First Notice | 3/14/2016 | 3/14/2016 | 4/12/2016 | | DONE |
Candy A. Nichols
|
|
|
sent in mail 4-13-16
|
BLD-Final | 3/14/2016 | 3/15/2016 | 3/14/2016 | A | PASS |
Jim Sly
|
|
|
Eric Phone #: ###-####
|
DOC - Permit Finaled | 3/14/2016 | 3/14/2016 | 3/14/2016 | P | PASS |
Jim Sly
|
|
|
|
FIRE-Final Inspection | 3/11/2016 | 3/14/2016 | 3/14/2016 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
BLD-Final | 3/10/2016 | 3/11/2016 | 3/11/2016 | A | NR |
Jim Sly
|
|
|
Eric Phone #: ###-#### Need Public works and Fire finals
|
PubWorks Occupancy Approval | 3/11/2016 | 3/11/2016 | 3/11/2016 | | DONE |
Tiffany Lowery
|
|
|
|
FIRE-Final Inspection | 3/10/2016 | 3/10/2016 | 3/10/2016 | P | FAIL |
Troy Cobbley
|
|
|
Provide building address on the street side of the building, remove arrow on exit sign directing people to locked door, provide fire dept access signage per notes.
|
Inspection Record Card- Bld | | | 3/3/2016 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 12/14/2015 | 12/15/2015 | 12/15/2015 | P | PASS |
Jim Sly
|
|
|
Eric Phone #: ###-####
|
BLD-Ceiling Grid Inspection | 12/1/2015 | 12/1/2015 | 12/1/2015 | P | PART |
Jim Sly
|
|
|
Eric Phone #: ###-#### 1st layer of rock on ceiling.....OK OK for 2nd layer.
|
BLD-Framing/Rough-in | 11/30/2015 | 11/30/2015 | 11/30/2015 | P | PART |
Jim Sly
|
|
|
Eric Phone #: ###-#### Ext shear nailing OK.......Trusses OK......OK to install 1st layer of rock on ceiling .......... pending Electr, Plumb and Mech. approval for cover.
|
CHANGE STATUS TO (ISS) | | | 11/16/2015 | | DONE |
|
|
|
|
(F) Reprint permit | | | 11/16/2015 | | DONE |
|
|
|
|
OVERRIDE | | | 11/13/2015 | | |
|
|
|
|
Telephone call | | | 11/13/2015 | | DONE |
|
|
|
called Renny to let know that the plan mod is ready and how much is owed-left message on his cell-PLEASE DO NOT RE ISSUE
|
Routing - PLAN CHECK | 11/5/2015 | | 11/13/2015 | | PASS |
Tim L. Woodard
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/13/2015 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/13/2015 | | DONE |
|
|
|
PWK15-00208 and PWK15-002015 fees need paid, then please do not re issue
|
Plan assigned to (TLW) | 10/23/2015 | | 11/13/2015 | | PASS |
Tim L. Woodard
|
|
|
|
Routing PW Drainage | 11/12/2015 | | 11/12/2015 | | PASS |
Jason C. Taylor
|
|
|
Project approved. JCT
|
Plan Modification Accepted | | | 11/5/2015 | | DONE |
|
|
|
received (3) sets of grading and drainage plans (L1.10, L1.15) and specifications
|
Routing PW Drainage | 10/27/2015 | | 10/27/2015 | | FAIL |
Jason C. Taylor
|
|
|
Geotechnical report has hadpan confining layer under swale. Grading plan must be revised to reflect percolation rate of a minimum 1/2" per hour. Jason Taylor ###-####.
|
Routing - PLAN CHECK | 10/23/2015 | | 10/26/2015 | | PASS |
Tim L. Woodard
|
|
|
Drainage plans only. TLW
|
Routing PW Drainage | 10/26/2015 | | 10/26/2015 | | FAIL |
Jason C. Taylor
|
|
|
Need 2 full size copies of Sheet L2.15 to process application. Jason Taylor ###-####
|
Plan Modification Accepted | | | 10/23/2015 | | DONE |
|
|
|
received (2) sets of grading & drainage plans and calculations & Erosion plans
|
BLD-Foundation | 9/30/2015 | 10/1/2015 | 10/1/2015 | P | PASS |
Jim Sly
|
|
|
Wes Phone #: ###-####
|
BLD-Footing | 9/29/2015 | 9/30/2015 | 9/30/2015 | A | PASS |
Jim Sly
|
|
|
Wes Phone #: ###-####
|
BLD-Footing | 9/25/2015 | 9/28/2015 | 9/28/2015 | P | NR |
Jim Sly
|
|
|
Jerry Phone #: ###-####
|
BLD-Footing | 9/24/2015 | 9/25/2015 | 9/25/2015 | P | CANC |
Jim Sly
|
|
|
Dane Phone #: ###-####
|
Case Summary (BLD) | | | 9/10/2015 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
|
Issue PAID IN FULL permit | | | 9/9/2015 | | DONE |
|
|
|
|
Place hold on job | 9/1/2015 | | 9/9/2015 | | DONE |
Brittany Hill
|
|
|
DO NOT ISSUE WITHOUT BLD15-00378
|
OVERRIDE | | | 9/1/2015 | | |
|
|
|
|
Inspection Record Card- Bld | | | 9/1/2015 | | DONE |
|
|
|
|
Telephone call | | | 9/1/2015 | | DONE |
Christina Prado
|
|
|
Called Robyn toadvise both permits are ready pending ACHD, RP, GC & Revised cert of value for issuance
|
Permit Ready to Issue | | | 9/1/2015 | | DONE |
|
|
|
***MET*** GC Form and Revised Cert of Value
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/31/2015 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 8/28/2015 | | 8/31/2015 | | PASS |
Tim L. Woodard
|
|
|
Approved for showing compliance with previously mentioned items only. A complete re-review was not done. This plans was previously fully reviewed by John Menard. TLW
|
Plan assigned to (TLW) | 5/5/2015 | | 8/31/2015 | | PASS |
Tim L. Woodard
|
|
|
1st Review Complete New Commercial - Reassigned from John Menard
|
Routing Off Site - STRUCTURAL | 8/18/2015 | | 8/31/2015 | | PASS |
Tim L. Woodard
|
|
|
|
Routing - Erosion and Sediment | 8/19/2015 | | 8/31/2015 | | PASS |
Evan Jenkins
|
|
|
Approved and stamped approved on Plans by EEJ. TLW
|
Routing - MECHANICAL | 8/28/2015 | | 8/28/2015 | | PASS |
Troy James
|
|
|
|
Routing - Design Review | 8/19/2015 | | 8/19/2015 | | PASS |
Andrea Tuning
|
|
|
|
Plan resubmittals received | | | 8/4/2015 | | DONE |
|
|
|
Two copies of Strategic SOS Stormwater Runoff Management and Treatment Calculations, Two copies of Storm Drainage System Operation and Maintenance Requirements, Three copies of Revised Structural Calculations, Two Copies of sheets A0.1, A0.2, A1.1, A1.2, A1.3, A1.4, A1.5, A1.6, A2.1, A3.1, A3.2, A3.3, A3.4, S1.0, S1.1, S1.1.1, S2.1, S1.2.1, L0.00, L1.10, L1.15, L2.10, L2.15, L3.1, M-1.0, M-2.0, P-1, P-2, E-0.0, E-0.1, E-1.0, E-2.0, E-3.0, E-4.0, and E-5.0. Taken to Tim W
|
Plan assigned to (JCM) | 2/13/2105 | | 5/5/2015 | | DEFR |
John Menard
|
|
|
1st Review Complete 3/12/2105
Reassigned to Tim Woodard
|
Route to Impact Fee Review | 3/17/2015 | 3/20/2015 | 3/26/2015 | | PASS |
Cindy M. Gould
|
|
|
|
Routing - FIRE | 3/12/2015 | | 3/17/2015 | | PASS |
Scott Arellano
|
|
|
Attached comments to plans.
|
1st review completed | | | 3/17/2015 | | FAIL |
|
|
|
Failed DR, Plan Check, Mech, Structural
|
Plan resubmittals requested | | | 3/12/2015 | | DONE |
John Menard
|
|
|
E-mailed the architect a copy of the plan review requesting revisions. JCM
|
Routing - PLAN CHECK | 2/26/2015 | | 3/12/2015 | | FAIL |
John Menard
|
|
|
|
Routing Off Site - STRUCTURAL | 3/4/2015 | | 3/4/2015 | | PASS |
John Menard
|
|
|
|
Plan resubmittals received | | | 3/3/2015 | | DONE |
|
|
|
Recieved three sets of revised plans marked S2.1, S1.1 and S1.2.1, plans inserted by arch and taken to John M for review
|
Plan resubmittals requested | | | 3/2/2015 | | DONE |
John Menard
|
|
|
E-mailed the architect a copy of the structural review requesting revisions. JCM
|
Routing Off Site - STRUCTURAL | 2/13/2015 | | 3/2/2015 | | FAIL |
John Menard
|
|
|
Received comment list from conulting structural engineer requesting revisions. JCM
|
Routing - MECHANICAL | 2/24/2015 | | 2/26/2015 | | FAIL |
Troy James
|
|
|
See TI permit for corrections
|
Plan resubmittals received | | | 2/25/2015 | | DONE |
Christina Prado
|
|
|
Received two sets revised plan sheets marked A0.2, A1.1, S1.1, m-1, P-1 & p-2; Plans inserted by arch and taken back to plan review
|
Routing - PLUMBING | 2/24/2015 | | 2/24/2015 | | PASS |
Daryl Spivey
|
|
|
Per plan and ISPC. Note on water heater pan drain and t&p drain.
|
Routing - Erosion and Sediment | 2/23/2015 | | 2/24/2015 | | PASS |
Evan Jenkins
|
|
|
(SITE PREP INSPECTION REQUIRED)
Shell and Core for Commercial Building
|
Routing - Design Review | 2/23/2105 | | 2/23/2015 | | FAIL |
Sarah Schafer
|
|
|
The applicant is required to provide a 30-foot front setback to preserve the landscape easment along Eagle Road.
|
Routing - PUBLIC WORKS | 2/18/2015 | | 2/20/2015 | | PASS |
Jennifer Bruner
|
|
|
|
Routing PW Solid Waste | 2/18/2015 | | 2/20/2015 | | PASS |
Megan Durrell
|
|
|
No trash enclosure indicated on the drawing.
Trash enclosure for sub is undersized. No dumpsters are allowed.
All tenants must use commercial cart trash/recycling service. 4 carts are allowed. All carts must be stored in the trash enclosure.
|
Routing PW Sewer Design | 2/18/2015 | | 2/19/2015 | | PASS |
Kyle S. Rosenmeyer
|
|
|
Sewer constructed under DRI 1375 in 2006.
|
Routing PW Street Lights | 2/18/2015 | | 2/19/2015 | | PASS |
Mike D Hedge
|
|
|
No street lighting required.
|
Routing PW Drainage | 2/18/2015 | | 2/19/2015 | | PASS |
Brian Murphy
|
|
|
APPROVED UNDER PREVIOUS ODI
|
Routing PW Sewer Rating | 2/18/2015 | | 2/18/2015 | | PASS |
Jennifer Bruner
|
|
|
per Architect see Sheet A1.1; Rate space with future TI
|
Routing - Addressing | 2/17/2015 | | 2/18/2015 | | PASS |
Jason C. Taylor
|
|
|
|
Routing - PLANNING Land Div | 2/13/2015 | | 2/17/2015 | | PASS |
Todd Tucker
|
|
|
Building must be moved 10 feet to the east. There is a platted 30 foot wide landscape easement along Eagle Road.
|
Plans ACCEPTED BY PLAN TECH | | | 2/13/2015 | | DONE |
Christina Prado
|
|
|
|
Intake Approval | | | 2/13/2015 | | PASS |
Carl D Madsen
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 2/13/2015 | | DONE |
Christina Prado
|
|
|
|
Pending Assignment by JCM | 2/13/2015 | | 2/13/2015 | | DONE |
John Menard
|
|
|
|
Application received | | 2/13/2015 | | | |
|
|
|
|