BLD-Final | 5/3/2016 | 5/13/2016 | 5/13/2016 | P | PASS |
Dave Hannah
|
|
|
would like call ahead; Clint Phone #: ###-####
|
DOC - Permit Finaled | 5/13/2016 | 5/13/2016 | 5/13/2016 | P | PASS |
Dave Hannah
|
|
|
|
FIRE-Final Inspection | 5/10/2016 | 5/12/2016 | 5/12/2016 | P | PASS |
Jim Page
|
|
|
Previously noted items addressed/repaired. HVAC diffusers have been changed from a multi-direction diffuser to a single direction diffuser to help prevent false alarms from direct air flow to smoke detector. Smoke detector replacement (smoke detectors were replaced, not relocated during renovation) is being veiwed as a maintenance item per conversation with Lee Meridith. Fire extinguishers are in place with current inspection tags. No fire sprinklers, smoke detectors are stand alone, final life fire safety inspection passed/complete.
|
FIRE-Final Inspection | 5/9/2016 | 5/10/2016 | 5/10/2016 | P | FAIL |
Troy Cobbley
|
|
|
Arrived on site and met Clint. He did not have the city approved documents on site and left to get them. I started the inspection and noted that the fire extinguishers are not tagged with the annual inspection tag and several of the smoke alarms do not meet NFPA 72 spacing for being with-in 12" of the ceiling and more than 3' from supply air grills. Clint called to let me know he was on the way back and I let him know of what I found. He was not in agreement and wanted to conference with Scott about my findings. I notified Scott and spoke to Lee.
|
BLD-Aging Inspection | 2/11/2016 | 2/11/2016 | 2/12/2016 | | PEND |
Tony Young
|
|
|
|
BLD-Aging Inspection | 2/10/2016 | 2/10/2016 | 2/11/2016 | | PEND |
Tony Young
|
|
|
|
BLD-Framing/Rough-in | 9/28/2015 | 9/29/2015 | 9/29/2015 | A | PASS |
Tony Young
|
|
|
Clint-fire boxes Phone #: ###-####
|
BLD-Framing/Rough-in | 9/23/2015 | 9/23/2015 | 9/23/2015 | P | PASS |
Tony Young
|
|
|
James Phone #: ###-####
|
OVERRIDE | | | 8/25/2015 | | |
|
|
|
|
Plan assigned to (AJS) | 8/24/2015 | 8/24/2015 | 8/25/2015 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
Routing - PLAN CHECK | 8/24/2015 | | 8/25/2015 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
1st review completed | | | 8/25/2015 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/25/2015 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/25/2015 | | DONE |
|
|
|
all requirments met
|
Issue PAID IN FULL permit | | | 8/25/2015 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 8/25/2015 | | DONE |
|
|
|
|
Intake Approval | | | 8/24/2015 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
Routing - Addressing | 8/24/2015 | | 8/24/2015 | | PASS |
Emily Dixon
|
|
|
|
Routing - PUBLIC WORKS | 8/24/2015 | | 8/24/2015 | | PASS |
Jennifer Bruner
|
|
|
|
Application received | | | 8/21/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 21 2015 1:17AM
|
Intake Approval | | | 8/21/2015 | | FAIL |
David Ferguson
|
|
|
#518 - Minor Tenant Improvement Submittal Checklist
Instruction:
The checklist is not complete unless all information is filled out, all appropriate boxes are checked and all plan page numbers are listed.
No checklist was uploaded with your submittal. Please fill out and upload application #518 and resubmit.
Thank you,
Dave
|
First Notice | 5/13/2016 | 5/13/2016 | | | |
Dave Hannah
|
|
|
|