Case Summary (BLD) | | | 1/6/2015 | | DONE |
|
|
|
|
First Notice | | 12/29/2014 | 1/2/2015 | | DONE |
|
|
|
|
BLD-Final | 12/19/2014 | 12/19/2014 | 12/19/2014 | P | PASS |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Final | 12/18/2014 | 12/19/2014 | 12/19/2014 | A | PASS |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
Permanent Occupancy | | | 12/19/2014 | | DONE |
|
|
|
|
FIRE-Final Inspection | 12/18/2014 | 12/18/2014 | 12/18/2014 | P | PASS |
Forrest France
|
|
|
C/N items verified. Life safety finaled.
|
Zoning Approval | 12/18/2014 | 12/18/2014 | 12/18/2014 | | DONE |
Andrea Tuning
|
|
|
|
FIRE-Final Inspection | 12/16/2014 | 12/17/2014 | 12/17/2014 | A | FAIL |
Troy Cobbley
|
|
|
Provide fire dept access signage at entrance as discussed, provide additional fire extinguisher in basement, remove deadbolt from interior door, provide remote annunciator/testing of the duct smoke detector.
|
PubWorks Occupancy Approval | 12/15/2014 | 12/15/2014 | 12/15/2014 | | DONE |
Tiffany Lowery
|
|
|
|
BLD-Ceiling Grid Inspection | 11/18/2014 | 11/18/2014 | 11/18/2014 | P | PASS |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Ceiling Grid Inspection | 11/12/2014 | 11/13/2014 | 11/13/2014 | A | NR |
Mike Jordan
|
|
|
please park at the nail salon next door Phone #: ###-#### Inspection requested via web by Jared Waggoner. Needs electrical and mech. rough in inspections first.
|
BLD-Energy code compliance | 10/14/2014 | 10/15/2014 | 10/15/2014 | P | PASS |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Energy code compliance | 10/13/2014 | 10/14/2014 | 10/14/2014 | P | PART |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Jared Waggoner north side ok
|
BLD-Energy code compliance | 10/10/2014 | 10/13/2014 | 10/13/2014 | A | PART |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Jared Waggoner air seal ok
|
BLD-Energy code compliance | 10/13/2014 | 10/13/2014 | 10/13/2014 | A | PASS |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Jared Waggonerairseal ok
|
BLD-Framing/Rough-in | 10/9/2014 | 10/10/2014 | 10/10/2014 | P | PASS |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Framing/Rough-in | 10/7/2014 | 10/8/2014 | 10/8/2014 | P | PASS |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Jared Waggoner exterior
|
BLD-Wall Bracing | 10/8/2014 | 10/8/2014 | 10/8/2014 | P | PASS |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Jared Waggoner ok to cover exterior/ 316 aproved soffit framing for cover.
|
BLD-Framing/Rough-in | 10/1/2014 | 10/2/2014 | 10/2/2014 | A | PART |
Jim Sly
|
|
|
Drive through canopy roof nailing inspection, exterior soffit framing Phone #: ###-#### Inspection requested via web by Jared Waggoner OK
|
BLD-Concrete | 9/30/2014 | 9/30/2014 | 9/30/2014 | P | PART |
Jim Sly
|
|
|
reinforcing inspection of fence CMU pilasters prior to grout at 3pm. Phone #: ###-#### Inspection requested via web by Jared Waggoner OK.
|
BLD-Framing/Rough-in | 9/29/2014 | 9/30/2014 | 9/30/2014 | P | PART |
Jim Sly
|
|
|
Roof Framing for cover Phone #: ###-#### Inspection requested via web by Jared Waggoner Roof nailing and fence pilasters......OK.
|
BLD-Foundation | 9/12/2014 | 9/15/2014 | 9/15/2014 | A | PASS |
Jim Storey
|
|
|
Inspection of below grade concrete related to CMU fence pilasters. Requested time 11am. Will call concrete for 1pm Phone #: ###-#### Inspection requested via web by Jared Waggoner depth and rebar ok
|
BLD-Concrete | 9/8/2014 | 9/9/2014 | 9/9/2014 | P | PASS |
Jim Storey
|
|
|
Energy inspection at below grade (underslab) and reinforced slab on deck. Concrete slab poured 9/10 at 6am with special inspection. Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Foundation | 9/5/2014 | 9/8/2014 | 9/8/2014 | A | PASS |
Jim Storey
|
|
|
Concrete column piers in drive through and trash enclosure walls. Concrete onsite at 8:45am. Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Footing | 9/3/2014 | 9/4/2014 | 9/4/2014 | A | PASS |
Jim Storey
|
|
|
request 11am // Jared Phone #: ###-#### pad ft for drive thru placed with si ok
|
BLD-Energy code compliance | 8/28/2014 | 8/29/2014 | 8/29/2014 | A | PASS |
Jim Storey
|
|
|
Foundation wall vertical only subgrade 2" rigid insulation Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Foundation | 8/26/2014 | 8/27/2014 | 8/27/2014 | A | PASS |
Jim Storey
|
|
|
Please arrive around 11am for inspection. Concrete is expected at 1:30pm same day. Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Footing | 8/21/2014 | 8/21/2014 | 8/21/2014 | P | PASS |
Phil Shearer
|
|
|
Exterior building footing
|
BLD-Footing | 8/21/2014 | 8/21/2014 | 8/21/2014 | P | DEFR |
Jim Storey
|
|
|
Jared Phone #: ###-####to 470
|
BLD-Foundation | 8/1/2014 | 8/1/2014 | 8/1/2014 | P | PASS |
Jim Storey
|
|
|
Basement wall reinforcing inspection. Phone #: ###-#### Inspection requested via web by Jared Waggoner
|
BLD-Footing | 7/24/2014 | 7/25/2014 | 7/25/2014 | A | PASS |
Phil Shearer
|
|
|
Jared Phone #: ###-#### Basement footings
|
OVERRIDE | | | 7/24/2014 | | |
|
|
|
|
Telephone call | | | 7/24/2014 | | DONE |
Candy A. Nichols
|
|
|
called Larry-left message telling him permit is ready and how much is owed
|
Issue PAID IN FULL permit | | | 7/24/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Routing - PLAN CHECK | 7/23/2014 | | 7/24/2014 | | PASS |
Carl D Madsen
|
|
|
|
Case Summary (BLD) | | | 7/24/2014 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/24/2014 | | DONE |
|
|
|
|
Print Occupancy Form | | | 7/24/2014 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 7/24/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Plan assigned to (CDM) | 6/16/2014 | | 7/24/2014 | | PASS |
Carl D Madsen
|
|
|
|
Routing Off Site - STRUCTURAL | | | 7/24/2014 | | FAIL |
|
|
|
|
Routing Off Site - STRUCTURAL | 7/8/2014 | | 7/24/2014 | | FAIL |
Carl D Madsen
|
|
|
|
Routing Off Site - STRUCTURAL | 7/17/2014 | | 7/24/2014 | | PASS |
Carl D Madsen
|
|
|
Resubs on 7/17
|
Routing - FIRE | 7/22/2014 | 7/22/2014 | 7/23/2014 | | PASS |
Craig D. Hanson
|
|
|
See Fire Plan Review Rev 1 07-23-14
|
Route to Impact Fee Review | 7/18/2014 | 7/21/2014 | 7/22/2014 | | PASS |
James McMahon
|
|
|
IF's assessed by C. Gould
|
Routing - PLUMBING | 7/16/2014 | | 7/22/2014 | | PASS |
Bill VanDegrift
|
|
|
per plan and ISPC.
|
Plan resubmittals received | | | 7/17/2014 | | DONE |
Christina Prado
|
|
|
Received three sets of revised plan sheets marked A0, A1.0, A3.0, A4.0, A6.2, A8.0, A9.0, A10.0, A10.1, A10.02 & P2.12 as well as one each response letter for Carl Madsen & Craig Hansen, Revised Fire flow sheet, structural notations and one complate set of civil revisions marked C1, C2, C3 & C4; Plans stamped and taken to Carl Madsen for further review
|
Routing PW Drainage | 7/15/2014 | | 7/16/2014 | | PASS |
Brian Murphy
|
|
|
|
Routing - PUBLIC WORKS | 7/16/2014 | | 7/16/2014 | | PASS |
Beverly Mountain
|
|
|
|
Routing - PUBLIC WORKS | 7/15/2014 | | 7/16/2014 | | PASS |
Beverly Mountain
|
|
|
|
Routing PW Street Lights | 6/19/2014 | | 7/15/2014 | | PASS |
Mike D Hedge
|
|
|
No lights required per Rob B. bam
|
Routing - FIRE | 7/14/2014 | | 7/15/2014 | | FAIL |
Craig D. Hanson
|
|
|
See Fire Plan Review 07-15-14
|
1st review completed | | | 7/15/2014 | | FAIL |
|
|
|
Failed: PW, Plan Check, Fire Plumbing
|
Routing - PLAN CHECK | 6/24/2014 | | 7/14/2014 | | FAIL |
Carl D Madsen
|
|
|
Plan review sent to Larry Knopp 7-14-14 CDM
|
Plan resubmittals received | | | 7/10/2014 | | DONE |
Candy A. Nichols
|
|
|
2 sets of revised erosion narratives were resubmitted -took to Carl M
|
Additional plans submitted | | | 7/9/2014 | | DONE |
Tisha Gallop
|
|
|
received third copy of structural calcs and plans; taken to Carl Madsen
|
Telephone call | | | 7/8/2014 | | DONE |
Candy A. Nichols
|
|
|
talked to Bell @ Action Couriers for pick up
|
Plan resubmittals received | | | 7/3/2014 | | DONE |
Candy A. Nichols
|
|
|
received sets of each-sheets A2.0, A2.1, A4.0, A4.1, A6.2-2, 2 sets of struc calcs from Wolfe Engineering-took to John M.
|
Plan resubmittals received | | | 7/2/2014 | | DONE |
Christina Prado
|
|
|
Received five revised sets of plan sheets matked Site Grading, Utility Plan as well as one O & M maintenance Description;Plans taken to carl for further review
|
Plan resubmittals received | | | 6/27/2014 | | DONE |
Candy A. Nichols
|
|
|
2 sheets of P2.11 resubmitted-took to CDM
|
Routing - PLANNING | 6/24/2014 | | 6/24/2014 | | PASS |
Andrea Tuning
|
|
|
|
Routing - PLUMBING | 6/20/2014 | | 6/24/2014 | | FAIL |
Bill VanDegrift
|
|
|
plumbing plans shows roof drainage to a site system- civil shows no site system
|
Routing - Erosion and Sediment | 6/19/2014 | | 6/20/2014 | | PASS |
Evan Jenkins
|
|
|
Construction of New Pioneer Fed. Credit Union.
Approx: 40,000 Sq. Ft.
|
Routing - PUBLIC WORKS | 6/17/2014 | | 6/19/2014 | | FAIL |
Beverly Mountain
|
|
|
|
Routing PW Solid Waste | 6/19/2014 | | 6/19/2014 | | PASS |
Peter J. McCullough
|
|
|
|
Routing PW Sewer Rating | 6/17/2014 | | 6/17/2014 | | PASS |
Jennifer Bruner
|
|
|
|
Routing - Addressing | 6/16/2014 | | 6/17/2014 | | PASS |
Jason C. Taylor
|
|
|
|
Routing PW Sewer Design | 6/17/2014 | | 6/17/2014 | | PASS |
Kyle S. Rosenmeyer
|
|
|
Show sewer connection as connection to existing service stub.
|
Routing - PLANNING Land Div | 6/16/2014 | | 6/16/2014 | | PASS |
Dave Abo
|
|
|
Lot 1, Block 1 of Carnation Townhouse Subdivision.
|
Plans ACCEPTED BY PLAN TECH | | | 6/13/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Intake Approval | | | 6/13/2014 | | PASS |
Candy A. Nichols
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 6/13/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Application received | | 6/13/2014 | | | |
|
|
|
|
Telephone call | | | | | |
Candy A. Nichols
|
|
|
called Action Currier to pick up plans 6-16-14
|
Pending Assignment by JCM | 6/16/2014 | | | | |
John Menard
|
|
|
|
Routing PW Drainage | 6/17/2014 | | | | FAIL |
Brian Murphy
|
|
|
needs monitoring well
|