Second Notice | | 9/7/2014 | 10/6/2014 | | DONE |
|
|
|
interoffice mail to Scott Canning
|
First Notice | 7/28/2014 | 7/28/2014 | 8/28/2014 | | DONE |
Dave Hannah
|
|
|
interoffice mail to Scott Canning
|
BLD-Final | 7/24/2014 | 7/28/2014 | 7/28/2014 | A | PASS |
Dave Hannah
|
|
|
Keith ###-####
|
DOC - Permit Finaled | 7/28/2014 | 7/28/2014 | 7/28/2014 | P | PASS |
Dave Hannah
|
|
|
|
BLD-Final | 7/24/2014 | 7/24/2014 | 7/24/2014 | P | PASS |
Tony Young
|
|
|
Please call at least 15 mins prior to inspection-Keith Phone #: ###-####
|
FIRE-Final Inspection | 7/24/2014 | 7/24/2014 | 7/24/2014 | P | PASS |
Troy Cobbley
|
|
|
life safety passed
|
BLD-Final | 7/10/2014 | 7/11/2014 | 7/11/2014 | A | NR |
Dave Hannah
|
|
|
Kieth-call to meet Phone #: ###-####
|
FIRE-Final Inspection | 7/10/2014 | 7/11/2014 | 7/11/2014 | A | FAIL |
Troy Cobbley
|
|
|
Strobe coverage has been blocked by the new door. Provide additional coverage with-in 15'-0" of the end of the corridor including coverage in the pocket. See NFPA 72 18.5.5.5.5.
Smoke detector coveage has been blocked by the new door. Provide additional smoke detector coverage as per NFPA 72 17.5.3.1 and 17.6.3.1.1.
Provide city approved plans and small documents.
|
Fees Due Hold | 9/17/2013 | | 9/18/2013 | | DONE |
Rita DeYoung
|
|
|
|
Plan assigned to (TLW) | 9/6/2013 | | 9/16/2013 | | PASS |
Tim L. Woodard
|
|
|
|
Routing - PLAN CHECK | 9/6/2013 | | 9/16/2013 | | PASS |
Tim L. Woodard
|
|
|
|
1st review completed | | | 9/16/2013 | | DONE |
Tim L. Woodard
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/16/2013 | | DONE |
Tim L. Woodard
|
|
|
|
Permit Ready to Issue | | | 9/16/2013 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/16/2013 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 9/16/2013 | | DONE |
|
|
|
|
Intake Approval | | | 9/6/2013 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
Application received | | | 8/30/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 30 2013 2:43PM
|