Third Notice | | 7/14/2014 | 7/28/2014 | | DONE |
Christina Prado
|
|
|
completed 7-28-14
|
Second Notice | | 6/15/2014 | 7/9/2014 | | DONE |
|
|
|
|
First Notice | 5/15/2014 | 5/15/2014 | 6/5/2014 | | DONE |
Mike Jordan
|
|
|
|
BLD-Final | 5/14/2014 | 5/15/2014 | 5/15/2014 | A | PASS |
Mike Jordan
|
|
|
Eric Phone #: ###-####
|
DOC - Permit Finaled | 5/15/2014 | 5/15/2014 | 5/15/2014 | P | PASS |
Mike Jordan
|
|
|
|
FIRE-Final Inspection | 5/2/2014 | 5/5/2014 | 5/5/2014 | P | PASS |
Forrest France
|
|
|
For previous correction items listed per C. Hanson
|
Zoning Approval | 5/2/2014 | 5/2/2014 | 5/2/2014 | | PASS |
Josh Wilson
|
|
|
|
FIRE-Final Inspection | 2/14/2014 | 2/18/2014 | 2/18/2014 | A | FAIL |
Craig D. Hanson
|
|
|
1. #'s need posted on outside of building. 2. Exit signs w/bug eyes need added (total 3) 3. Fire extinguisher needs mounted and serviced 4.Door hung wrong way as per plan and needs to be changed towards the egress route. 5. "doors to remain unlocked..." signs to be added (x3)
|
BLD-Final | 2/10/2014 | 2/11/2014 | 2/11/2014 | P | NR |
Mike Jordan
|
|
|
Please call ahead to meet Eric on site for final - Eric Phone #: ###-####. Called and spoke to eric, noted that fire/life/safety final not yet completed and a zoning final is also required.
|
FIRE-Final Inspection | 2/10/2014 | 2/11/2014 | 2/11/2014 | A | FAIL |
Troy Cobbley
|
|
|
I left message on the contacts voice mail that I was on the way. Stopped at site and spoke to receptionist and Eric the dentist but they had no plans and it was the wrong Eric. No inpsection was performed. Eric Phone #: ###-####
|
BLD-Final | 1/16/2014 | 1/21/2014 | 1/22/2014 | A | NR |
Mike Jordan
|
|
|
call for access - Eric Phone #: ###-####. Called eric and left message, needs life/safety and zoning finals.
|
BLD-Framing/Rough-in | 9/26/2013 | 9/27/2013 | 9/27/2013 | P | PASS |
Jim Storey
|
|
|
Chad Phone #: ###-####
|
BLD-Framing/Rough-in | 9/5/2013 | 9/6/2013 | 9/6/2013 | P | PASS |
Mike Jordan
|
|
|
partial r/i -- Chad Phone #: ###-####. Interior wood framed wals for phase 1 ok.
|
BLD-Conference | 8/1/2013 | 8/2/2013 | 8/2/2013 | A | DONE |
Mike Jordan
|
|
|
9am .. chad Phone #: ###-####
|
OVERRIDE | | | 8/1/2013 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 8/1/2013 | | DONE |
Tisha Gallop
|
|
|
|
Inspection Record Card- Bld | | | 8/1/2013 | | DONE |
Tisha Gallop
|
|
|
|
Permit Ready to Issue | | | 8/1/2013 | | DONE |
Tisha Gallop
|
|
|
|
1st review completed | | | 7/26/2013 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/26/2013 | | DONE |
|
|
|
|
Plan assigned to (AJS) | 7/15/2013 | | 7/26/2013 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
Leve 2 Due 7/26
|
Routing - PLAN CHECK | 7/15/2013 | | 7/26/2013 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
Routing PW Sewer Rating | 7/16/2013 | | 7/26/2013 | | PASS |
Connie Baumgartner
|
|
|
approved in e plan
|
Routing - FIRE | 7/25/2013 | 7/25/2013 | 7/25/2013 | | PASS |
Scott Arellano
|
|
|
Attached comments to plans.
|
Routing - PLUMBING | 7/15/2013 | | 7/18/2013 | | PASS |
Daryl Spivey
|
|
|
Provide tempered water at lavs and may require additional backflow protection.
|
Routing - PLANNING | 7/15/2013 | | 7/17/2013 | | PASS |
Josh Wilson
|
|
|
OK per CZC13-00144
|
Routing - Addressing | 7/15/2013 | | 7/17/2013 | | PASS |
Jason C. Taylor
|
|
|
|
Routing - PUBLIC WORKS | 7/15/2013 | | 7/16/2013 | | PASS |
Beverly Mountain
|
|
|
|
Routing - Erosion and Sediment | 7/15/2013 | | 7/16/2013 | | PASS |
Kimberly M. Johnson
|
|
|
waiver approved
|
Routing PW Drainage | 7/16/2013 | | 7/16/2013 | | PASS |
Brian Murphy
|
|
|
|
Intake Approval | | | 7/15/2013 | | PASS |
Tim L. Woodard
|
|
|
|
Application received | | | 7/12/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 12 2013 11:15AM
|
Intake Approval | | | 7/12/2013 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
Please upload a completed com check for the lighting being installed.
Lighting compliance COMcheck signed & printed on the plans if new lighting is being installed or when the tenant use changes or specific room uses change [Page ___________________________]
|