Second Notice | | 2/21/2016 | 2/22/2016 | | DONE |
|
|
|
This permit finaled on the web by Tim Scheibe
|
First Notice | | 2/6/2016 | 2/11/2016 | | DONE |
|
|
|
sent in mail 2-12-16
|
Permanent Occupancy | | | 1/27/2016 | | DONE |
|
|
|
|
BLD-Final | 1/22/2016 | 1/25/2016 | 1/25/2016 | P | PASS |
Mike Jordan
|
|
|
Tim Phone #: ###-####. Ok for perm occ.
|
FIRE-Final Inspection | 1/22/2016 | 1/25/2016 | 1/25/2016 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
FIRE-Conference | 1/21/2016 | 1/22/2016 | 1/22/2016 | A | DONE |
Troy Cobbley
|
|
|
All items have been corrected except for the bollards and the mag lock sensors/buttons.
|
BLD-Final | 1/20/2016 | 1/21/2016 | 1/21/2016 | P | NR |
Mike Jordan
|
|
|
Tim Phone #: ###-####
|
FIRE-Final Inspection | 1/20/2016 | 1/21/2016 | 1/21/2016 | A | FAIL |
Troy Cobbley
|
|
|
Repair all exit signs and emergency lights and provide testing, provide egress sensors/request to exit buttons on the doors utilizing the mag locks, remove thumbturn dead bolts, contact scott arellano for guidence on the too narrow drive way around the south side of building and the now blocked off fire dept access from the adjoinging parking lot due to the new fence and three manual gates to the property that are not shown on the city approved plans.
|
BLD-Other | 1/4/2016 | 1/5/2016 | 1/5/2016 | A | PASS |
Mike Jordan
|
|
|
Tim-Garage door Phone #: ###-####
|
FIRE-Final Inspection | 12/10/2015 | 12/11/2015 | 12/11/2015 | A | FAIL |
Troy Cobbley
|
|
|
Tim and I discussed the need for a fire alarm permit. Project is not ready for fire life safety yet.
|
FIRE-Final Inspection | 11/23/2015 | 11/23/2015 | 11/24/2015 | P | FAIL |
Troy Cobbley
|
|
|
Not ready for a final due to the fire sprinkler permit in the review status and no fire alarm permit even submitted yet. I did go over emergency light requierments with the electrician.
|
FIRE-Final Inspection | 11/10/2015 | 11/10/2015 | 11/10/2015 | P | FAIL |
Troy Cobbley
|
|
|
Repair all exit signs and emergency lights, provide emergency lighting ina all paths of travel. Fire sprinkler coverage is missing in several rooms and possibly blocked in another with painted sprinkler heads. Sprinkler contractor to provide modifications. Install all ceiling tile. Provide verification that the fire alarm system is being monitored. Fire alarm system notification is missing in many areas and overspaced in others. Fire alarm contractor to provide modifications. Provide single action hardware for all exterior doors. Remove dead bolts from exterior doors. All access controlled egress doors to meet IFC 1008.1.9.8 or 1008.1.9.9. Provide fire extinguishers on mezzanines. The wall layout/mezzanines are not shown on the plans/does not match plans. Please verify with building plan reviewer.
I suggested to the contractor that a fire sprinkler contractor and a fire alarm contractor walk the building and provide code compliant systems.
|
BLD-Conference | 11/2/2015 | 11/2/2015 | 11/2/2015 | P | PART |
Mike Jordan
|
|
|
Tim Phone #: ###-####. The 3,000 s.f. remodel portion is completed. Owner is hiring his own trades to complete the remainderr of the work. Owner will need to call for a final inspection after trades are finaled prior to occupancy.
|
BLD-Final | 10/23/2015 | 10/27/2015 | 10/27/2015 | A | FAIL |
Mike Jordan
|
|
|
Tim Phone #: ###-####. Provide all special inspection reports, Permits shows that mech, electrical and plumbing permits are required. A fire/life/safety final inspection is required. Also framing for fur down? A correrction notice was issued.
|
Print Occupancy Form | | | 10/13/2015 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 10/13/2015 | | DONE |
|
|
|
|
OVERRIDE | | | 10/6/2015 | | |
|
|
|
|
Plan assigned to (JG) | 9/24/2015 | 9/24/2015 | 10/6/2015 | | PASS |
Javier Guzman
|
|
|
1st review completed, Pending Sp. Insp form, 10/07 L2 Enviro - Tech
|
Plan resubmittals received | | | 10/6/2015 | | DONE |
|
|
|
received one copy of #310 form- put with plans on Javier's desk
|
Routing - PLAN CHECK | 10/6/2015 | | 10/6/2015 | | PASS |
Javier Guzman
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/6/2015 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/6/2015 | | DONE |
|
|
|
NEED RP, GC FORM AND REVISED CERT OF VALUE
|
1st review completed | | | 10/5/2015 | | FAIL |
Javier Guzman
|
|
|
|
Routing - PLAN CHECK | 9/24/2015 | | 10/5/2015 | | FAIL |
Javier Guzman
|
|
|
Pending special inspection form from engineer
|
Routing - FIRE | 9/24/2015 | 9/24/2015 | 9/28/2015 | | PASS |
Katie Marron
|
|
|
Report attached to case.
|
Routing - Erosion and Sediment | 9/24/2015 | | 9/25/2015 | | PASS |
Evan Jenkins
|
|
|
Demolition 2 walls and add exterior garage ground level door
|
Intake Approval | | | 9/24/2015 | | PASS |
David Ferguson
|
|
|
|
Routing - Addressing | 9/24/2015 | | 9/24/2015 | | PASS |
Emily Dixon
|
|
|
|
Routing - PUBLIC WORKS | 9/24/2015 | | 9/24/2015 | | PASS |
Jennifer Bruner
|
|
|
|
Routing - Design Review | 9/24/2015 | | 9/24/2015 | | PASS |
Andrea Tuning
|
|
|
|
Intake Approval | | | 9/23/2015 | | FAIL |
David Ferguson
|
|
|
Tim, after reviewing your latest submittal, it appears that the following items are still needed.
1) Upload each large plan sheet individually so that all 3 sheets are not in one file
2) Provide a Table of Contents on the Cover Page
3) Provide a Zoning Certificate from our Planning Department (Andrea Tunning can probably help with this)
If you run into difficulties with our ePlan review system, please contact Christina Prado at ###-#### for assistance.
|
Intake Approval | | | 9/17/2015 | | FAIL |
David Ferguson
|
|
|
Please see the redlined Checklist that you submitted for missing items. These include the following:
1) No Key Plan
2) No exterior elevations for new door
3) No Table of Contents
4) No approval letter from Planning for the exterior changes
5) No Erosion and Sediment Control waiver from Erosion Control
|
Intake Approval | | | 9/15/2015 | | FAIL |
David Ferguson
|
|
|
Checklist was not uploaded
|
Application received | | | 9/6/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 6 2015 12:38PM
|