Information based on query as of Saturday, June 29, 2024.
Permit Information
Permit NumberBLD14-00826
StatusFinaled
Name WESTMINSTER II
Site Address 2943 N SELKIRK DR
Project Name 
Customer Number 
ePlanReviewNo
Description
***Plan modification #3, to change the theater room into bedroom 5 and adding two window openings of which one to be emergency escape and rescue egress*** **Plan modification #2 adding 808 sq. ft. to modified lower floor area within existing engineered foundation wall area to include (new 425 sq. ft. theater room and new 383 sq. ft. by enlarging game room shifting exterior wall at bedroom #4, bathroom and storage room over to the right** *Plan modification #1 dated 2/4/2015 adding engineered helical piers per the approved plans* WUI Zone A, Class A Roof, Permit for the construction of a new 3763 sq. ft., two story (first story 2373 sq. ft., lower level 1390 sq. ft.) single family dwelling with 5 bedrooms, 5 bathrooms, approximately 1,192 sq. ft. of covered patio/porch and a 748 sq. ft. attached garage per the approved plans, plan review report and any notations. R-1B zoning and setbacks per planning. Note: Revised grading plan submitted 12/9/15 JG
A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable must be approved by Public Works prior to scheduling a footing inspection. Call Jason Taylor at 384-3946

Prior to obtaining a final for the permit, the roof storm drainage system must be inspected by Public Works. Call Jason Taylor at 384-3946.
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final12/29/201512/30/201512/30/2015ADONE
DetailsTony Young
Call for access // Josh Phone #: ###-####
BLD-Final12/28/201512/29/201512/29/2015APASS
DetailsTony Young
Call for access // Josh Phone #: ###-####
DOC - Permit Finaled12/29/201512/29/201512/29/2015PPASS
DetailsTony Young
bond in place,,
PubWorks Occupancy Approval12/29/201512/29/201512/29/2015 DONE
DetailsJason C. Taylor

A bond for the sites final grading, retaining walls, and re-vegetation has been received by Public Works. Occupancy may be approved by the building department. Jason Taylor ###-####.
BLD-Final12/23/201512/24/201512/24/2015ANR
DetailsTony Young
Josh Phone #: ###-####,, walk through only,, need hill side,, steps out 2 doors
CHANGE STATUS TO (ISS)  12/23/2015 DONE
(F) Reprint permit  12/23/2015 DONE
OVERRIDE  12/11/2015  
Plan assigned to (JG)12/8/201512/8/201512/11/2015 PASS
DetailsJavier Guzman
Grading resubmittals
Routing - PLAN CHECK12/8/2015 12/11/2015 PASS
DetailsJavier Guzman
Telephone call  12/11/2015 DONE
Left a message stating that the plan mod is ready to be picked up and the fee amount that is due.
Case Summary (BLD)  12/11/2015 DONE
DetailsJavier Guzman
PLANS/APPL TAKEN TO FRONT DESK  12/11/2015 DONE
Case Summary (BLD)  12/11/2015 DONE
DetailsJavier Guzman
Permit Ready to Issue  12/11/2015 DONE
DO NOT REISSUE PLAN MOD
Routing PW Grading-Hillside  12/9/2015 PASS
DetailsJason C. Taylor
New grading plan approved. Retaining wall repairs will need to be submitted prior to installation (micro-piles). JCT
Plan Modification Accepted  12/8/2015 DONE
received (3) copies of Grading & Drainage Plan (C1)
BLD-Framing/Rough-in10/6/201510/7/201510/7/2015APART
DetailsDave Hannah
Josh Phone #: ###-#### ok to cover bathroom addn area in basement nrw change
Plan assigned to (JG)9/23/20159/23/201510/6/2015 PASS
DetailsJavier Guzman
1st review completed, need engineering and pass Mech, Plan Mod
Routing - PLAN CHECK10/5/2015 10/6/2015 PASS
DetailsJavier Guzman
Case Summary (BLD)  10/6/2015 DONE
DetailsJavier Guzman
Plan Reviewer's activity  10/6/2015 DONE
DetailsJavier Guzman
spoke with Joshua Baker and told him to bring me in the field set of plans so that i may red line the elevation sheet for the new window openings created in plan mod #3
PLANS/APPL TAKEN TO FRONT DESK  10/6/2015 DONE
CHANGE STATUS TO (ISS)  10/6/2015 DONE
(F) Reprint permit  10/6/2015 DONE
Routing - MECHANICAL10/5/2015 10/5/2015 PASS
DetailsTroy James
Plan resubmittals received  10/2/2015 DONE
received one Manual J- put on Javier's desk with the plans
Plan resubmittals received  10/1/2015 DONE
resubmittals received 2 sets of eng calcs-took to JG
Routing - PLAN CHECK9/23/2015 9/30/2015 FAIL
DetailsJavier Guzman
Need engineering for new window openings and pass mechanical
Routing PW Grading-Hillside9/28/2015 9/30/2015 CANC
DetailsJason C. Taylor
No review necessary. JCT
Routing - MECHANICAL9/28/2015 9/30/2015 FAIL
DetailsTroy James
emailed applicant to provide revised manual j report
Plan Modification Accepted  9/23/2015 DONE
Changing the movie room into a bed room with bath. Two copies of sheets 3, 10 and 12. Taken to Javier
BLD-Conference8/4/20158/5/20158/5/2015APEND
DetailsTony Young
under floor venting will be required
BLD-Energy code compliance8/4/20158/4/20158/4/2015PPASS
DetailsTony Young
Jason Phone #: ###-####
BLD-Energy code compliance8/3/20158/3/20158/3/2015PNR
DetailsTony Young
Insulation // Josh Phone #: ###-####
BLD-Framing/Rough-in8/3/20158/3/20158/3/2015PPASS
DetailsTony Young
Josh Phone #: ###-####
BLD-Framing/Rough-in7/14/20157/15/20157/15/2015ANR
DetailsTony Young
Josh Phone #: ###-####,, still waiting on fixing correction notice
BLD-Framing/Rough-in7/13/20157/14/20157/14/2015ANR
DetailsTony Young
Josh Phone #: ###-####
BLD-Framing/Rough-in7/13/20157/13/20157/13/2015PFAIL
DetailsTony Young
Josh Phone #: ###-####,, correction notice posted
BLD-Conference7/10/20157/10/20157/11/2015PCANC
DetailsTony Young
frame walk through
BLD-Framing/Rough-in7/9/20157/10/20157/10/2015ANR
DetailsTony Young
BLD-Framing/Rough-in7/9/20157/9/20157/9/2015PNR
DetailsTony Young
need trades,, seal package
CHANGE STATUS TO (ISS)  7/9/2015 DONE
OVERRIDE  7/8/2015  
Plan assigned to (JG)4/22/20154/22/20157/8/2015 PASS
DetailsJavier Guzman
1st review completed, Plan Mod
Routing - PLAN CHECK7/8/2015 7/8/2015 PASS
DetailsJavier Guzman
Case Summary (BLD)  7/8/2015 DONE
DetailsJavier Guzman
PLANS/APPL TAKEN TO FRONT DESK  7/8/2015 DONE
Permit Ready to Issue  7/8/2015 DONE
plan mod fees due; do NOT re-issue
Plan resubmittals received  7/6/2015 DONE
DetailsChristina Prado
Received two sets of revised Foundation plan marked 2; Plans stamped and taken to JG for additional review
BLD-Wall Bracing6/17/20156/17/20156/17/2015PPASS
DetailsTony Young
Shear // Josh Phone #: ###-####,, exterior ok
Routing - MECHANICAL6/11/2015 6/12/2015 PASS
DetailsTroy James
Routing - PLAN CHECK6/11/2015 6/11/2015 FAIL
DetailsJavier Guzman
Plan resubmittals received  6/9/2015 DONE
resubmittal received 2 each sheet 1,2,3,4,5,6,7,8,9,10,11,12-2 engineered calcs for cantilevered retaining wall 2 manuals-took to JG
BLD-Footing4/24/20154/27/20154/27/2015APART
DetailsTony Young
ok to pour interior pony wall footings and west piers over helicals,, work in progress
Routing - PLAN CHECK4/27/2015 4/27/2015 FAIL
DetailsJavier Guzman
Routing - PLAN CHECK4/22/2015 4/27/2015 FAIL
DetailsJavier Guzman
emailed applicant review report of modification 4/27/2015
BLD-Footing4/24/20154/24/20154/24/2015PNR
DetailsTony Young
Phone #: ###-####
Plan Modification Accepted  4/22/2015 DONE
plan mod received 2 of each sheet # 3 & 2 as well as approved engineering calcs, site consulting, ICC eval., acc & teremination devices-took to JG
BLD-Foundation4/14/20154/14/20154/14/2015PPASS
DetailsPhil Shearer
Adam Phone #: ###-####
BLD-Footing4/10/20154/10/20154/10/2015PPASS
DetailsJim Sly
Going to pour between 1230 and 1 // Adam Phone #: ###-####
PubWorks Subgrade Approval4/10/20154/10/20154/10/2015 DONE
DetailsJason C. Taylor

*GARAGE FOOTINGS**A letter from the applicant’s geotechnical engineer indicating that the footing subgrade is acceptable has been received by Public Works. Footing inspection may be scheduled with the Building Department. Jason Taylor ###-####.
BLD-Foundation3/20/20153/23/20153/23/2015APART
DetailsTony Young
Adam Phone #: ###-####,, basement walls ok
BLD-Wall Bracing3/20/20153/20/20153/20/2015PPART
DetailsTony Young
Adam Phone #: ###-####,, wanted a basement wall inspection,, work in progress,, ok
BLD-Footing3/10/20153/10/20153/10/2015PPART
DetailsTony Young
Adam-pour time 2:30 Phone #: ###-####,, work in progress,,, helical piers in place within footing
BLD-Footing3/9/20153/9/20153/10/2015PDEFR
DetailsTony Young
Adam-pour time 2:30 Phone #: ###-####
PubWorks Subgrade Approval3/10/20153/10/20153/10/2015 DONE
DetailsJason C. Taylor
*BASEMENT OR LOWER LEVEL FOUNDATIONS ONLY EXCLUDING 5 ISOLATED PADS TO NORTH***A letter from the applicant’s geotechnical engineer indicating that the footing subgrade is acceptable has been received by Public Works. Footing inspection may be scheduled with the Building Department. Jason Taylor ###-####.
CHANGE STATUS TO (ISS)  2/5/2015 DONE
DetailsCandy A. Nichols
OVERRIDE  2/4/2015  
Plan assigned to (JG)1/30/20151/30/20152/4/2015 PASS
DetailsJavier Guzman
foundation Plan Mod
Telephone call  2/4/2015 DONE
DetailsCandy A. Nichols
called to let know plan mod permit is ready and how much is owed-left message on machine
Case Summary (BLD)  2/4/2015 DONE
DetailsJavier Guzman
PLANS/APPL TAKEN TO FRONT DESK  2/4/2015 DONE
Permit Ready to Issue  2/4/2015 DONE
do not re-issue
Plan Modification Accepted  1/29/2015 DONE
Two copies of Cal. packet and two copies of sheet 2
Issue PAID IN FULL permit  9/12/2014 DONE
DetailsTisha Gallop
OVERRIDE  9/8/2014  
Telephone call  9/8/2014 DONE
DetailsChristina Prado
called George to advise permit is ready and gave fees due
Permit Ready to Issue  9/8/2014 DONE
DetailsChristina Prado
Routing - FIRE9/5/20149/5/20149/5/2014 PASS
DetailsScott Arellano
This structure has been reviewed for fire department vehicle access.
Plan assigned to (JG)4/17/20144/17/20149/5/2014 PASS
DetailsJavier Guzman
1st review completed, Pending planning and hillside, Due 5/06 M L2 Hillside**
Case Summary (BLD)  9/5/2014 DONE
DetailsJavier Guzman
PLANS/APPL TAKEN TO FRONT DESK  9/5/2014 DONE
Inspection Record Card- Bld  9/5/2014 DONE
DetailsCandy A. Nichols
Routing - PLAN CHECK8/1/2014 9/5/2014 PASS
DetailsJavier Guzman
Routing - PLANNING9/5/2014 9/5/2014 PASS
DetailsJoshua Johnson
Routing PW Grading-Hillside9/3/2014 9/4/2014 PASS
DetailsJason C. Taylor

A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable must be approved by Public Works prior to scheduling a footing inspection. Call Jason Taylor at ###-####

Prior to obtaining a final for the permit, the roof storm drainage system must be inspected by Public Works. Call Jason Taylor at ###-####.
Plan resubmittals received  9/2/2014 DONE
DetailsTisha Gallop
received three copies of C1; taken to Javier
Routing - PLAN CHECK5/6/2014 8/1/2014 FAIL
DetailsJavier Guzman
Pending planning and Hillside approval
Plan resubmittals received  7/23/2014 DONE
DetailsChristina Prado
Received two full sets of revised plan sheets marked 1,2,3,4,5,6,7,8,9,10,11 & 12; Plans taken to Javier for further review
Plan resubmittals received  5/19/2014 DONE
DetailsChristina Prado
Received three copies of revised structural calcs;taken to Javier for further review
Plan resubmittals received  5/15/2014 DONE
DetailsTisha Gallop
received three copies of Geotech report and addendum; taken to Javier
1st review completed  5/6/2014 FAIL
DetailsJavier Guzman
Routing - PLAN CHECK  5/6/2014 FAIL
DetailsJavier Guzman
emailed review report to applicant
Routing - Erosion and Sediment4/24/2014 4/25/2014 PASS
DetailsEvan Jenkins
Routing - MECHANICAL  4/24/2014 PASS
DetailsTroy James
Routing - PUBLIC WORKS4/21/2014 4/22/2014 PASS
DetailsConnie Baumgartner
Route to Impact Fee Review4/17/20144/20/20144/21/2014 PASS
DetailsCindy M. Gould
Routing PW Grading-Hillside4/21/2014 4/21/2014 FAIL
DetailsJason C. Taylor
Needs revised grading plans, geotechnical reports, retaining wall calculations. Jason Taylor ###-####.
Routing - Addressing4/18/2014 4/21/2014 PASS
DetailsJason C. Taylor
Application received 4/8/20144/17/2014 DONE
DetailsTisha Gallop
Recd Pcfee & Taken To Pln CK  4/17/2014 DONE
DetailsBarbara Stitt
Intake Approval  4/17/2014 PASS
DetailsBarbara Stitt
Plans ACCEPTED BY PLAN TECH  4/17/2014 DONE
DetailsBarbara Stitt
Intake Approval  4/8/2014 FAIL
DetailsTisha Gallop
needs esc plans/narrative, wall bracing, WUI details, 1 extra full size copy of civil sheet.
Routing - PLANNING    FAIL
Site Plan needs to match grading plan from Hillside Approval. Driveway is too wide within the front setback.
Routing - PLANNING7/25/2014   FAIL
DetailsJoshua Johnson
Fail, applicant needs house plans to match grading plan.