Permanent Occupancy | | | 10/26/2015 | | DONE |
|
|
|
|
BLD-Final | 10/19/2015 | 10/19/2015 | 10/19/2015 | P | PASS |
Dave Hannah
|
|
|
Lisa Phone #: ###-####
|
BLD-Final | 9/17/2015 | 9/18/2015 | 9/18/2015 | P | FAIL |
Phil Shearer
|
|
|
Lisa Phone #: ###-####. storage area as well as the side entrance have twist turn door handles, not paddle type.
|
FIRE-Final Inspection | 9/17/2015 | 9/18/2015 | 9/18/2015 | A | PASS |
Jim Page
|
|
|
Life fire safety passed/complete. Noted that the storage area as well as the side employee entrance have twist turn door handles, not paddle type.
|
BLD-Final | 7/2/2015 | 7/6/2015 | 7/7/2015 | P | NR |
Dave Hannah
|
|
|
Please call ahead 20min to meet - Lisa Phone #: ###-#### needs fire final first
|
FIRE-Final Inspection | 7/2/2015 | 7/6/2015 | 7/6/2015 | A | FAIL |
Jim Page
|
|
|
Fire sprinkler located in the back area of tenant space to far off of wall, head is 9ft 4in, does not meet acceptable spacing requirements for ordinary hazard, 130 square feet per head.
|
Telephone call | | | 7/6/2015 | | DONE |
|
|
|
Spoke with Lisa McGrath regarding noted correction item. Informed Lisa that the fire sprinker head spacing in noted area will need to be corrected prior to final occupancy. However, upon receiving an application for fire sprinkler permit, this office will permit a temporary certificate of occupancy (TCO) for a period of 15 days while the fire sprinkler spacing deficiency is corrected by a licensed fire sprinkler contractor. SJA
|
Plan assigned to (CJW) | 6/29/2015 | | 7/2/2015 | | PASS |
Carl Westfall
|
|
|
(July 1 - 3 days)
|
Routing - PLAN CHECK | 7/1/2015 | | 7/2/2015 | | PASS |
Carl Westfall
|
|
|
|
1st review completed | | | 7/2/2015 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/2/2015 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/2/2015 | | DONE |
|
|
|
|
Telephone call | | | 7/2/2015 | | DONE |
|
|
|
called Lisa to let know permit is ready
|
Print Occupancy Form | | | 7/2/2015 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 7/2/2015 | | DONE |
Christina Prado
|
|
|
|
Routing - Addressing | 6/29/2015 | | 7/1/2015 | | PASS |
Jason C. Taylor
|
|
|
|
Routing - PUBLIC WORKS | 7/1/2015 | | 7/1/2015 | | PASS |
Jennifer Bruner
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 6/29/2015 | | DONE |
|
|
|
|
Intake Approval | | | 6/29/2015 | | PASS |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 6/29/2015 | | DONE |
|
|
|
|
First Notice | | 11/5/2015 | | | |
|
|
|
|
Application received | | 6/29/2015 | | | |
|
|
|
|