DOC - Permit Finaled | | | 6/19/2017 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
Building, Fire, Planning and all trade permits finaled, no cof o issed.
|
BLD-Final | 3/11/2016 | 3/14/2016 | 3/14/2016 | A | PASS |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by Clayn Sonderegger. Ok for perm occ.
|
Zoning Approval | 3/10/2016 | 3/10/2016 | 3/10/2016 | | DONE |
Andrea Tuning
|
|
|
|
BLD-Final | 3/3/2016 | 3/4/2016 | 3/4/2016 | A | NR |
Mike Jordan
|
|
|
Call prior to going Phone #: 7942509 >> Inspection requested via mobile web by Clayn. Needs zoning final. Only need to inspect upstairs restroom for ADA compliance. Everything else ok.
|
Zoning Approval | 3/4/2016 | 3/4/2016 | 3/4/2016 | | PASS |
Josh Wilson
|
|
|
|
FIRE-Final Inspection | 3/2/2016 | 3/3/2016 | 3/3/2016 | A | PASS |
Jim Page
|
|
|
Previously noted items repaired. Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers have current inspection tags. Final life fire safety inspection passed/complete.
|
FIRE-Final Inspection | 3/1/2016 | 3/2/2016 | 3/2/2016 | P | FAIL |
Troy Cobbley
|
|
|
Need the project related fire alarm permit finaled, remove the exit sign directing people to the elevator, repair the non-functional exit signs/emergency lights, provide additional signage for the elevator on the second floor.
|
BLD-Energy code compliance | 12/15/2015 | 12/15/2015 | 12/15/2015 | P | PASS |
Jim Sly
|
|
|
As late as possible Phone #: 7942509 >> Inspection requested via mobile web by Clayn
|
BLD-Framing/Rough-in | 12/15/2015 | 12/15/2015 | 12/15/2015 | P | PASS |
Jim Sly
|
|
|
As late as possible Phone #: 7942509 >> Inspection requested via mobile web by Clayn
|
BLD-Conference | 12/3/2015 | 12/3/2015 | 12/3/2015 | P | CANC |
Mike Jordan
|
|
|
As late as possible Phone #: 7942509 >> Inspection requested via mobile web by Clayn
|
BLD-Framing/Rough-in | 12/3/2015 | 12/3/2015 | 12/3/2015 | P | PASS |
Mike Jordan
|
|
|
As late as possible Phone #: 7942509 >> Inspection requested via mobile web by Clayn
|
BLD-Conference | 12/1/2015 | 12/1/2015 | 12/1/2015 | P | CANC |
Mike Jordan
|
|
|
Phone #: 7942509 >> Inspection requested via mobile web by Clayn
|
BLD-Framing/Rough-in | 12/1/2015 | 12/1/2015 | 12/1/2015 | P | PASS |
Mike Jordan
|
|
|
Phone #: 7942509 >> Inspection requested via mobile web by Clayn. upeer and lower roof framing. Will also get RFI for relocating the upper straps.
|
BLD-Other | 11/12/2015 | 11/12/2015 | 11/12/2015 | P | DEFR |
Mike Jordan
|
|
|
We plan on grouting at 2:30pm. Phone #: ###-#### Inspection requested via web by Clayn Sonderegger. Specil inspector on site.
|
BLD-Other | 11/6/2015 | 11/9/2015 | 11/9/2015 | A | PASS |
Phil Shearer
|
|
|
As early as possible Phone #: 7942509 >> Inspection requested via mobile web by Clayn. 0'-8' First lift
|
BLD-Other | 11/6/2015 | 11/6/2015 | 11/6/2015 | P | PART |
Mike Jordan
|
|
|
Block/Pre-grout/rebar inspection for 1st 8''. Grout is Monday morning at 8:30am. Phone #: ###-#### Inspection requested via web by Clayn Sonderegger. Work in progress, 0 to 8ft. elevation. High lift, cleanouts ok. PLacing grout monday morning. Special inspector will be on site.
|
BLD-Conference | 11/2/2015 | 11/3/2015 | 11/3/2015 | P | PART |
Mike Jordan
|
|
|
I have the engineers letter approving #5 bar as installed in lieu of the #6 bar specified. We will be trying to pour sometime Tuesday afternoon. Phone #: ###-#### Inspection requested via web by Clayn Sonderegger. Reviewed engineers RFI. Pending special inspection. work was in progress.
|
BLD-Conference | 11/2/2015 | 11/2/2015 | 11/2/2015 | P | NR |
Mike Jordan
|
|
|
Mike,
We anticipate having something from the engineer this morning on the rebar. We would still like to pour the walls this afternoon, if possible. With the engineer''s.response, do we still need MTI for rebar inspection? Do we need MTI for cylinders? What is the best email to send your the engineer"s response? Thanks Phone #: ###-#### Inspection requested via web by Clayn Sonderegger. No response from engineer of record for in place work or repair.
|
BLD-Conference | 10/29/2015 | 10/30/2015 | 10/30/2015 | P | CANC |
Mike Jordan
|
|
|
Please call first. Phone #: ###-#### Inspection requested via web by Clayn Sonderegger
|
BLD-Foundation | 10/30/2015 | 10/30/2015 | 10/30/2015 | P | FAIL |
Mike Jordan
|
|
|
Please call first. Phone #: ###-#### Inspection requested via web by Clayn Sonderegger. Provide the missing #6 verts a shown on approved plans, the required horizontal bars with the 180 degree hooks. provide RFI from engineer of record for fix.
|
BLD-Footing | 10/27/2015 | 10/27/2015 | 10/27/2015 | P | PASS |
Mike Jordan
|
|
|
|
BLD-Conference | 10/26/2015 | 10/27/2015 | 10/27/2015 | A | DONE |
Mike Jordan
|
|
|
Call prior to going Phone #: 2087942509 >> Inspection requested via mobile web by Clayn
|
Telephone call | | | 10/8/2015 | | DONE |
|
|
|
emailed Dianne about a check we received. The fees have already been paid so as per the request of Tammy Cox I shredded the check and sent her a copy of the for check for her records
|
Issue PAID IN FULL permit | | | 10/7/2015 | | DONE |
|
|
|
|
OVERRIDE | | | 9/18/2015 | | |
|
|
|
|
Plan assigned to (CJW) | 8/5/2015 | 8/5/2015 | 9/18/2015 | | PASS |
Carl Westfall
|
|
|
EMERALD BUILDING ELEVATOR ADDITION (Aug. 24 - 15 days) Level 3 TI - ePlanReview
|
Routing - PLAN CHECK | 9/11/2015 | | 9/18/2015 | | PASS |
Carl Westfall
|
|
|
(9-12-15) Issues resolved except for structural
(9-18-15) Approved by Structural
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/18/2015 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/18/2015 | | DONE |
Christina Prado
|
|
|
**ALL REQUIREMENTS MET AS OF 9-28-15//cdp
Need ACHD, RP, GC & Revised cert of value for issuance--- ONLY NEED ACHD as of 9-22-15- emailed Clayn fees due and let him know we still need ACHD--- KRS
|
Routing Off Site - STRUCTURAL | 9/12/2015 | | 9/17/2015 | | PASS |
Carl Westfall
|
|
|
Dave Haugland
|
Routing - Design Review | 9/12/2015 | | 9/15/2015 | | PASS |
Andrea Tuning
|
|
|
|
Plan resubmittals received | | | 9/11/2015 | | DONE |
|
|
|
|
Route to Impact Fee Review | 9/1/2015 | 9/4/2015 | 9/8/2015 | | PASS |
Cindy M. Gould
|
|
|
|
1st review completed | | | 9/1/2015 | | DONE |
|
|
|
|
Plan resubmittals requested | | | 9/1/2015 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 8/5/2015 | | 9/1/2015 | | FAIL |
Carl Westfall
|
|
|
Revised drawings required
|
Routing Off Site - STRUCTURAL | 8/5/2015 | | 8/13/2015 | | FAIL |
Carl Westfall
|
|
|
Dave Haugland
|
Routing - FIRE | 8/5/2015 | 8/5/2015 | 8/10/2015 | | PASS |
Scott Arellano
|
|
|
Comments attached to case.
|
Routing - Design Review | 8/5/2015 | | 8/5/2015 | | PASS |
Andrea Tuning
|
|
|
Andrea Tuning - CZC10-00171
|
Routing - Addressing | 8/5/2015 | | 8/5/2015 | | PASS |
Emily Dixon
|
|
|
|
Routing - PUBLIC WORKS | 8/5/2015 | | 8/5/2015 | | PASS |
Beverly Mountain
|
|
|
|
Routing - Erosion and Sediment | 8/5/2015 | | 8/5/2015 | | PASS |
Evan Jenkins
|
|
|
(EMERALD BUILDING ELEVATOR ADDITION) New exterior elevator addition, interior lobby remodel work, new lighting, HVAC diffuser relocation, extend fire sprinklers. 187 SF of Disturbance from construction activity
|
Plan Reviewer's activity | | | 8/5/2015 | | DONE |
Jason Blais
|
|
|
Emailed architect to contact ACHD to evaluate if any additional impact fees are due. Our Permit Counter will need written verification from ACHD prior to the building permit being issued.
|
Routing Off Site - STRUCTURAL | 8/5/2015 | | 8/5/2015 | | DONE |
Kristal Soland
|
|
|
Per JCB- routed to AHJ Engineers for outside structural review
|
Pending Assignment by JCB | 8/5/2015 | | 8/5/2015 | | DONE |
Jason Blais
|
|
|
|
Intake Approval | | | 8/4/2015 | | PASS |
Jason Blais
|
|
|
Prescreen approved by Tim Woodard and plan review fees paid.
|
Application received | | | 8/3/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 3 2015 5:05PM
|