Second Notice | | 3/13/2015 | 3/19/2015 | | DONE |
|
|
|
This permit finaled on the web by Jason Ramsey
|
First Notice | | 2/8/2015 | 3/3/2015 | | DONE |
|
|
|
mailed 3-3-15
|
BLD-Final | 1/29/2015 | 1/29/2015 | 1/29/2015 | P | PASS |
Mike Jordan
|
|
|
Jason// please call before for access Phone #: ###-####. ok for perm occ.
|
Permanent Occupancy | | | 1/29/2015 | | DONE |
Christina Prado
|
|
|
|
BLD-Final | 1/15/2015 | 1/16/2015 | 1/16/2015 | A | PART |
Mike Jordan
|
|
|
Jason Phone #: ###-####. ok to move equipment, office furniture etc.. only. Needs to install ventiiation equipment in repair area, pull plumbing permit for drinking fountain and mech. permit.
|
FIRE-Final Inspection | 1/15/2015 | 1/16/2015 | 1/15/2015 | A | PASS |
Troy Cobbley
|
|
|
life safety passed
|
FIRE-Final Inspection | 1/14/2015 | 1/15/2015 | 1/15/2015 | A | FAIL |
Troy Cobbley
|
|
|
Remove thumbturn deadbolts from three exits, keyed ok at the main exit, provide single action hardware for all doors per approved plans.
|
Issue PAID IN FULL permit | | | 12/29/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Plan assigned to (AJS) | 10/28/2014 | 10/28/2014 | 12/26/2014 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
1st review completed Level 3 TI - Paper - Lemhi Bldg Auto Repair 11/24
|
Case Summary (BLD) | | | 12/26/2014 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/26/2014 | | DONE |
|
|
|
|
Print Occupancy Form | | | 12/26/2014 | | DONE |
|
|
|
|
CHANGE STATUS TO (FEE) | | | 12/26/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Permit Ready to Issue | | | 12/26/2014 | | DONE |
|
|
|
|
Telephone call | | | 12/26/2014 | | DONE |
Candy A. Nichols
|
|
|
called Jason to let know permit is ready and how much is owed-left message
|
Routing - FIRE | 12/19/2014 | 12/19/2014 | 12/22/2014 | | PASS |
Scott Arellano
|
|
|
Attached comments to plans.
|
Plan resubmittals received | | | 12/18/2014 | | DONE |
Candy A. Nichols
|
|
|
received resubmittals- 2 each sheets 1 & 2 and 2 response comments-took to Adele
|
Routing - MECHANICAL | 11/19/2014 | | 11/20/2014 | | PASS |
Troy James
|
|
|
|
1st review completed | | | 11/20/2014 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
|
Routing - PLAN CHECK | 11/5/2014 | | 11/20/2014 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
approved with red line corrections
|
Routing - Addressing | 10/28/2014 | | 11/20/2014 | | PASS |
Jason C. Taylor
|
|
|
|
Routing - FIRE | 11/20/2014 | | 11/20/2014 | | FAIL |
Craig D. Hanson
|
|
|
See Fire Plan Review 11-20-14
|
Routing - PLANNING | 11/5/2014 | | 11/19/2014 | | PASS |
Bruce Eggleston
|
|
|
Bruce Eggleston - CZC14-00296
|
Plan resubmittals received | | | 11/13/2014 | | DONE |
|
|
|
received two copies of M-1
|
Routing - MECHANICAL | | | 11/5/2014 | | FAIL |
Troy James
|
|
|
emailed corrections to kartchner engineering
|
Routing - Erosion and Sediment | 11/3/2014 | | 11/4/2014 | | PASS |
Andy J. Long
|
|
|
No ESC permit needed based on scope of work provided. Project is Change of Use and interior remodel. Exterior activity includes install accessible ramp from parking lot to curb and installing parking signs.
No trench work or change to site drainage reported.
|
Routing PW Environmental | 10/30/2014 | | 11/4/2014 | | PASS |
Rick Christenson
|
|
|
|
Routing - PUBLIC WORKS | 10/30/2014 | | 11/3/2014 | | PASS |
Jennifer Bruner
|
|
|
|
Plan Reviewer's activity | | | 10/29/2014 | | DONE |
Jason Blais
|
|
|
No ACHD impact fees due per email from Christy Little of ACHD noted below:
Although no impact fees were ever paid at this location, ACHD will provide a “prior use adjustment” to the new tenant, and no additional impact fees will be due. If this is just a tenant improvement, then Boise City will need to know that there are no impact fees due and no inspection required. You can forward this e-mail to whoever you are working with in the Building Department.
Christy
Christy Little
Program Administrator, ACHD
Development Services
|
Pending Assignment by JCB | 10/24/2014 | | 10/28/2014 | | DONE |
Jason Blais
|
|
|
|
Plan Reviewer's activity | | | 10/28/2014 | | DONE |
Jason Blais
|
|
|
Emailed architect to have him contact ACHD to determine if any additional impact fees are due. Written verification needs to be provided to our Permit Counter prior to the building permit being issued.
|
Plans ACCEPTED BY PLAN TECH | | | 10/24/2014 | | DONE |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 10/24/2014 | | DONE |
|
|
|
|
Intake Approval | | | 10/23/2014 | | PASS |
|
|
|
|
Application received | | 10/23/2014 | | | |
|
|
|
|