BLD-Final | 9/6/2013 | 9/6/2013 | 9/6/2013 | P | NR |
Jim Sly
|
|
|
Curtis Phone #: ###-#### Need fire final......
|
BLD-Final | 8/23/2013 | 8/26/2013 | 8/26/2013 | P | NR |
Jim Sly
|
|
|
Craig Phone #: ###-####
|
FIRE-Final Inspection | 8/23/2013 | 8/26/2013 | 8/26/2013 | A | FAIL |
Troy Cobbley
|
|
|
No city approved plans on site. I did a quick walk through with Craig on the phone and I found pendant sprinkler heads overspaced on the west side of the new wall at the Lobby (small room rule can not be used in a merchantile space), one pendant in the restroom may be too close to the wall, provide one fire extinguisher in the new space since the other exceed 75' travel distance, and remove the keyed hardware from the main exit door in the new space and provide single action or get plan review approval to delete the store front door.
|
BLD-Framing/Rough-in | 8/9/2013 | 8/9/2013 | 8/9/2013 | P | PASS |
Jim Storey
|
|
|
cory Phone #: ###-####
|
Issue PAID IN FULL permit | | | 8/9/2013 | | DONE |
|
|
|
|
Print Occupancy Form | | | 8/9/2013 | | DONE |
|
|
|
|
Plan assigned to (CDM) | 7/30/2013 | 7/30/2013 | 8/7/2013 | | PASS |
Carl D Madsen
|
|
|
|
Routing - PLAN CHECK | 7/30/2013 | | 8/7/2013 | | PASS |
Carl D Madsen
|
|
|
|
Routing - PUBLIC WORKS | 7/30/2013 | | 8/7/2013 | | PASS |
Connie Baumgartner
|
|
|
|
1st review completed | | | 8/7/2013 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/7/2013 | | DONE |
|
|
|
|
Routing PW Sewer Rating | 7/30/2013 | | 8/7/2013 | | PASS |
Connie Baumgartner
|
|
|
|
Permit Ready to Issue | | | 8/7/2013 | | DONE |
|
|
|
|
Routing - Addressing | 7/30/2013 | | 7/31/2013 | | PASS |
Jason C. Taylor
|
|
|
|
Intake Approval | | | 7/30/2013 | | PASS |
Tim L. Woodard
|
|
|
|
Application received | | | 7/23/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 23 2013 3:57PM
|