Print Statement | | | 8/2/2016 | | DONE |
|
|
|
|
Second Notice | | 5/22/2016 | 7/14/2016 | | DONE |
|
|
|
Mailed 7-15-16
|
First Notice | | 5/7/2016 | 5/12/2016 | | DONE |
|
|
|
Mailed 5-13-16
|
BLD-Final | 4/26/2016 | 4/27/2016 | 4/27/2016 | A | PASS |
Jim Storey
|
|
|
Larry Phone #: ###-####
|
Permanent Occupancy | | | 4/27/2016 | | DONE |
|
|
|
|
FIRE-Final Inspection | 4/25/2016 | 4/25/2016 | 4/25/2016 | P | PASS |
Jim Page
|
|
|
Previously noted items addressed/repaired. Occupancy sign was being printed at time of inspection, will be installed by general contractor. No fire sprinklers, duct detector is stand alone and tested correctly, commercial hood suppression system inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIRE-Final Inspection | 4/22/2016 | 4/22/2016 | 4/22/2016 | P | FAIL |
Troy Cobbley
|
|
|
Rear door exit discharge light can not be connected to a photo cell or timer, duct smoke detector did not shut down the hvac unit upon activation, need occupant load sign at the main exit.
|
FIRE-Final Inspection | 4/1/2016 | 4/4/2016 | 4/4/2016 | A | FAIL |
Troy Cobbley
|
|
|
Can't perform life safety until the project related hood suppression permit is finaled. Per scott and my discussion the new hood and duct smoke detector do not need to be connected to the existing fire alarm system in the day care at the south end of the building due to an existing 4 hour wall that provides separation.
|
BLD-Ceiling Grid Inspection | 3/30/2016 | 3/31/2016 | 4/1/2016 | P | PASS |
Jim Storey
|
|
|
Larry Phone #: ###-####
|
(F) Reprint permit | | | 2/17/2016 | | DONE |
|
|
|
|
BLD-Ceiling Grid Inspection | 2/3/2016 | 2/3/2016 | 2/3/2016 | P | PASS |
Jim Storey
|
|
|
Larry Phone #: ###-####
|
Zoning Approval | 1/7/2016 | 1/7/2016 | 1/7/2016 | | PASS |
Josh Wilson
|
|
|
|
BLD-Energy code compliance | 12/16/2015 | 12/17/2015 | 12/17/2015 | P | PASS |
Jim Storey
|
|
|
Larry Phone #: ###-####
|
BLD-Framing/Rough-in | 12/15/2015 | 12/16/2015 | 12/16/2015 | P | PASS |
Jim Storey
|
|
|
Larry Phone #: ###-####
|
Print Occupancy Form | | | 8/31/2015 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 8/31/2015 | | DONE |
|
|
|
|
OVERRIDE | | | 8/13/2015 | | |
|
|
|
|
Plan assigned to (AJS) | 6/18/2015 | 6/18/2015 | 8/13/2015 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
1st review completed New Structure Wok King
|
Routing - PLAN CHECK | 8/6/2015 | | 8/13/2015 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/13/2015 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/13/2015 | | DONE |
|
|
|
NEED GC form, Certificate of Value, RP, and ACHD
|
Routing Off Site - C.D.H | 8/6/2015 | | 8/6/2015 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
recieved approved sign off uploaded in documents
|
Routing - PLAN CHECK | 7/24/2015 | | 7/30/2015 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
|
Routing Off Site - C.D.H | 7/24/2015 | | 7/30/2015 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
|
Routing Off Site - STRUCTURAL | 7/24/2015 | | 7/30/2015 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
Routing Off Site - STRUCTURAL | 6/18/2015 | | 7/21/2015 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
|
Routing PW Environmental | 6/19/2015 | | 7/21/2015 | | PASS |
Rick Christenson
|
|
|
Exterior Grease Interceptor 1500 gallon located out back
|
Routing Off Site - C.D.H | 7/21/2015 | | 7/21/2015 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
We require the food facility application, plan review and food license fee, pre-operational plan review form completed and a complete plan review. Facility owners need to contact CDHD to submit all paperwork
|
1st review completed | | | 7/21/2015 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
|
Routing - PLAN CHECK | 6/18/2015 | | 7/21/2015 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
|
Routing - FIRE | 6/18/2015 | 6/18/2015 | 6/19/2015 | | PASS |
Katie Marron
|
|
|
Comments attached to case
|
Routing PW Sewer Rating | 6/19/2015 | | 6/19/2015 | | PASS |
Connie Baumgartner
|
|
|
|
Routing - MECHANICAL | 6/18/2015 | | 6/19/2015 | | PASS |
Troy James
|
|
|
Redlined drawing
|
Routing - PLUMBING | 6/18/2015 | | 6/19/2015 | | PASS |
Daryl Spivey
|
|
|
See notes under bld15-01841
|
Routing - Addressing | 6/18/2015 | | 6/19/2015 | | PASS |
Emily Dixon
|
|
|
Address corrected to 2146 S Broadway Ave.
|
Routing - PUBLIC WORKS | 6/18/2015 | | 6/19/2015 | | PASS |
Jennifer Bruner
|
|
|
|
Routing - Erosion and Sediment | 6/18/2015 | | 6/19/2015 | | PASS |
Evan Jenkins
|
|
|
REBUILD THE STRUCTURE BACK FROM A FIRE
|
Routing - Design Review | 6/18/2015 | | 6/18/2015 | | PASS |
Josh Wilson
|
|
|
|
Intake Approval | | | 6/18/2015 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
Application received | | 6/18/2015 | | | |
|
|
|
|