Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberBLD15-02470
StatusFinaled
Name JORDAN WILCOMB CONSTRUCTION
Site Address 733 S PIONEER ST
Project NamePayette Brewery
Customer Number 
ePlanReviewYes
Description
(PAYETTE BREWERY) PLAN MODIFICATION FOR INTERIOR WALK IN COOLER**3-22-16 AJS**PLAN MODIFICATION TO DELETE DRINKING FOUNTAIN IN TASTING ROOM ONLY 1-21-16 **AJS**Change of use from an existing health club with office to a production brewery - office and tasting room. Work will include: loading docks, new rollup doors, metal awnings, a parapet over the east side, boiler room, new restrooms, new patio, new office layout and brewery equipment. Walk in cooler is NOT included under this permit. It will be permitted separately. Demo work will include cutting existing tilt-up concrete walls and mezzanine area. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **ajs**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice 1/16/20172/13/2017 DONE
DetailsChristina Prado
emailed to Jordan Wilcomb rep.
Third Notice 12/18/20161/11/2017 DONE
Third Notice 11/26/201612/13/2016 DONE
Third Notice 10/15/201611/21/2016 DONE
Third Notice 9/24/201610/10/2016 DONE
Third Notice 8/17/20169/19/2016 DONE
Third Notice 7/16/20168/12/2016 DONE
Second Notice 6/20/20167/11/2016 DONE
Mailed 7-12-16
First Notice 5/30/20166/10/2016 DONE
Mailed 6-13-16
BLD-Final5/19/20165/20/20165/20/2016APASS
DetailsJim Sly
Kevin Phone #: ###-####
OK for Perm Occ.
Permanent Occupancy  5/20/2016 DONE
DetailsChristina Prado
Zoning Approval5/19/20165/19/20165/19/2016 PASS
DetailsJosh Wilson
Final ok
BLD-Final5/9/20165/10/20165/10/2016APART
DetailsDave Hannah
Kevin Phone #: ###-#### ok to occ the office area
BLD-Other4/28/20164/28/20164/29/2016PDONE
DetailsDave Hannah
Hand rail // Kevin Phone #: ###-####
BLD-Conference4/29/20164/29/20164/29/2016APART
DetailsDave Hannah
Hand rail // Kevin Phone #: ###-#### ok to use mezzanine
Temporary Occupancy4/26/20167/25/20164/26/2016 DONE
DetailsCarlos Velazquez
see Jason Blais approval attached
BLD-Final4/21/20164/22/20164/25/2016PPART
DetailsDave Hannah
Kevin Phone #: ###-#### need PW inspection ok for temp occ tasting rm
PubWorks Occupancy Approval4/25/20164/25/20164/25/2016 DONE
DetailsTiffany Lowery
FIRE-Final Inspection4/21/20164/22/20164/22/2016APASS
DetailsJim Page
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with curent inspection tags. Signage for fire sprinkler riser room to be installed before final building inspection. Final life fire safety inspection passed/complete.
Zoning Approval Temp4/21/20164/21/20164/21/2016 PASS
DetailsJosh Wilson
180 day ok
BLD-Conference4/19/20164/20/20164/20/2016ADONE
DetailsDave Hannah
Kevin Phone #: ###-####
CHANGE STATUS TO (ISS)  4/13/2016 DONE
DetailsChristina Prado
OVERRIDE  3/24/2016  
Plan assigned to (AJS)3/4/20163/4/20163/24/2016 PASS
DetailsAdele J Schaffeld-Griffin
Plan mod Payetter Brewery
Routing - PLAN CHECK3/8/2016 3/24/2016 PASS
DetailsAdele J Schaffeld-Griffin
walk in coolers
PLANS/APPL TAKEN TO FRONT DESK  3/24/2016 DONE
Permit Ready to Issue  3/24/2016 DONE
DetailsChristina Prado
DO NOT RE-ISSUE - PLAN MOD APPROVED FOR DEFERRED SUBMITTAL

Must pay all fees prior to changing status to ISS
Routing - PLUMBING3/8/2016 3/11/2016 PASS
DetailsDaryl Spivey
additional cross connection protection may be required
Routing - FIRE3/8/20163/8/20163/9/2016 PASS
DetailsKatie Marron
Cooler plans reviewed. Modifications to the fire sprinkler plans/permit will be required.
Routing - MECHANICAL3/8/2016 3/8/2016 PASS
DetailsTroy James
no review required
Plan Modification Accepted  3/4/2016 DONE
DetailsChristina Prado
Deferred submittal requested for built in cooler revisions
BLD-Framing/Rough-in2/29/20163/1/20163/1/2016APASS
DetailsDave Hannah
Kevin Phone #: ###-####ext soffits
BLD-Framing/Rough-in2/18/20162/19/20162/19/2016APASS
DetailsDave Hannah
Kevin-tasting room Phone #: ###-####
Print Occupancy Form  2/5/2016 DONE
DetailsChristina Prado
BLD-Framing/Rough-in1/28/20161/29/20161/29/2016APART
DetailsMike Jordan
Ceiling // Kevin Phone #: ###-####. Provide detail for hardlids.
CHANGE STATUS TO (ISS)  1/22/2016 DONE
DetailsChristina Prado
OVERRIDE  1/21/2016  
Plan assigned to (AJS)1/21/20161/21/20161/21/2016 PASS
DetailsAdele J Schaffeld-Griffin
Plan Mod. Payette Brewery
Telephone call  1/21/2016 DONE
Mike called and said that he will let Brad know that the plan mod needs to be done online and that paper plans need to be picked up
Routing - PLAN CHECK1/21/2016 1/21/2016 PASS
DetailsAdele J Schaffeld-Griffin
plan mod to remove drinking fountain from tasting room only
Routing - PUBLIC WORKS1/21/2016 1/21/2016 PASS
DetailsRachael Beierle
PLANS/APPL TAKEN TO FRONT DESK  1/21/2016 DONE
Permit Ready to Issue  1/21/2016 DONE
DetailsChristina Prado
**DO NOT RE-ISSUE** Plan mod only

All requirements met for plan mod, must pay additional review fees prior to changing status to ISS
Plan Modification Accepted  1/21/2016 DONE
DetailsChristina Prado
Plan mod requested by architecture firm to remove existing drinking fountain
CHANGE STATUS TO (ISS)  1/20/2016 DONE
Plan Mod Should be done online
Telephone call  1/20/2016 DONE
Left a message for Mike F that the Plan modification would need to be done online since the original plans were don't online.
BLD-Framing/Rough-in1/14/20161/14/20161/15/2016PPASS
DetailsDave Hannah
Kevin Phone #: ###-####
Issue PAID IN FULL permit  12/28/2015 DONE
Print Occupancy Form  12/28/2015 DONE
Expiration Notice12/18/20151/12/201612/18/2015 DONE
DetailsBrittany Hill
OVERRIDE  12/2/2015  
Plan assigned to (AJS)7/21/20157/21/201512/2/2015 PASS
DetailsAdele J Schaffeld-Griffin
1st review completed 8/17Level 3 TI - ePlanReview - Payette Brewery
Routing - PLAN CHECK12/2/2015 12/2/2015 PASS
DetailsAdele J Schaffeld-Griffin
PLANS/APPL TAKEN TO FRONT DESK  12/2/2015 DONE
Permit Ready to Issue  12/2/2015 DONE
**MET** NEED GC Form and Certificate of value
Routing - PLUMBING11/20/2015 11/27/2015 PASS
DetailsBill VanDegrift
Routing PW Sewer Design11/20/2015 11/27/2015 PASS
DetailsMike Sheppard
signed off in e plan and grd15-00044
Routing - PLAN CHECK11/20/2015 11/27/2015 FAIL
DetailsAdele J Schaffeld-Griffin
Routing - Design Review11/20/2015 11/25/2015 PASS
DetailsJosh Wilson
Ok per DRH15-00435
Routing PW Flood Plain7/22/2015 11/25/2015 PASS
DetailsJim Wyllie
Applicant needs to submit an Elevation Certificate for the Building Permit.
Jim Wyllie / ###-####
Routing PW Flood Plain11/20/2015 11/25/2015 PASS
DetailsJim Wyllie
Routing PW Drainage11/20/2015 11/24/2015 PASS
DetailsJason C. Taylor
See GRD15-00044 for original approval- This approval was for modification. JCT
Routing PW Sewer Rating11/20/2015 11/20/2015 PASS
DetailsBeverly Mountain
Routing - MECHANICAL11/20/2015 11/20/2015 PASS
DetailsTroy James
Routing - PLANNING11/20/2015 11/20/2015 PASS
DetailsCody Riddle
Plan Reviewer's activity  11/18/2015 DONE
DetailsAdele J Schaffeld-Griffin
deleted all uploaded sheets all sheets must be named to version
Route to Impact Fee Review8/17/20158/20/20158/19/2015 PASS
DetailsCindy M. Gould
Building will remain commercial CMG
1st review completed  8/17/2015 FAIL
DetailsAdele J Schaffeld-Griffin
Routing - PLAN CHECK7/21/2015 8/17/2015 FAIL
DetailsAdele J Schaffeld-Griffin
Routing PW Drainage7/22/2015 8/17/2015 FAIL
DetailsBrian Murphy
See Grading permit for details. Jason Taylor
Routing PW Solid Waste7/22/2015 8/14/2015 PASS
DetailsMegan Durrell
Architect agreed to remove bollards in/around trash enclosure. Gates to open 120 degrees.
Routing PW Environmental7/22/2015 8/14/2015 PASS
DetailsRick Christenson
Architect notified future Pretreatment may be needed for compliance.
Routing PW Sewer Design7/22/2015 8/6/2015 FAIL
DetailsKyle S. Rosenmeyer
Provide Utility Sheet or otherwise show connection points to public sewer. New sewer connections require 48 hour notice to public works to schedule inspection and tap permit.

Grading Sheet: maximum height of grade rings is 21".
Routing PW Sewer Rating7/22/2015 7/30/2015 FAIL
DetailsBeverly Mountain
Information required from owner regarding flows prior to sign off. May require sampling station. bam
Routing - PLUMBING7/21/2015 7/28/2015 FAIL
DetailsBill VanDegrift
Install RPBP on filtered water and on boiler line. Also 4 inch drain required in room with 3 inch RPBP.
Routing - MECHANICAL7/21/2015 7/24/2015 FAIL
DetailsTroy James
Routing - FIRE7/21/20157/21/20157/23/2015 PASS
DetailsScott Arellano
Comments attached to case.
Routing PW Street Lights7/22/2015 7/23/2015 PASS
DetailsMike D Hedge
Routing - PLANNING7/21/2015 7/22/2015 FAIL
DetailsCody Riddle
Cody Riddle - CUP15-00010

Site specific condition of approval #6 required a floodplain development permit prior to issuance of construction permits. Emailed the architect/applicant this morning. CER
Routing - Design Review7/21/2015 7/22/2015 PASS
DetailsJosh Wilson
Josh Wilson - DRH15-00209
Routing - PUBLIC WORKS7/21/2015 7/22/2015 PASS
DetailsBeverly Mountain
Routing - Addressing7/21/2015 7/21/2015 PASS
DetailsEmily Dixon
Intake Approval  7/21/2015 PASS
DetailsJason Blais
Prescreen approved by Javier Guzman and plan review fees paid.
Pending Assignment by JCB7/21/2015 7/21/2015 DONE
DetailsJason Blais
Routing - Erosion and Sediment7/21/2015 7/21/2015 PASS
DetailsEvan Jenkins
(Site Prep Inspection and Approval Required prior to Earth Disturbance)
NOTE: THIS PLAN MEETS THE CITY OF BOISE BCC 8-17 ESC REQUIREMENTS, BUT NOT THE FEDERAL EPA SWPPP REQUIREMENTS. DUE TO BEING OVER AN ACRE, AN eNOI NEEDS TO BE FILED WITH THE EPA, AND MEET SWPPP REQUIREMENTS. The City cannot Fail due to this fact, since it meets the City's ESC Requirements.
Evan Jenkins ###-####

PAYETTE BREWERY) Change of use from an existing health club with office to a production brewery - office and tasting room.
Work will include: loading docks, new rollup doors, metal awnings, a parapet over the east side.
Demo work will include cutting existing tilt-up concrete walls.
Intake Approval  7/20/2015 FAIL
DetailsJavier Guzman
Please provide the following:
1. Electrical Building Plans drawn to scale on 18”x24” minimum size plan sheets
2. Erosion & Sediment Control (ESC) Plan Waiver Request Letter in lieu of an Erosion & Sediment Control plan if applicable. See form #707 – ESC Requirements for Tenant Improvements or Erosion & Sediment Control (ESC) ESC plans (2 paper copies incorporated into plans), and ESC narrative if applicable. Plans must be designed for the specific project, and be prepared and signed by a plan designer certified by Boise City. See form #707 – ESC Requirements for Tenant Improvements.
3. The submitted Drainage System Operation & Maintenance Plan is blank from page 1 to page 9, please resubmit.
4. Missing plan sheet S6.01 as shown on checklist and foundation plan sheet.
Application received  7/16/2015 DONE
Application submitted via PDS Online on Jul 16 2015 9:03AM