Third Notice | | 6/10/2014 | 7/7/2014 | | DONE |
Christina Prado
|
|
|
final value completed 7-7-14
|
Second Notice | | 5/4/2014 | 6/5/2014 | | DONE |
Christina Prado
|
|
|
|
First Notice | | 4/10/2014 | 4/24/2014 | | DONE |
|
|
|
|
BLD-Final | 3/27/2014 | 3/31/2014 | 3/31/2014 | A | PASS |
Bob Archibald
|
|
|
Troy Phone #: ###-####. Corrections made OK.
|
Permanent Occupancy | | | 3/31/2014 | | DONE |
Christina Prado
|
|
|
|
FIRE-Final Inspection | 3/27/2014 | 3/28/2014 | 3/28/2014 | P | PASS |
Forrest France
|
|
|
Previous correction items verified for completion. Fire life safety passed.
|
FIRE-Final Inspection | 3/26/2014 | 3/27/2014 | 3/27/2014 | A | FAIL |
Forrest France
|
|
|
Missing exit signs at five locations per approved plans, need to repair one existing exit sign, replace pin at one self-closing door, missing closure at the storage room door per key notes. Remainder of walkthrough passed.
|
BLD-Final | 3/27/2014 | 3/27/2014 | 3/27/2014 | P | CANC |
Dave Hannah
|
|
|
Troy Phone #: ###-####
|
BLD-Framing/Rough-in | 1/24/2014 | 1/24/2014 | 1/27/2014 | P | PASS |
Bob Archibald
|
|
|
Rick Phone #: ###-####
|
BLD-Framing/Rough-in | 1/15/2014 | 1/15/2014 | 1/15/2014 | P | PART |
Mike Jordan
|
|
|
Rick Phone #: ###-####. Restroom walls, 0ft. to 10ft. elevation only ok to cover.
|
Issue PAID IN FULL permit | | | 12/2/2013 | | DONE |
Christina Prado
|
|
|
|
OVERRIDE | | | 11/8/2013 | | |
|
|
|
|
Plan assigned to (SRZ) | 10/29/2013 | 10/29/2013 | 11/8/2013 | | PASS |
Sam Zahorka
|
|
|
|
Case Summary (BLD) | | | 11/8/2013 | | DONE |
Sam Zahorka
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/8/2013 | | DONE |
Sam Zahorka
|
|
|
|
Telephone call | | | 11/8/2013 | | DONE |
Tisha Gallop
|
|
|
left vm for Chris at Design West, need new cert of value since on last resub scope of work decreased.
|
Print Occupancy Form | | | 11/8/2013 | | DONE |
|
|
|
|
Telephone call | | | 11/8/2013 | | DONE |
Tisha Gallop
|
|
|
e-mailed Chris Vondemkamp resub ready, new fee calc, need GC and RP.
|
Permit Ready to Issue | | | 11/8/2013 | | DONE |
Tisha Gallop
|
|
|
|
Routing - PLUMBING | 11/4/2013 | | 11/7/2013 | | PASS |
Daryl Spivey
|
|
|
Additional resubmittals received prior to permit issuance. See transmittal for changes.
|
Routing - PLAN CHECK | 10/29/2013 | | 11/4/2013 | | PASS |
Sam Zahorka
|
|
|
Additional resubmittals received prior to permit issuance. See transmittal for changes.
|
Plan resubmittals received | | | 11/1/2013 | | |
|
|
|
11-1-13 received one copy of sheet 2.00,3.00,3.30,3.31 sent to Sam Z
NOTE: These resubmittals sheets are the same as the resubmittals received on 10/29/13. Sheets date stamped received on 11/1/13 are additional copies of the 10/29/13 resubs.
|
CHANGE STATUS TO (REV) | | | 10/30/2013 | | DONE |
Sam Zahorka
|
|
|
|
Plan resubmittals received | | | 10/29/2013 | | DONE |
Sam Zahorka
|
|
|
|
OVERRIDE | | | 10/4/2013 | | |
|
|
|
|
Plan assigned to (SRZ) | 9/23/2013 | 9/23/2013 | 10/4/2013 | | PASS |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 9/27/2013 | | 10/4/2013 | | PASS |
Sam Zahorka
|
|
|
Resubmittals received prior to permit issuance. See transmittal for changes.
|
Telephone call | | | 10/4/2013 | | DONE |
Tisha Gallop
|
|
|
called William Hamlin and left vm permit is ready, fee due, and need GC/form and RP.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/4/2013 | | DONE |
Sam Zahorka
|
|
|
|
Print Occupancy Form | | | 10/4/2013 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 10/4/2013 | | DONE |
Tisha Gallop
|
|
|
|
Routing - PLUMBING | 9/25/2013 | | 9/27/2013 | | PASS |
Daryl Spivey
|
|
|
Resubmittals received prior to permit issuance. See transmittal for changes.
413.1 and 418.0 ISPC requires limitation of 120 degree water supplied to public lavs and showers.
|
Routing - Design Review | 9/27/2013 | | 9/27/2013 | | PASS |
Josh Wilson
|
|
|
Ok- removal/infill of windows deleted from scope of permit
|
Case Summary (BLD) | | | 9/26/2013 | | DONE |
Sam Zahorka
|
|
|
|
Case Summary (BLD) | | | 9/26/2013 | | DONE |
Sam Zahorka
|
|
|
|
Routing PW Sewer Rating | 9/25/2013 | | 9/25/2013 | | PASS |
Connie Baumgartner
|
|
|
|
Routing - PUBLIC WORKS | 9/25/2013 | | 9/25/2013 | | PASS |
Connie Baumgartner
|
|
|
Resubmittals received prior to permit issuance. See transmittal for changes.
|
Plan resubmittals received | | | 9/23/2013 | | DONE |
Christina Prado
|
|
|
received two sets of revised plan sheets marked 1, 2, ,3, 3.30, 3.31, 3.60, 5.20, MG1.00, MG2.00, MG3.00, MG3.10, M1.00, M1.10, M2.00, M2.10, M3.00, M4.00, P1.00, P2.00, P2.10, P3.00, P3.10, P4.00, EG1.0, E1.00, E2.00, E3.00, E4.00, E5.00 & E6.00;Taken to Sam for futher review
|
OVERRIDE | | | 9/9/2013 | | |
|
|
|
|
Plan assigned to (SRZ) | 8/23/2013 | 8/23/2013 | 9/9/2013 | | PASS |
Sam Zahorka
|
|
|
Plan revisions received prior to issuance.
|
Case Summary (BLD) | | | 9/9/2013 | | DONE |
Sam Zahorka
|
|
|
|
Case Summary (BLD) | | | 9/9/2013 | | DONE |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 8/23/2013 | | 9/9/2013 | | PASS |
Sam Zahorka
|
|
|
Plan changes prior to issuance.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/9/2013 | | DONE |
Sam Zahorka
|
|
|
|
Print Occupancy Form | | | 9/9/2013 | | DONE |
Barbara Stitt
|
|
|
|
Permit Ready to Issue | | | 9/9/2013 | | DONE |
Barbara Stitt
|
|
|
|
Plan resubmittals received | | | 8/23/2013 | | |
|
|
|
8-23-13 received 2 copies of sheets 1.00,2.00,3.00,3.30,3.31,3.60,3.20,5.20,mg1.00,mg2.00,mg3.00mg3.10,mm1.00,m1.10,m2.00,m2.10,m3.00,m4.00,p1.00,p2.00,p2.10,p3.00,p3.10,p4.00,eg1.0,e1.00,e2.00,e3.00,e4.00,e5.00,e6.00 sent to Sam Z
|
CHANGE STATUS TO (REV) | | | 8/23/2013 | | DONE |
Sam Zahorka
|
|
|
|
OVERRIDE | | | 8/8/2013 | | |
|
|
|
|
Plan assigned to (SRZ) | 7/5/2013 | 7/5/2013 | 8/8/2013 | | PASS |
Sam Zahorka
|
|
|
1st review completed. Interfaith Sanctuary
|
Telephone call | | | 8/8/2013 | | DONE |
Barbara Stitt
|
|
|
Called and taked w/Chris told him permit is ready, fees due, need GC & RP info on 8-8-13 @ 11:10am///BAS
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/8/2013 | | DONE |
Sam Zahorka
|
|
|
|
Print Occupancy Form | | | 8/8/2013 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 8/8/2013 | | DONE |
Barbara Stitt
|
|
|
|
Case Summary (BLD) | | | 8/7/2013 | | DONE |
Sam Zahorka
|
|
|
|
Routing - Design Review | 8/7/2013 | | 8/7/2013 | | PASS |
Josh Wilson
|
|
|
Ok for exterior changes per CZC13-00163. JGW 8-7-13
|
Routing - Addressing | 7/5/2013 | | 8/7/2013 | | CANC |
Sam Zahorka
|
|
|
Addressing did not need to review per April Wing.
|
Routing - PLAN CHECK | 7/29/2013 | | 8/7/2013 | | PASS |
Sam Zahorka
|
|
|
|
Plan resubmittals received | | | 8/6/2013 | | DONE |
Tisha Gallop
|
|
|
received two copies of plan sheets M1.00, M2.00, M4.00, E4.00, E5.00, E6.00; taken to Sam Zahorka.
|
Routing - FIRE | 7/26/2013 | | 7/29/2013 | | PASS |
Scott Arellano
|
|
|
Attached Fire Review comments to plans.
|
1st review completed | | | 7/29/2013 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 7/12/2013 | | 7/26/2013 | | FAIL |
Sam Zahorka
|
|
|
|
Plan resubmittals received | | | 7/24/2013 | | DONE |
Christina Prado
|
|
|
received two complete revised sets of plans marked 1.00, 2.00, 3.00, 3.30, 3.31, 3.60, 5.20, MG1.00, MG2.00, MG3.00, MG3.10, M1.00, M1.10, M2.00, M2.10, M3.00, M4.00, P1.00, P2.00, P2.10, P3.00, P3.10, P4.00, EG1.0, E1.00, E2.00, E3.00, E4.00, E5.00 & E6.00;Plan sets taken to Sam for further review
|
Routing - Design Review | 7/11/2013 | | 7/12/2013 | | PASS |
Sarah Schafer
|
|
|
Sarah Schafer - CZC13-00163
Approved with only interior changes. No changes to the windows allowed as part of this permit.
|
Routing - PLUMBING | 7/9/2013 | | 7/11/2013 | | PASS |
Bill VanDegrift
|
|
|
413.1 and 418.0 ISPC requires limitation of 120 degree water supplied to public lavs and showers.
Per plan and ISPC.
|
Routing - Erosion and Sediment | 7/8/2013 | | 7/9/2013 | | PASS |
Kimberly M. Johnson
|
|
|
waiver approved
|
Routing PW Sewer Rating | 7/8/2013 | | 7/8/2013 | | PASS |
Connie Baumgartner
|
|
|
|
Routing - PUBLIC WORKS | 7/8/2013 | | 7/8/2013 | | PASS |
Connie Baumgartner
|
|
|
|
Pending Assignment by JCB | 7/3/2013 | | 7/5/2013 | | DONE |
Jason Blais
|
|
|
|
Application received | | 7/3/2013 | 7/3/2013 | | DONE |
|
|
|
|
Intake Approval | | | 7/3/2013 | | PASS |
Sam Zahorka
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 7/3/2013 | | DONE |
Christina Prado
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 7/3/2013 | | DONE |
Christina Prado
|
|
|
|