BLD-Final | 8/19/2015 | 8/21/2015 | 8/21/2015 | A | PASS |
Dave Hannah
|
|
|
Delta Phone #: ###-#### ext: 21
|
Permanent Occupancy | | | 8/21/2015 | | DONE |
|
|
|
|
BLD-Final | 8/11/2015 | 8/12/2015 | 8/12/2015 | A | PART |
Dave Hannah
|
|
|
214 Delta Phone #: ###-#### ok for temp occ
|
BLD-Final | 8/7/2015 | 8/6/2015 | 8/6/2015 | P | FAIL |
Dave Hannah
|
|
|
Delta(in ste 200) ext. 214 Phone #: ###-#### needs to fix door hardwear
|
FIRE-Final Inspection | 8/4/2015 | 8/6/2015 | 8/6/2015 | A | PASS |
Jim Page
|
|
|
Life fire safety passed/complete
|
FIRE-Final Inspection | 8/4/2015 | 8/4/2015 | 8/4/2015 | P | FAIL |
Jim Page
|
|
|
All exit signs inside of tenant space were not illuminated at time of inspection, exit signs are required to stay illuminated at all times. Exit discharge landings do not have emergency egress illumination, exit discharge landings are required to have emergency egress illumination. Exit signs not installed by the two east side exit discharge doors, exit sign in north/south corridor is one sided, due to location of exit sign both sides of exit sign need to indicated exit and direction of travel. More than one door associated with tenant space have double-keyed deadbolts on exterior doors, tenant space allowed one double-keyed deadbolt lock. Interior door hardware in tenant space are paddle type door handles but door handles are not single action, if locked from inside the room doors do not unlock without twisting the lock mechanism on door handle. Fire extinguishers need to be mounted, not less than 4 inches to bottom of extinguisher, not more than 48 to extinguisher mechanism.
|
Telephone call | | | 8/4/2015 | | DONE |
|
|
|
Left message for Angie informing her that the Occupancy permit is ready to be picked up.
|
Issue PAID IN FULL permit | | | 8/4/2015 | | DONE |
|
|
|
|
Plan assigned to (CDM) | | 7/29/2015 | 8/3/2015 | | PASS |
Carl D Madsen
|
|
|
|
Routing - PLAN CHECK | 7/30/2015 | | 8/3/2015 | | PASS |
Carl D Madsen
|
|
|
|
1st review completed | | | 8/3/2015 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 8/3/2015 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/3/2015 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/3/2015 | | DONE |
|
|
|
ALL REQUIREMENTS MET
|
Print Occupancy Form | | | 8/3/2015 | | DONE |
|
|
|
|
Routing - PUBLIC WORKS | | | 7/30/2015 | | PASS |
|
|
|
|
Routing - Addressing | 7/29/2015 | | 7/29/2015 | | PASS |
Emily Dixon
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 7/29/2015 | | DONE |
Christina Prado
|
|
|
|
Intake Approval | | | 7/29/2015 | | PASS |
Carl D Madsen
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 7/29/2015 | | DONE |
Christina Prado
|
|
|
|
First Notice | | 8/31/2015 | | | |
|
|
|
|
Application received | | 7/29/2015 | | | |
|
|
|
|