Second Notice | | 12/7/2013 | 12/12/2013 | | DONE |
|
|
|
|
First Notice | 11/8/2013 | 11/8/2013 | 11/27/2013 | | DONE |
Jim Sly
|
|
|
|
BLD-Final | 11/7/2013 | 11/8/2013 | 11/8/2013 | A | PASS |
Jim Sly
|
|
|
Jason Phone #: ###-####
|
DOC - Permit Finaled | 11/8/2013 | 11/8/2013 | 11/8/2013 | P | PASS |
Jim Sly
|
|
|
|
BLD-Final | 11/5/2013 | 11/5/2013 | 11/5/2013 | P | NR |
Jim Sly
|
|
|
jason Phone #: ###-#### Need Mech. and Plumb. finals.
|
FIRE-Final Inspection | 11/4/2013 | 11/5/2013 | 11/5/2013 | A | PASS |
Troy Cobbley
|
|
|
life safety passed
|
FIRE-Final Inspection | 10/31/2013 | 11/1/2013 | 11/1/2013 | A | CANC |
Craig D. Hanson
|
|
|
request 8:30 am // Jason Phone #: ###-####. Canceled by Jason 11/01
|
FIRE-Final Inspection | 10/30/2013 | 10/30/2013 | 10/30/2013 | P | FAIL |
Troy Cobbley
|
|
|
life safety will be ok to pass when the project related fire alarm permit has been addressed.
|
BLD-Framing/Rough-in | 10/24/2013 | 10/25/2013 | 10/25/2013 | A | PASS |
Jim Sly
|
|
|
Ceiling grid insepction please-Jason Phone #: ###-####
|
BLD-Framing/Rough-in | 9/24/2013 | 9/25/2013 | 9/25/2013 | A | PART |
Jim Sly
|
|
|
Jason Phone #: ###-#### Long..... East to West partiotion wall OK to cover.
|
Telephone call | | | 9/18/2013 | | DONE |
|
|
|
value stays same
|
Permit Ready to Issue | | | 9/18/2013 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 9/18/2013 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Bld | | | 9/18/2013 | | DONE |
Christina Prado
|
|
|
|
Plan assigned to (AJS) | 9/12/2013 | 9/12/2013 | 9/16/2013 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
Due 9/18 e plan
|
Routing - PLAN CHECK | 9/12/2013 | | 9/16/2013 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
1st review completed | | | 9/16/2013 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/16/2013 | | DONE |
|
|
|
|
Intake Approval | | | 9/12/2013 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
Application received | | | 9/10/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 10 2013 9:58AM
|
Intake Approval | | | 9/10/2013 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
Please submit for 304, Design Professional of Record
Please provide signature of design professional on seal on the plan sheets. Digital signature is acceptable.
Please re name the plan sheets in required standard for. The discipline shall be first then number followed by name and then any other identifying information. A002.1- 1st floor plan
Please provide a cross section of the new interior partition wall. Please include the required bracing for the top of the wall in the detail.
|