|
|
Routing - PLAN CHECK | 9/3/2013 | | 9/9/2013 | | FAIL |
Tim L. Woodard
|
|
|
Refer to change marks in E-Plan. TLW
|
Telephone call | | | 9/9/2013 | | DONE |
Tim L. Woodard
|
|
|
Called Ryan Griffiths to discuss last of review items. Informed him we could issue a Partial Permit at this point if needed. TLW
|
Routing - MECHANICAL | 9/3/2013 | | 9/4/2013 | | FAIL |
Troy James
|
|
|
eplan
|
Routing PW Sewer Rating | 9/3/2013 | | 9/3/2013 | | PASS |
Connie Baumgartner
|
|
|
|
Plan resubmittals received | | | 9/3/2013 | | DONE |
Tim L. Woodard
|
|
|
Plans approved
|
Routing - FIRE | 7/30/2013 | 7/30/2013 | 8/19/2013 | | PASS |
Scott Arellano
|
|
|
Attached review comments to case and plans.
|
Routing - PLAN CHECK | 7/30/2013 | | 8/19/2013 | | FAIL |
Tim L. Woodard
|
|
|
Refer to E-plan changemarks. TLW
|
1st review completed | | | 8/19/2013 | | FAIL |
Tim L. Woodard
|
|
|
|
Routing - PLUMBING | 7/30/2013 | | 8/1/2013 | | PASS |
Bill VanDegrift
|
|
|
1)R.P. on water to soda.
2) 2" vent required on the 3" floor sink at the water softener.
3) vent combination waste and vent system per ISPC.
4)indirect water heater to be double wall with leak detection.
|
Routing - PUBLIC WORKS | 7/30/2013 | | 7/31/2013 | | PASS |
Connie Baumgartner
|
|
|
|
Routing - Design Review | 7/30/2013 | | 7/31/2013 | | PASS |
Sarah Schafer
|
|
|
Sarah Schafer - Approved per DRH11-00240.
|
Routing PW Sewer Rating | 7/30/2013 | | 7/31/2013 | | FAIL |
Connie Baumgartner
|
|
|
Will need to resubmit floor plans per Tim Woodard. Will calculate customer service area then.
|
Routing PW Environmental | 7/30/2013 | | 7/30/2013 | | PASS |
Walt Baumgartner
|
|
|
|
Routing - Addressing | 7/30/2013 | | 7/30/2013 | | PASS |
Jason C. Taylor
|
|
|
|
Payment Received | | | 7/29/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Intake Approval | | | 7/29/2013 | | PASS |
Jason Blais
|
|
|
Prescreen passed on 7/26/13. Plan Review Fees paid on 7/29/13.
|
Telephone call | | | 7/22/2013 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
email sent 7/22/13
Update
I spoke with Ryan on Thursday 7/18 and he told me the plans would be submitted on Friday 7/19.
On Friday afternoon I spoke with both Ryan and Lyle about the status as I had not received the revised plans. Lyle told me they were having a hard time trying to get a hold of an architect. They were trying to contact Babcock and could not get a call back from them. Lyle told me I would have the plans submitted no later than Monday as they were desperate to get them submitted.
I followed up with them just now as I have not received any resubmittals. Sometimes resubmittals get hung out in cyber space. They have contacted CTA to stamp the plans but CTA has reservations on stamping the plans as they are not the primary contract holder. Ryan has put a call into the State to see if there is a way to resolve this.
As of now we still do not have resubmittal to approve the prescreen.
Will let you when and if it changes.
Thanks
Adele J. Schaffeld-Griffin
City of Boise
Plans Examiner II
###-####
|
Intake Approval | | | 7/16/2013 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
email sent 7/16/13 7:46 am
Ryan, I have completed the prescreen. The 3 items below will still need to be addressed prior to the prescreen being approved.
1. Please provide the completed Form #304, Design professional. 7/9 comment
*The 304 form did not upload. Please re upload this form. 7/16 comment
2. All sheets submitted for review shall be stamped and signed by the design professional of record. The only sheets stamped and signed are the plumbing, mechanical and electrical sheets. 7/9 comment
*Sheets A4.1, A4.2, A4.3, A5.1, A5.2, A6.1, A6.2 currently still do not have a stamp by the licensed design professional. 7/16 comment
3. In the check list it is specified that the specification book for this project is separate. Please upload the specification books. 7/9 comment
*Comment addressed
4. The plans shall be stamped by a Idaho licensed Architect as noted in the check list that you submitted. You checked yes that the Architect was licensed in Idaho. I have verified with the State of Idaho that Lyle Beecher has not been licensed in Idaho since his license expired in April of 2008.
x Building Plans (2 complete paper sets). Plans drawn to scale on 18”x24” minimum size plan sheets.
Architectural stamped and signed by an Idaho licensed architect; Civil, structural, mechanical & plumbing
stamped and signed by Idaho licensed engineers. Note: Mechanical and plumbing may be designed by the
architect for minor work where approved in advance by the Chief Plumbing/Mechanical Inspector.
*Please upload all of the architectural sheets with a current Idaho Licensed Stamp and Signature.
If you have any questions or need any assistance please feel free to contact me.
Thank you
Adele J. Schaffeld-Griffin
City of Boise
Plans Examiner II
###-####
|
Telephone call | | | 7/12/2013 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
called Ryan left voice mail. I went in and checked e plan and the form 304 was uploaded yesterday. It did not come through. I left a message with Rayan to send it to me and I would upload it for him if he is having trouble. I also let him know that we had still not recieved any revised plan sheets to address the pre screen commentsl 7/12/13 1:40 pm ajs
|
Telephone call | | | 7/10/2013 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
Returned call to Ryan 7/10/13 questions on intake.
|
Intake Approval | | | 7/9/2013 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
email sent to Ryan 7/9/13
Ryan, I have completed the prescreen. The 3 items below will still need to be addressed prior to the prescreen being approved.
1. Please provide the completed Form #304, Design professional.
2. All sheets submitted for review shall be stamped and signed by the design professional of record. The only sheets stamped and signed are the plumbing, mechanical and electrical sheets.
3. In the check list it is specified that the specification book for this project is separate. Please upload the specification books.
I have attached change marks on the check list. This will allow you to see the exact location the requirement is specified from.
If you need any assistance please feel free to contact me.
Thank you
Adele J. Schaffeld-Griffin
City of Boise
Plans Examiner II
###-####
|
Plan Reviewer's activity | | | 7/1/2013 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
EMAIL SENT TO RYAN 7/1/13
Ryan, I received you message and wanted to send you the forms/link hoping it may be easier for you. We need form 304 http://pds.cityofboise.org/home/documents/apps/300/# completed and uploaded.
We also need the 520 Major check list completed and uploaded. I have attached it to this email.
In your message you mentioned you had completed these forms so maybe someone in your office has them and they just need to be scanned in and uploaded.
If you are having trouble uploading the forms please email them to me and I will upload them for you.
I need these 2 items before I can start the prescreen.
Please let me know how we can be of any assistance.
Thank you
Adele J. Schaffeld-Griffin
City of Boise
Plans Examiner II
###-####
|
Telephone call | | | 6/28/2013 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
Called Ryan and left voice mail checking in on status of uploading check list to begin pre screen.
|
Application received | | | 6/21/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 21 2013 10:47AM
|
Intake Approval | | | 6/21/2013 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
Please upload the completed 520 Check list.
Please upload the completed 304 form.
I need this information to begin the pre screen.
Thank you
|