Print Occupancy Form | | | 4/20/2016 | | DONE |
|
|
|
|
Permanent Occupancy | | | 4/20/2016 | | DONE |
|
|
|
|
BLD-Final | 4/18/2016 | 4/18/2016 | 4/18/2016 | P | PASS |
Jim Sly
|
|
|
Greg Phone #: ###-####
|
FIRE-Final Inspection | 4/15/2016 | 4/18/2016 | 4/18/2016 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed. All items corrected. A sprinkler system analysis has been provided showing that Class 1 - 3 can be stored up to 20'. Per a discussion with Tim Frost and a review of the provided documentation it appears the the commodity is a Class IV which per NFPA 13 (see page 133) only allows a maximum storage height of 12'-0". On page 136 of NPFA 13 only a Class I will be allowed to be stored to 20'-0". So the maximum storage height allowed for the commodity stored will be 12'-0". All aisle widths to be a minimum of 44". I spoke to Greg McRoberts about these conditions. Side note: the previous product stored at 14'-0" has been reduced to 11'-0" at the time of inspection.
|
FIRE-Final Inspection | 4/12/2016 | 4/15/2016 | 4/15/2016 | A | CANC |
Jim Page
|
|
|
Customer called in for Monday morning since no one showed between 8-12 Friday. Greg Phone #: ###-####
|
FIRE-Final Inspection | 3/17/2016 | 3/18/2016 | 3/18/2016 | A | FAIL |
Troy Cobbley
|
|
|
Provide city approved plans, repair emergency lights, provide additional fire exitinguisher as discussed, provide sprinkler analysis for the high piled storage that is being utilized. I measured the storage at over 14'-0".
|
Plan Reviewer's activity | | | 3/18/2016 | | DONE |
|
|
|
See documents for existing hydraulic information,
|
Issue PAID IN FULL permit | | | 2/25/2016 | | DONE |
|
|
|
|
Plan assigned to (CJW) | 2/1/2016 | 2/1/2016 | 2/8/2016 | | PASS |
Carl Westfall
|
|
|
(Feb 5 - 5 days)
|
Routing - PLAN CHECK | 2/1/2016 | | 2/8/2016 | | PASS |
Carl Westfall
|
|
|
Plan review completed
|
1st review completed | | | 2/8/2016 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/8/2016 | | DONE |
|
|
|
|
Print Occupancy Form | | | 2/8/2016 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/8/2016 | | DONE |
|
|
|
|
Telephone call | | | 2/8/2016 | | DONE |
|
|
|
called Greg to let know permit is ready and that when he comes in we can set his inspections up if he's ready
|
Routing - Addressing | 2/1/2016 | | 2/1/2016 | | PASS |
Laura Hunter
|
|
|
|
Routing - PUBLIC WORKS | 2/1/2016 | | 2/1/2016 | | PASS |
Jennifer Bruner
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 2/1/2016 | | DONE |
|
|
|
|
Intake Approval | | | 2/1/2016 | | PASS |
Carl Westfall
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 2/1/2016 | | DONE |
|
|
|
|
First Notice | | 4/30/2016 | | | |
|
|
|
|
Application received | | 2/1/2016 | | | |
|
|
|
|