BLD-Final | 9/11/2017 | 9/11/2017 | 9/11/2017 | P | PASS |
Mike Jordan
|
|
|
as per Jason Blais-cnditions have been met and perm C of O can be issued Phone #: ###-####
|
Print Occupancy Form | | | 9/11/2017 | | DONE |
|
|
|
|
Letter of compliance/Occupancy | | | 9/11/2017 | | DONE |
|
|
|
|
CHANGE STATUS TO (FNL) | | | 9/11/2017 | | DONE |
|
|
|
as per Jason Blais temp C of O conditions have been met
|
BLD-Aging Inspection | 8/28/2017 | 8/28/2017 | 8/28/2017 | | PEND |
Mike Jordan
|
|
|
|
Temporary Occupancy | 8/10/2017 | 11/8/2017 | 8/10/2017 | | DONE |
Candy A. Nichols
|
|
|
Jason Blais ok'd extension of temp c of o good threw 10/27/17
|
BLD-Aging Inspection | 6/26/2017 | 6/26/2017 | 6/27/2017 | | PEND |
Mike Jordan
|
|
|
|
Temporary Occupancy | 5/31/2017 | 8/29/2017 | 5/31/2017 | | DONE |
Candy A. Nichols
|
|
|
Jason Blais ok 60 day ext good from 5-30-17
|
Telephone call | | | 5/25/2017 | | DONE |
|
|
|
emailed Lori that temp c of o will expire next week on the 30th
|
BLD-Aging Inspection | 4/4/2017 | 4/4/2017 | 4/4/2017 | | PEND |
Mike Jordan
|
|
|
|
Temporary Occupancy | 2/28/2017 | 5/29/2017 | 2/28/2017 | | DONE |
Candy A. Nichols
|
|
|
as per Jason B-TCO request for 90 day extension approved
|
BLD-Aging Inspection | 1/31/2017 | 1/31/2017 | 1/31/2017 | | PEND |
Mike Jordan
|
|
|
|
Temporary Occupancy | 12/5/2016 | 3/5/2017 | 12/5/2016 | | DONE |
Candy A. Nichols
|
|
|
as per Jason B-ok to extend temp c of o
|
Telephone call | | | 12/5/2016 | | DONE |
|
|
|
called Lori about temp c of o that is expired-she will email Jason B today
|
Meeting | | | 12/5/2016 | | DONE |
|
|
|
ok to extend temp c of o-per Jason B
|
BLD-Aging Inspection | 11/29/2016 | 11/29/2016 | 11/30/2016 | | PEND |
Mike Jordan
|
|
|
|
Telephone call | | | 11/29/2016 | | DONE |
|
|
|
emailed Lori that the temp c of o was about to expire
|
Temporary Occupancy | 9/2/2016 | 12/1/2016 | 9/2/2016 | | DONE |
Candy A. Nichols
|
|
|
Jason Blais ok'd req for ext on temp c of o-good thru 9-1-16
|
Telephone call | | | 9/2/2016 | | DONE |
|
|
|
emailed Lori Vaughhan that Jason Blais ok's extension-good for 90 days
|
Telephone call | | | 8/31/2016 | | DONE |
|
|
|
emailed Lori-the temp c of o expires on 9/2/16 so he needs to either call for the perm c of o or ask for an extension
|
Temporary Occupancy | 6/14/2016 | 9/12/2016 | 6/14/2016 | | DONE |
Candy A. Nichols
|
|
|
as per Jason B ok for 90 day extension starting 6-4-16
|
Telephone call | | | 6/14/2016 | | DONE |
|
|
|
emailed Lori a reminder about the extension or final that is needed
|
Telephone call | | | 6/9/2016 | | DONE |
|
|
|
called Lori to remind her the temp c of o expired on 6/4/16. She asked me to email her
|
BLD-Aging Inspection | 4/11/2016 | 4/11/2016 | 4/12/2016 | | PEND |
Phil Shearer
|
|
|
|
Temporary Occupancy | 3/21/2016 | 6/19/2016 | 3/21/2016 | | DONE |
Candy A. Nichols
|
|
|
as per Jason Blais extension good from 3/6/16 thru 6/4/16
|
Telephone call | | | 3/10/2016 | | DONE |
|
|
|
called Lori to let know temp c of o is expired-she will email Jason B today
|
Telephone call | | | 3/7/2016 | | DONE |
|
|
|
called Lori to let know temp c of o is expired-voice mail won't let me leave message so emailed her
|
BLD-Aging Inspection | 2/8/2016 | 2/8/2016 | 2/9/2016 | | PEND |
Phil Shearer
|
|
|
|
BLD-Aging Inspection | 12/8/2015 | 12/8/2015 | 12/14/2015 | | PEND |
Phil Shearer
|
|
|
|
Temporary Occupancy | 12/7/2015 | 3/6/2016 | 12/7/2015 | | DONE |
Candy A. Nichols
|
|
|
|
Telephone call | | | 12/4/2015 | | DONE |
|
|
|
called Lori to let know permits expire today-she will email Jason B
|
BLD-Aging Inspection | 9/16/2015 | 9/16/2015 | 9/21/2015 | | DEFR |
Phil Shearer
|
|
|
|
Temporary Occupancy | 9/4/2015 | 12/5/2015 | 9/4/2015 | | DONE |
Brittany Hill
|
|
|
Per Jason Blais
|
Telephone call | | | 8/25/2015 | | DONE |
|
|
|
called Lori about temp c of o being expired and that she needs the final or needs to request an extension. She said she'd contact Jason Blais
|
BLD-Final | 3/10/2015 | 3/10/2015 | 3/10/2015 | A | PART |
Phil Shearer
|
|
|
Tad Phone #: ###-####. OK for Temp CO
|
BLD-Final | 1/26/2015 | 1/26/2015 | 1/26/2015 | P | CANC |
Phil Shearer
|
|
|
Tyler Phone #: ###-####// wrong permit
|
BLD-Wall Bracing | 12/2/2014 | 12/3/2014 | 12/3/2014 | P | PASS |
Phil Shearer
|
|
|
Tad-interior shear Phone #: ###-####
|
BLD-Energy code compliance | 12/1/2014 | 12/2/2014 | 12/2/2014 | A | PASS |
Phil Shearer
|
|
|
Tad Phone #: ###-####
|
BLD-Energy code compliance | 12/1/2014 | 12/1/2014 | 12/1/2014 | P | FAIL |
Phil Shearer
|
|
|
TAD Phone #: ###-####. Shingles are pushed under flashing and against firelpace chimny. Insulation above the front door needs to be double sided
|
BLD-Energy code compliance | 11/28/2014 | 11/28/2014 | 11/28/2014 | P | NR |
Jim Storey
|
|
|
Tad Phone #: ###-####
|
BLD-Framing/Rough-in | 11/24/2014 | 11/25/2014 | 11/25/2014 | P | PASS |
Phil Shearer
|
|
|
Tad Phone #: ###-####
|
BLD-Framing/Rough-in | 11/19/2014 | 11/20/2014 | 11/20/2014 | A | FAIL |
Mike Jordan
|
|
|
Tad Phone #: ###-####. Provide full height blocking on trusses A5 thru A7, provide the required strapping or 2x4 scabs on piggy back trusses as per sheet D8 from truss engineering. Justify all missid bearing points on trusses A1 thru A7. Ok to insulate, correction notice posted.
|
BLD-Framing/Rough-in | 11/19/2014 | 11/19/2014 | 11/19/2014 | P | NR |
Phil Shearer
|
|
|
Tad Phone #: ###-####
|
BLD-Framing/Rough-in | 11/17/2014 | 11/18/2014 | 11/18/2014 | A | CANC |
Phil Shearer
|
|
|
Tad Phone #: ###-####
|
BLD-Framing/Rough-in | 10/29/2014 | 10/30/2014 | 10/30/2014 | A | PART |
Phil Shearer
|
|
|
Thad Phone #: ###-####. Truss clips
|
Plan Modification Accepted | | | 10/30/2014 | | DONE |
|
|
|
new manual j report
|
Routing - MECHANICAL | 10/30/2014 | | 10/30/2014 | | PASS |
Troy James
|
|
|
resubmitted manual j report
|
BLD-Wall Bracing | 10/22/2014 | 10/23/2014 | 10/23/2014 | A | PASS |
Phil Shearer
|
|
|
Ron Phone #: ###-####
|
BLD-Wall Bracing | 10/21/2014 | 10/22/2014 | 10/22/2014 | A | NR |
Phil Shearer
|
|
|
John call for gate code Phone #: ###-####
|
BLD-Other | 9/23/2014 | 9/23/2014 | 9/23/2014 | P | FAIL |
Bill VanDegrift
|
|
|
1) sections 313.3 and 701 of the Idaho State Plumbing code require piping under buildings to be of approved material.
2) Remove and replace existing water and sewer piping with approved material.
3) Review and approval from Idaho Department of Environemtial Quality is required prior to any piping replacement.
|
BLD-Foundation | 9/9/2014 | 9/10/2014 | 9/10/2014 | P | PASS |
Jim Sly
|
|
|
Phone #: 2086971241 >> Inspection requested via mobile web by Heron
|
BLD-Footing | 9/8/2014 | 9/9/2014 | 9/9/2014 | P | PASS |
Phil Shearer
|
|
|
Phone #: 2086971241 >> Inspection requested via mobile web by Heron. There were no markted property lines. The foundation has min of ten feet from other foundations.
|
Issue PAID IN FULL permit | | | 9/8/2014 | | DONE |
Tisha Gallop
|
|
|
|
OVERRIDE | | | 8/29/2014 | | |
|
|
|
|
Inspection Record Card- Bld | | | 8/29/2014 | | DONE |
Christina Prado
|
|
|
|
Telephone call | | | 8/29/2014 | | DONE |
Christina Prado
|
|
|
Called Mike to advise permit is ready pending RP info and ACHD receipts and gave remaining fees due
|
Permit Ready to Issue | | | 8/29/2014 | | DONE |
Christina Prado
|
|
|
|
Plan assigned to (JG) | 7/15/2014 | 7/15/2014 | 8/28/2014 | | PASS |
Javier Guzman
|
|
|
1st review completed, Pending Addressing and Public Works 7/28 M L1* (Tisha)
|
Routing - PUBLIC WORKS | 8/28/2014 | | 8/28/2014 | | PASS |
Beverly Mountain
|
|
|
Bench SD okayed
|
Case Summary (BLD) | | | 8/28/2014 | | DONE |
Tisha Gallop
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/28/2014 | | DONE |
|
|
|
|
Routing - Addressing | 7/28/2014 | | 7/29/2014 | | PASS |
Jason C. Taylor
|
|
|
|
1st review completed | | | 7/28/2014 | | FAIL |
Javier Guzman
|
|
|
Pending Addressing and Public Works
|
Case Summary (BLD) | | | 7/28/2014 | | DONE |
Tisha Gallop
|
|
|
|
Routing - PLAN CHECK | 7/23/2014 | | 7/28/2014 | | PASS |
Javier Guzman
|
|
|
|
Routing - MECHANICAL | 1/18/2014 | | 7/23/2014 | | PASS |
Troy James
|
|
|
|
Routing - PLANNING | 7/17/2014 | | 7/18/2014 | | PASS |
Sue Cummings
|
|
|
|
Route to Impact Fee Review | 7/16/2014 | 7/19/2014 | 7/17/2014 | | PASS |
James McMahon
|
|
|
IF's assessed on permit.
|
Routing - Addressing | 7/16/2014 | | 7/17/2014 | | FAIL |
Jason C. Taylor
|
|
|
Correct space number (updated space numbers as of June 2014) was not identified in plans. Jason Taylor ###-####
|
Routing - PUBLIC WORKS | 7/16/2014 | | 7/17/2014 | | FAIL |
Jennifer Bruner
|
|
|
Fail per Bench Sewer
|
Application received | | 7/15/2014 | 7/16/2014 | | DONE |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 7/15/2014 | | DONE |
Tisha Gallop
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 7/15/2014 | | DONE |
Tisha Gallop
|
|
|
|
Intake Approval | | | 7/15/2014 | | PASS |
Tisha Gallop
|
|
|
|