Permit Information
Permit NumberBLD14-01863
StatusFinaled
Name RINDERKNECHT ASSOCIATES INC
Site Address 2653 S VICTORY VIEW WAY
Project NameInvolta Data Center
Customer Number 
ePlanReviewYes
Description
(INVOLTA DATA CENTER) Plan Modification 12-11-14 Customer rental office space that was shown on the original plans will now have a celing grid, carprt, lighting and power. **ajs**This submittal is for tenant improvement construction permit. Civil and Structural Footing/Foundation/Steel packages were previously submitted and approved under separate permits.

Project is for a new, single-story, 31,460 square foot data center and office tenant, with future 15,400 square foot Phase 2 (to be permitted separately at future date). This building will provide secure data storage for multiple customers. The facility will be staffed 24 hours a day, 7 days a week. Work to include interior noncombustible partition walls and interior build out with plumbing, mechanical and electrical per approved plans. Interior finish shall meet IBC chapter 8. Building is provided with ADA restrooms and drinking fountain. This building has office space and server area with room designed for future expansion. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **ajs**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Print Statement  5/11/2015 DONE
First Notice 3/14/20155/4/2015 DONE
BLD-Final3/3/20153/4/20153/4/2015APASS
DetailsJim Sly
Berny-zoning inspection scheduled for 10:00 so can you please go out after that for the final Phone #: ###-####
Zoning approved ........OK for Perm Occ.
Zoning Approval3/4/20153/4/20153/4/2015 DONE
DetailsAndrea Tuning
Permanent Occupancy  3/4/2015 DONE
DetailsCandy A. Nichols
BLD-Final3/3/20153/3/20153/3/2015PNR
DetailsJim Sly
Burrney Phone #: ###-####
Need to verify Zoning perm occ.
BLD-Final1/26/20151/27/20151/27/2015APART
DetailsMike Jordan
Bernie Phone #: ###-####. All issues resolved. Will be ok for perm occ. once zoning signs pem.
BLD-Final1/16/20151/16/20151/16/2015APART
DetailsMike Jordan
ok for temp occ. Waiting for new ADA signage.
Temporary Occupancy1/16/20154/16/20151/16/2015 DONE
DetailsChristina Prado
PubWorks Occupancy Approval1/16/20151/16/20151/16/2015 DONE
DetailsBrian Murphy
Zoning Approval Temp1/16/20151/16/20151/16/2015 DONE
DetailsAndrea Tuning
Temporary approval has been granted due to the fact that a bond has been placed for native grass seed, bike rack and the metal coping on the building. 120-day temporary occupancy.
BLD-Final1/13/20151/14/20151/14/2015AFAIL
DetailsMike Jordan
Bernie or ###-#### Jeremiah Phone #: ###-####. Provide special inspection report, post bond. Provide ADA compliant restroom signs.
FIRE-Final Inspection1/12/20151/13/20151/13/2015APASS
DetailsTroy Cobbley
life safety passed
FIRE-Final Inspection1/8/20151/9/20151/9/2015AFAIL
DetailsTroy Cobbley
Need approval from plan review for the lighting calculations, need battery room signage still, need spill clean up documentation as discussed, need riser room signage still, need emergency generator certification.
FIRE-Final Inspection12/17/201412/18/201412/18/2014PFAIL
DetailsTroy Cobbley
Went over life safety requirements with owner and general contractor. Need exit discharge lighting, Man Trap door operation approved, fire extinguishers verified, hydrant location verified, gate width verifed, emergency generator certification, need electrical room signs, battery room signs, riser room signage, fire dept access signage, need address, need project related fire alarm and fire sprinkler permits finaled.
FIRE-Final Inspection12/17/201412/17/201412/18/2014PFAIL
DetailsTroy Cobbley
Started life safety inspection. Missing all of the small documents. I noted problems with exit discharge lighting and access controled egress locks. This was only a partial inspection.
BLD-Ceiling Grid Inspection12/17/201412/17/201412/17/2014PPASS
DetailsMike Jordan
CHANGE STATUS TO (ISS)  12/17/2014 DONE
DetailsChristina Prado
Per AJS - Plan mod was minor and no fees were due. Changing status from FEE to ISS so inspections can continue
Routing - FIRE12/11/201412/11/201412/11/2014 PASS
DetailsCraig D. Hanson
No changes to original Fire Code review comments. Modifications will be required to the building fire protection system, under separate permit.
Plan assigned to (AJS)12/11/201412/11/201412/11/2014 PASS
DetailsAdele J Schaffeld-Griffin
plan mod
Routing - PLAN CHECK12/11/2014 12/11/2014 PASS
DetailsAdele J Schaffeld-Griffin
Plan resubmittals requested  12/4/2014 DONE
started workflow
BLD-Ceiling Grid Inspection11/20/201411/20/201411/20/2014PPASS
DetailsJim Sly
jason Phone #: ###-####
BLD-Framing/Rough-in10/22/201410/23/201410/23/2014PPASS
DetailsMike Jordan
Jason Phone #: ###-####. soffits and hardlids ok.
BLD-Framing/Rough-in9/26/20149/29/20149/29/2014ACANC
DetailsMike Jordan
Berne Phone #: ###-####. No inspection needed at this time.
BLD-Framing/Rough-in9/26/20149/26/20149/26/2014PPASS
DetailsJim Sly
BLD-Conference9/25/20149/26/20149/26/2014PPASS
DetailsJim Sly
Framing inspection for office area Phone #: ###-#### Inspection requested via web by Berne Hotchkiss
BLD-Conference9/16/20149/16/20149/16/2014ACANC
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Berne Hotchkiss
BLD-Framing/Rough-in9/16/20149/16/20149/16/2014APART
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Berne Hotchkiss. ok to start sheeting on exterior side of exterior walls only. Contractor to get clarification from structural engineer regarding the horizontal bridging at 5 ft and 4ft on center for all non bearing walls and walls smaller than 4" wide.
BLD-Framing/Rough-in9/12/20149/15/20149/15/2014PPART
DetailsMike Jordan
Bernie Phone #: ###-####. Exterior steel stud walls at south office area wall. Work in progress on remainder of exterior walls.
BLD-Framing/Rough-in9/3/20149/9/20149/9/2014APASS
DetailsMike Jordan
Berney Phone #: ###-####. Interior steel stud walls at data center portion only. Steel steud parapet also ok to shhet on interior side.
BLD-Framing/Rough-in9/2/20149/2/20149/2/2014PPART
DetailsMike Jordan
bernie Phone #: ###-####. Needs MEP inspections first. Reviewed special inspection reoprts to date. Also requested special inspection reports for precast concrete wall panels.
Issue PAID IN FULL permit  8/27/2014 DONE
DetailsChristina Prado
Print Occupancy Form  8/27/2014 DONE
DetailsChristina Prado
Plan assigned to (AJS)7/8/20147/8/20148/21/2014 PASS
DetailsAdele J Schaffeld-Griffin
resubs recieved 8/14 1st review completed Due 8/05 Project Management Level 3 TI - ePlanReview - Involta Data Center TI
PLANS/APPL TAKEN TO FRONT DESK  8/21/2014 DONE
Permit Ready to Issue  8/21/2014 DONE
DetailsChristina Prado
Routing - PLAN CHECK8/14/2014 8/21/2014 PASS
DetailsAdele J Schaffeld-Griffin
Routing - FIRE8/14/20148/14/20148/20/2014 PASS
DetailsScott Arellano
Attached revised comments to plans.
Route to Impact Fee Review8/5/20148/8/20148/5/2014 PASS
DetailsCindy M. Gould
1st review completed  7/31/2014 FAIL
DetailsAdele J Schaffeld-Griffin
Routing - PLAN CHECK7/8/2014 7/31/2014 FAIL
DetailsAdele J Schaffeld-Griffin
Routing - FIRE7/8/20147/8/20147/16/2014 FAIL
DetailsCraig D. Hanson
See Fire Plan Review 07-16-14
Routing - PLUMBING7/8/2014 7/9/2014 PASS
DetailsBill VanDegrift
approved with red lines
1) P100- 4"drain in mechanical room to recieve discharge of 2" R.P.,
2) P100- floor drain in restroom to be flush with finish floor.
3) P100- control valve to be in north wall for ADA compliance.
4) P200-R.P. required on water to mechanical equipment.
5) P210- same as P100
6) P211- same as P200
Routing PW Sewer Rating7/9/2014 7/9/2014 PASS
DetailsBeverly Mountain
Routing - Addressing7/8/2014 7/9/2014 PASS
DetailsJason C. Taylor
Routing - PUBLIC WORKS7/8/2014 7/9/2014 PASS
DetailsBeverly Mountain
Routing - Design Review7/8/2014 7/9/2014 PASS
DetailsAndrea Tuning
Andrea Tuning - DRH14-00042
Intake Approval  7/8/2014 PASS
DetailsJason Blais
Prescreen approved by Sam Zahorka. Plan Review Fees paid.
Pending Assignment by JCB7/8/2014 7/8/2014 DONE
DetailsJason Blais
Application received  7/1/2014 DONE
Application submitted via PDS Online on Jul 1 2014 12:41PM