Permit Information
Permit NumberBLD15-01068
StatusFinaled
Name PINNACLE BUILDERS INCORPORATED
Site Address 3000 S BOWN WAY
Project NameRiverwalk Condos at Bown Cross
Customer Number 
ePlanReviewYes
Description
(RIVERWALK CONDOS)(BOWN CROSSING) Plan modification; change to drainage only **ajs** 11-20-15 Permit for 10 Unit Apartment complex and assoicated carport with surface parking on existing parking area. The NFPA 13-R fire sprinkler system is used for occupancy. To construct a 10,000 square foot three story apartment building (5,338 sq. ft. 1st story, 5,338 sq. ft. 2nd story, 1,058 sq. ft. 3rd story, the 3rd story is only available through 3 of the 2nd floor units.). All ground floor units are required to comply as Type B dwelling units. No elevator is provided in this building. Work is to include concrete footings, concrete foundations, concrete slabs on grade, wood stud bearing walls, wood stud shear walls, fiberglass shingles, fiber-cement board siding, manufactured stone veneer, 1-hr dwelling unit separations, .75 hr (45 min) minimum fire-resistance-rated doors into the atruim with 20 minute smoke- and draft-control doors, interior nonbearing walls, millwork, and finishes. Special Inspection is required for?. The roof truss design is a deferred submittal item. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13-R and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **ajs**
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Print Occupancy Form  5/9/2017 DONE
Permanent Occupancy  5/9/2017 DONE
Zoning Approval5/8/20175/8/20175/8/2017 PASS
DetailsKatelyn Menuge
Design Review Pass
PubWorks Occupancy Approval5/5/20175/5/20175/5/2017 DONE
DetailsTiffany Lowery
BLD-Final1/26/20171/27/20171/27/2017PPASS
DetailsJim Storey
Please call Jaysen when in rout, thank you. Phone #: ###-#### Inspection requested via web by Jaysen Porter no card on site
BLD-Final1/19/20171/23/20171/23/2017ANR
DetailsJim Storey
Please contact me when in route, thank you. Phone #: ###-#### Inspection requested via web by Jaysen Porter rail bothsides common exit stairs/ gaurdrail pannels to be in place.
FIRE-Final Inspection1/19/20171/20/20171/20/2017APASS
DetailsJim Page
Previously noted items have been repaired. Final fire sprinkler inspection complete, final fire alarm inspection complete, fire extinguishers are in place with current inspection tags, knox box is in place, permanent addressing was being installed at time of inspection Final life fire safety inspection passed/complete.
FIRE-Final Inspection1/18/20171/19/20171/19/2017AFAIL
DetailsJim Page
Need signage for fire alarm control panel/fire sprinkler riser room. Extinguishers need to be mounted on all three levels in the common area's.
FIRE-Final Inspection1/18/20171/18/20171/18/2017PCANC
DetailsTroy Cobbley
Rescheduled for tomorrow morning. Need the two FIR permits called in for inspection prior to a life safety inspection
BLD-Aging Inspection1/4/20171/4/20171/4/2017 PASS
DetailsJim Storey
wip
BLD-Energy code compliance8/23/20168/23/20168/23/2016PPASS
DetailsJim Storey
Jason Phone #: ###-####
BLD-Framing/Rough-in8/12/20168/12/20168/12/2016PPASS
DetailsJim Storey
Jaysen Phone #: ###-####
BLD-Framing/Rough-in7/27/20167/28/20167/28/2016AFAIL
DetailsJim Storey
Jason-please call when on your way so can meet Phone #: ###-#### cmu opening engineering/ fire dampers/ fire stopping listings
BLD-Wall Bracing7/1/20167/1/20167/1/2016APASS
DetailsJim Storey
Phone #: 2086958133 >> Inspection requested via mobile web by Jaysen Porter
BLD-Final4/27/20164/27/20164/27/2016PNH
DetailsJim Storey
would like call ahead; Cliff Phone #: ###-####
BLD-Conference4/8/20164/11/20164/11/2016ADONE
DetailsJim Storey
Travis Phone #: ###-####
BLD-Conference4/7/20164/8/20164/8/2016PNH
DetailsJim Storey
Travis Phone #: ###-#### no plans no one on site
CHANGE STATUS TO (ISS)  12/14/2015 DONE
DetailsChristina Prado
CHANGE STATUS TO (RDY)  12/14/2015 DONE
DetailsChristina Prado
Pending PWK payment
CHANGE STATUS TO (ISS)  12/14/2015 DONE
DetailsChristina Prado
Plan mod paid for
OVERRIDE  11/20/2015  
BLD-Energy code compliance11/20/201511/20/201511/20/2015PPASS
DetailsJim Storey
Rob Hadock Phone #: ###-#### sub grade insulation ok
Plan assigned to (AJS)11/17/201511/17/201511/20/2015 PASS
DetailsAdele J Schaffeld-Griffin
PLANS/APPL TAKEN TO FRONT DESK  11/20/2015 DONE
Permit Ready to Issue  11/20/2015 DONE
fees need to be paid (PWK15-00107)- do NOT re-issue
Routing - PLAN CHECK11/17/2015 11/20/2015 PASS
DetailsAdele J Schaffeld-Griffin
Routing PW Drainage11/17/2015 11/19/2015 PASS
DetailsJason C. Taylor
Re-submittal approved. PW Fees need paid. JCT
Routing - Erosion and Sediment11/17/2015 11/17/2015 PASS
DetailsEvan Jenkins
(Site Prep Inspection and Approval Required Prior to Earth Disturbance)

***Approved Dewatering Plan "Approved" by ACHD is Required Prior To Discharges leaving Construction Site.***

(RIVERWALK CONDOS)(BOWN CROSSING) Permit for 10 Unit Apartment complex and assoicated carport with surface parking on existing parking area. The NFPA 13-R fire sprinkler system is used for occupancy. To construct a 10,000 square foot three story apartment building
Routing - PUBLIC WORKS11/17/2015 11/17/2015 PASS
DetailsJennifer Bruner
Plan Modification Accepted  11/17/2015 DONE
modifications to the Civil Plans
BLD-Footing11/13/201511/13/201511/13/2015PPASS
DetailsJim Storey
Travis Phone #: ###-####
BLD-Footing10/26/201510/26/201510/26/2015PPASS
DetailsJim Storey
Travis Phone #: ###-####
Issue PAID IN FULL permit  10/6/2015 DONE
DetailsChristina Prado
Print Occupancy Form  10/6/2015 DONE
DetailsChristina Prado
Extend Review Timeline  9/30/2015 DONE
180 Days approved by JCB. See Attached Document
Telephone call  9/30/2015 DONE
Left a message for Travis that the permit was showing to expire on the 4th of October. I informed him that I say he recieved a call yesterday that his permit is ready, but suggested that he may want to send in a request for a 180 day extension if they are unable to pick up the permit by 10-4
OVERRIDE  9/29/2015  
Routing - PLAN CHECK9/10/2015 9/29/2015 PASS
DetailsAdele J Schaffeld-Griffin
Routing - Design Review9/29/2015 9/29/2015 PASS
DetailsJosh Wilson
OK per DRH15-00015
PLANS/APPL TAKEN TO FRONT DESK  9/29/2015 DONE
Permit Ready to Issue  9/29/2015 DONE
DetailsChristina Prado
All requirements met
Plan assigned to (AJS)6/15/2015 9/29/2015 PASS
DetailsAdele J Schaffeld-Griffin
1st review completed Condo's Ward S.
Routing - PLANNING9/28/2015 9/28/2015 PASS
DetailsDavid Moser
PUD14-00014 and CUP15-00075
Routing - Design Review9/10/2015 9/14/2015 FAIL
DetailsJosh Wilson
Pending Design Review appeal period expires 9-26-15.
Routing - PLANNING9/10/2015 9/11/2015 FAIL
DetailsDavid Moser
Need to wait for the 10 day appeal period (CUP15-00075) which ends on 9-18-15.
Routing - Erosion and Sediment9/10/2015 9/10/2015 PASS
DetailsEvan Jenkins
(Site Prep Inspection and Approval Required Prior to Earth Disturbance)

(RIVERWALK CONDOS)(BOWN CROSSING) Permit for 10 Unit Apartment complex and assoicated carport with surface parking on existing parking area. The NFPA 13-R fire sprinkler system is used for occupancy. To construct a 10,000 square foot three story apartment building (5,338 sq. ft. 1st story, 5,338 sq. ft. 2nd story, 1,058 sq. ft. 3rd story, the 3rd story is only available through 3 of the 2nd floor units.). All ground floor units are required to comply as Type B dwelling units. No elevator is provided in this building. Work is to include concrete footings, concrete foundations, concrete slabs on grade,
Routing - PLAN CHECK9/10/2015 9/10/2015 FAIL
DetailsAdele J Schaffeld-Griffin
returned plans without routing, drawings not uploaded correctly emailed ward.
Routing - PLAN CHECK8/18/2015 8/21/2015 FAIL
DetailsAdele J Schaffeld-Griffin
Routing - FIRE8/18/20158/18/20158/19/2015 PASS
DetailsKatie Marron
Updated report attached to case.
Routing - Erosion and Sediment8/18/2015 8/19/2015 FAIL
DetailsEvan Jenkins
Plan Designer Certification Expired this past March. Obtain Interim PD Certification by paying the $10 fee and show proof of registration to next PD course to permit technician. Evan Jenkins 794.3958
Routing - Design Review8/18/2015 8/18/2015 FAIL
DetailsJosh Wilson
Applicant has not received Design Review approval and requested that approval be put on hold until the negotiations regarding the trash enclosure have run their course. Submittal of a final site plan resolving trash enclosure issue required for Design Review approval.
Routing - PLANNING8/18/2015 8/18/2015 FAIL
DetailsDavid Moser
Applicant needs to provide a signed trash enclosure agreement with adjacent property owner - Mr. Saetrum. Or submit a CUP mod. application for a trash enclosure on site.
Routing PW Drainage7/21/2015 8/4/2015 PASS
DetailsBrian Murphy
signed off in e plan and verified approval with Jim Wylie, ajs
Routing - PLAN CHECK7/21/2015 8/3/2015 FAIL
DetailsAdele J Schaffeld-Griffin
Routing Off Site - STRUCTURAL7/21/2015 7/27/2015 PASS
DetailsAdele J Schaffeld-Griffin
2nd review
Routing - MECHANICAL7/21/2015 7/23/2015 PASS
DetailsTroy James
Routing - Design Review7/21/2015 7/22/2015 FAIL
DetailsJosh Wilson
Applicant has not received Design Review approval and requested that approval be put on hold until the negotiations reagrding the trash enclosure have run their course. Submittal of a final site plan resolving trash enclosure issue required for Design Review approval.
Routing - FIRE7/21/20157/21/20157/21/2015 FAIL
DetailsKatie Marron
Previous correction items were not appropriately addressed per resubmittal instructions.
Routing - Erosion and Sediment7/21/2015 7/21/2015 FAIL
Full ESC Narrative Required Per BCC 8-17
ESC Site Map Sufficient. Please Submit Full ESC Narrative for 2nd Review. Evan Jenkins 794.3958
Routing - PLANNING7/21/2015 7/21/2015 FAIL
DetailsDavid Moser
The Site Plan A1.0 shows a Trash Enclosure that was not on the site plan approved with PUD14-00014. This change in the project requires a CUP Mod Application.
Route to Impact Fee Review7/16/20157/19/20157/17/2015 PASS
DetailsCindy M. Gould
1st review completed  7/16/2015 FAIL
DetailsAdele J Schaffeld-Griffin
Routing - PLAN CHECK6/15/2015 7/16/2015 FAIL
DetailsAdele J Schaffeld-Griffin
Routing Off Site - STRUCTURAL6/15/2015 6/29/2015 FAIL
DetailsAdele J Schaffeld-Griffin
Routing PW Drainage6/15/2015 6/23/2015 FAIL
DetailsBrian Murphy
needs elevations near BRA need variance for1to1 slope o and m report ect.
Plan Reviewer's activity  6/23/2015 DONE
DetailsAdele J Schaffeld-Griffin
emailed ward asking for revised index, the draings do not match and if the index is correct there are sheets missing.
Routing - PLUMBING6/15/2015 6/19/2015 PASS
DetailsDaryl Spivey
Per plan and ISPC.
Routing - MECHANICAL6/15/2015 6/17/2015 FAIL
DetailsTroy James
Routing PW Sewer Rating6/15/2015 6/17/2015 PASS
DetailsJennifer Bruner
Routing - FIRE6/15/2015 6/17/2015 FAIL
DetailsScott Arellano
Report emailed to architect and attached to case.
Routing - Erosion and Sediment6/15/2015 6/16/2015 FAIL
DetailsEvan Jenkins
Full ESC Narrative Required Per BCC 8-17
ESC Site Map Sufficient. Please Submit Full ESC Narrative for 2nd Review. Evan Jenkins 794.3958
Routing PW Street Lights6/15/2015 6/16/2015 PASS
DetailsMike D Hedge
No new street lighting required.
Routing PW Sewer Design6/15/2015 6/16/2015 PASS
DetailsKyle S. Rosenmeyer
Spoke w/ Architect 6/16. Intent is to use existing sewer stub. Plumbing drawings will need to be revised to match.
Routing - PLANNING6/15/2015 6/15/2015 FAIL
DetailsDavid Moser
Failed; the site plan does not match the approved site plan as per PUD14-00014. The new site plan adds a trash enclosure, removes two parking spaces, and relocates the carports. A conditional use modification application is required for these proposed changes. In addition, the new trash enclosure will require a variance since it is not setback 5 feet from the side yard property line.
Routing - PLANNING Land Div6/15/2015 6/15/2015 PASS
DetailsDave Abo
Lot 64, Block 2 of Riverwalk Subdivision #3
Routing - Addressing6/15/2015 6/15/2015 PASS
DetailsEmily Dixon
Routing - PUBLIC WORKS6/15/2015 6/15/2015 PASS
DetailsJennifer Bruner
Routing - Design Review6/15/2015 6/15/2015 FAIL
DetailsJosh Wilson
Needs Design Review approval. Architect contacted for materials required to complete DR submittal.
Intake Approval  6/15/2015 PASS
DetailsTim L. Woodard
Pending Assignment by TLW6/15/2015 6/15/2015 DONE
DetailsTim L. Woodard
Intake Approval  5/8/2015 FAIL
Ward,
Please address the following items:
1) Please reupload all sheets to be in the horizontal position. 2)Strutural sheets also need to be broken out into individual sheets and uploaded separatly. 3)Upload a soils and geotech report. 4)Upload a Site Drainage Report. 5)Incorporate the ESC Plan Sheet into the "Plans" folder (rotate as needed). 6)Provide manual J,D, and S reports. 7)Provide additional sheets for form #310 Special Inspections. 8)Provide lighting compliance for common areas. 9)Revise Envelope Compliance to show compliance with the 2012 IECC.

Please call if you have any questions,

Tim Woodard
Plans Examiner II
Application received  4/7/2015 DONE
Application submitted via PDS Online on Apr 7 2015 10:21AM
First Notice 5/19/2017   
Routing - PLAN CHECK11/17/2015    
DetailsAdele J Schaffeld-Griffin