Case Summary (BLD) | | | 5/26/2015 | | DONE |
|
|
|
|
PubWorks Occupancy Approval | 5/1/2015 | 5/1/2015 | 5/1/2015 | | DONE |
Jason C. Taylor
|
|
|
A letter from the applicant’s civil engineer indicating that the final grading and drainage is acceptable has been received by Public Works. Final occupancy may be approved by the building department. Jason Taylor ###-####.
|
BLD-Final | 3/30/2015 | 3/31/2015 | 3/31/2015 | A | PASS |
Tony Young
|
|
|
Brian Phone #: ###-####,, made ok
|
DOC - Permit Finaled | 3/31/2015 | 3/31/2015 | 3/31/2015 | P | PASS |
Tony Young
|
|
|
done
|
BLD-Other | 2/9/2015 | 2/10/2015 | 2/10/2015 | A | PASS |
Tony Young
|
|
|
Bryon,, soffit ; Phone #: ###-####,, removed non compliant soffit material,, layer of 5/8 sheetrock in place now,, over fire rated plywood,, ok to apply soffit material
|
BLD-Final | 2/5/2015 | 2/6/2015 | 2/6/2015 | A | FAIL |
Tony Young
|
|
|
Brian Phone #: ###-####,, soffit work and window finish not complete,, no work going on
|
BLD-Final | 2/4/2015 | 2/5/2015 | 2/5/2015 | A | PEND |
Tony Young
|
|
|
Brian Phone #: ###-####
|
BLD-Final | 2/2/2015 | 2/4/2015 | 2/4/2015 | A | PEND |
Tony Young
|
|
|
Brian Phone #: ###-####
|
BLD-Final | 1/30/2015 | 2/2/2015 | 2/2/2015 | P | PEND |
Tony Young
|
|
|
Brian Phone #: ###-####
|
BLD-Blower Door Test Results | 1/30/2015 | 2/2/2015 | 2/2/2015 | A | PASS |
Tony Young
|
|
|
Brian Phone #: ###-####// 4.4
|
BLD-Final | 1/29/2015 | 1/30/2015 | 1/30/2015 | P | PART |
Tony Young
|
|
|
Brian Phone #: ###-####,, all made ok except for the soffit on rear porch area,, will change out next week and call in,, window for egress has been dropped,, will do finish work next week
|
BLD-Final | 1/26/2015 | 1/27/2015 | 1/27/2015 | P | FAIL |
Tony Young
|
|
|
Bryan Phone #: ###-####,, need soffits oked by fire chief,, egress per code,, rise per code,, mech final,, furr out weather resistant, etc
|
PubWorks Occupancy Approval | 1/27/2015 | 1/27/2015 | 1/27/2015 | | DONE |
Jason C. Taylor
|
|
|
A bond for the sites final grading and re-vegetation has been received by Public Works. Occupancy may be approved by the building department. Jason Taylor ###-####.
|
BLD-Framing/Rough-in | 1/5/2015 | 1/5/2015 | 1/5/2015 | P | PART |
Tony Young
|
|
|
not for the full house // Brian Phone #: ###-####,, rear patio frame ok,, need to get electrical (if needed for lighting) and soffit protection inspection prior to cover
|
BLD-Footing | 12/8/2014 | 12/9/2014 | 12/9/2014 | A | PASS |
Jim Storey
|
|
|
Brian Phone #: ###-####
|
CHANGE STATUS TO (ISS) | | | 12/8/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Plan assigned to (JG) | | 11/13/2014 | 12/5/2014 | | PASS |
Javier Guzman
|
|
|
1st review completed, Plan Mod covered patio
|
Routing - PLAN CHECK | 12/2/2014 | | 12/5/2014 | | PASS |
Javier Guzman
|
|
|
|
Case Summary (BLD) | | | 12/5/2014 | | DONE |
Javier Guzman
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/5/2014 | | DONE |
|
|
|
|
Telephone call | | | 12/5/2014 | | DONE |
Candy A. Nichols
|
|
|
called Brain to let know Mod is ready and how much is owed
|
Plan resubmittals received | | | 12/2/2014 | | DONE |
Candy A. Nichols
|
|
|
received 1 set of truss calcs and 2 sets of each sheet 1, A-101, A-102A-103, A-104, A-101, A-102, A-103, A-104-took to JG
|
Routing - PLANNING | 12/2/2014 | | 12/2/2014 | | PASS |
Sue Cummings
|
|
|
|
Plan resubmittals received | | | 11/21/2014 | | DONE |
Christina Prado
|
|
|
Received revised reduced site plan;taken to JG for review
|
Routing - PLAN CHECK | 11/17/2014 | | 11/21/2014 | | FAIL |
Javier Guzman
|
|
|
emailed report to applicant
|
Routing - PLANNING | 11/17/2014 | | 11/17/2014 | | FAIL |
Sue Cummings
|
|
|
Javier pointed out that there is no detail on the patio. site plan and floor plan do not show patio at all. Needs to re-submitt
ACTUAL plans.
|
Routing PW Grading-Hillside | 11/13/2014 | | 11/17/2014 | | PASS |
Jason C. Taylor
|
|
|
No changes for Public Works.
|
Plan Modification Accepted | | | 11/13/2014 | | DONE |
Christina Prado
|
|
|
Received two sest of revised plan sheets marked Elevations 1, Elevations 2, Lower Level, Main Level, Second Level, Sections 1, Sections 2 & Site Plan as well as two sets reduced site plan and structural calcs;Plans stamped and taken to JG for review
|
BLD-Energy code compliance | 10/14/2014 | 10/15/2014 | 10/15/2014 | A | PASS |
Tony Young
|
|
|
Brian Phone #: ###-####
|
BLD-Energy code compliance | 10/14/2014 | 10/14/2014 | 10/14/2014 | P | NH |
Tony Young
|
|
|
Brian Phone #: ###-####
|
BLD-Energy code compliance | 10/13/2014 | 10/14/2014 | 10/14/2014 | A | NR |
Tony Young
|
|
|
Brian Phone #: ###-####
|
BLD-Framing/Rough-in | 10/13/2014 | 10/13/2014 | 10/13/2014 | P | PART |
Tony Young
|
|
|
Brian Phone #: ###-####,, still need truss fixes,, need fireblocking at top of chase.,, ok to cover exterior
|
BLD-Energy code compliance | 10/10/2014 | 10/13/2014 | 10/13/2014 | A | PART |
Tony Young
|
|
|
Brian Phone #: ###-####,, seal ok
|
BLD-Framing/Rough-in | 10/10/2014 | 10/13/2014 | 10/13/2014 | A | PART |
Tony Young
|
|
|
Brian Phone #: ###-####,, ok to insulate,, c/n posted
|
BLD-Energy code compliance | 10/9/2014 | 10/10/2014 | 10/10/2014 | A | PART |
Tony Young
|
|
|
Brian Phone #: ###-####,, seal pack ok
|
BLD-Framing/Rough-in | 10/9/2014 | 10/10/2014 | 10/10/2014 | A | FAIL |
Tony Young
|
|
|
Brian Phone #: ###-####,, do not insulate,, correction notice posted,, may need to modify permit if adding a porch cover on rear
|
BLD-Framing/Rough-in | 10/7/2014 | 10/8/2014 | 10/8/2014 | A | NR |
Phil Shearer
|
|
|
Need to provide truss engineering.
|
BLD-Framing/Rough-in | 10/1/2014 | 10/2/2014 | 10/2/2014 | P | NR |
Tony Young
|
|
|
Brian// please call 30 min prior Phone #: ###-####,, need trades 1st
|
BLD-Foundation | 8/8/2014 | 8/8/2014 | 8/8/2014 | A | PASS |
Phil Shearer
|
|
|
Phone #: 2086971241 >> Inspection requested via mobile web by Heron
|
BLD-Footing | 8/7/2014 | 8/7/2014 | 8/7/2014 | P | PASS |
Phil Shearer
|
|
|
Phone #: 2086971241 >> Inspection requested via mobile web by Heron
|
PubWorks Subgrade Approval | 8/6/2014 | 8/6/2014 | 8/6/2014 | | DONE |
Jason C. Taylor
|
|
|
A letter from the applicant’s geotechnical engineer indicating that the entire building footing subgrade is acceptable has been received by Public Works. Footing inspection may be scheduled with the Building Department. Jason Taylor ###-####.
|
OVERRIDE | | | 7/25/2014 | | |
|
|
|
|
Application received | | 6/20/2014 | 7/25/2014 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 7/25/2014 | | DONE |
Tisha Gallop
|
|
|
|
Inspection Record Card- Bld | | | 7/25/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Bld | | | 7/25/2014 | | DONE |
Barbara Stitt
|
|
|
|
Permit Ready to Issue | | | 7/25/2014 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (JG) | 6/23/2014 | 6/23/2014 | 7/24/2014 | | PASS |
Javier Guzman
|
|
|
1st review completed, Due 7/10 TH L2**
|
Routing - PLAN CHECK | 7/23/2014 | | 7/24/2014 | | PASS |
Javier Guzman
|
|
|
|
Plan resubmittals received | | | 7/24/2014 | | DONE |
Tisha Gallop
|
|
|
received two copies of response letter and plan sheets Elevations 1, Elevations 2, Lower Level, Main Floor, Second Floor, Sections 1, Sections, Roof Layout; taken to Javier.
|
Case Summary (BLD) | | | 7/24/2014 | | DONE |
Javier Guzman
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/24/2014 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 7/10/2014 | | 7/23/2014 | | FAIL |
Javier Guzman
|
|
|
see plan review report 7-23-2014
|
Plan resubmittals received | | | 7/22/2014 | | |
|
|
|
1 copy of plan reveiw responses, 2 copies of sheets Elevations 1, Elevations 2, Lower level, Main floor, Second floor, Sections 1, Sections, Roof layout taken to Javier's desk
|
Plan resubmittals received | | | 7/21/2014 | | DONE |
Christina Prado
|
|
|
Received two sets of revised plans marked Elevations 1, Elevations 2, Lower Level, Main Floor, Sections, Sections 1, Second Floor, Roof Layout as well as one set of revised structural calcs; Plans stamped and taken to Javier for further review
|
1st review completed | | | 7/10/2014 | | FAIL |
Javier Guzman
|
|
|
|
Routing PW Grading-Hillside | 7/10/2014 | | 7/10/2014 | | PASS |
Jason C. Taylor
|
|
|
A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable must be approved by Public Works prior to scheduling a footing inspection. Call Jason Taylor at ###-####
Prior to obtaining a final for the permit, the roof storm drainage system must be inspected by Public Works. Call Jason Taylor at ###-####.
|
Routing - PLAN CHECK | | | 7/10/2014 | | FAIL |
Javier Guzman
|
|
|
emailed review report to applicant
|
Routing - FIRE | 7/8/2014 | | 7/8/2014 | | PASS |
Scott Arellano
|
|
|
No comments. This building has been evaluated for Fire Department Vehicle Access.
|
Routing - Erosion and Sediment | 7/2/2014 | | 7/2/2014 | | PASS |
Andy J. Long
|
|
|
ESC plan and SWPPP narrative submitted and approved. Valid RP and PD designated.
|
Routing - MECHANICAL | 6/26/2014 | | 7/2/2014 | | PASS |
Troy James
|
|
|
|
Routing - Addressing | 6/23/2014 | | 6/26/2014 | | PASS |
Jason C. Taylor
|
|
|
|
Routing - PUBLIC WORKS | 6/26/2014 | | 6/26/2014 | | PASS |
Jennifer Bruner
|
|
|
|
Routing - PLANNING | 6/26/2014 | | 6/26/2014 | | PASS |
Sue Cummings
|
|
|
|
Routing PW Grading-Hillside | 6/26/2014 | | 6/26/2014 | | FAIL |
Jason C. Taylor
|
|
|
Need new grading plans dropped off.
|
Intake Approval | | | 6/23/2014 | | PASS |
|
|
|
|
Intake Approval | | | 6/20/2014 | | FAIL |
Christina Prado
|
|
|
need reduced site plan, co/smoke detector called out, extra grading set, bracing calcs & garage seperation
|