Permit Information
Permit NumberBLD16-02979
StatusFinaled
Name SHUCKLE LLC
Site Address 7655 N JENNIE LN
Project NameRiver Academy
Customer NumberESC16-01122
ePlanReviewYes
Description
(RIVER ACADAMY/EXPERT REALTY) (CUP occ load max 120 for daycare) "" PLAN MODIFICATION TO ADD A TYPE 1 HOOD"" ""PLAN MODIFICATION TO ADD A 1,500 GALLON GREASE INTERCEPTOR) Permit for the construction of a new 10,030 sq. ft. 2 story building with 8,220 sq. ft. on the first story and 1,810 sq. ft. on the second story, work to include general site and utility work and the construction of a two story wood framed structure per the approved plans and the attached engineering. The real estate office and the daycare have the same owner with the real estate office also utilized as support office space for the daycare. In the event that real-estate portion of the business is leased to an outside entity a separate C of O will be required for each entity. This building is to be fully fire sprinklered. CDM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Meeting  3/25/2019 DONE
Went over final numbers in detail with Steve Ellis with Shuckle LLC. Final value submitted on 8/14/18 included many items not included with definition of Project Value. New final cert of value submitted for $1,151,762.19. Original value at time of permit issuance was $1,200,000.00. No final value fees for BLD permit due.
Print Statement  3/14/2019 DONE
3rd late notice sent
Print Statement  2/6/2019 DONE
sent 2nd late notice
Print Statement  11/23/2018 DONE
sent 1st late notice
Print Statement  10/3/2018 DONE
Print Statement  8/16/2018 DONE
First Notice 8/5/20188/8/2018 DONE
mailed 8-10-18
Permanent Occupancy  7/26/2018 DONE
BLD-Final7/18/20187/18/20187/19/2018PPASS
DetailsTony Young
need pass final for perm occ (not sure if you need to go out or not?) Steve Ellis Phone #: ###-####
BLD-Aging Inspection7/2/20187/2/20187/5/2018 PASS
DetailsTony Young
PubWorks Occupancy Approval6/26/20186/26/20186/26/2018 DONE
DetailsTiffany Lowery
Temporary Occupancy5/31/20188/29/20185/31/2018 DONE
DetailsCandy A. Nichols
5-31-18 JB ok'd temp c of o extension from 6/3/18
Telephone call  5/31/2018 DONE
called Steve to let know that the temp c of o will expire 6/3/18-he will email Jason Blais for an extension
BLD-Aging Inspection4/30/20184/30/20185/1/2018 PASS
DetailsTony Young
BLD-Final4/30/20184/30/20184/30/2018PPART
DetailsTony Young
Steve Phone #: ###-####,, ok pending others
Zoning Approval4/27/20184/27/20184/27/2018 DONE
DetailsKatelyn Menuge
2-28-18
Temporary Occupancy3/5/20186/3/20183/5/2018 DONE
DetailsBrittany Hill
BLD-Final2/28/20183/1/20183/1/2018PPART
DetailsTony Young
still need GRD permit finaled as well as ELE Steve Phone #: ###-####,, temp. occupancy ok
FIRE-Final Inspection2/28/20183/1/20183/1/2018APASS
DetailsTroy Cobbley
Life safety passed

Steve Phone #: ###-####
FIRE-Final Inspection2/27/20182/27/20182/27/2018PFAIL
DetailsTroy Cobbley
Need the project related fire sprinkler underground and overhead permits finaled. Need the project related fire alarm permit finaled. A stand alone smoke alarm is being required to be added in the Infant room as per the Assistant Fire Marshal. A separate permit is needed for the second business located in this building. Deadbolts need to be removed. Approved hardware is needed on the Restroom Barn Doors. Fire extinguishers need to be mounted. Exit signs and emergency lights need to be tested. Small documents need to be on site. An address needs to be installed as discussed.


Steve-please call 10 minutes prior to meet-wants to go threw inspection with him Phone #: ###-####
FIRE-Conference2/23/20182/23/20182/23/2018PDONE
DetailsJim Page
Fire conference complete. Provide panic hardware on southwest exterior gate. Provide knox box by main entry. Verify door hardware is code compliant on level 2 balcony door. provide fire extinguishers throughout building. Provide correct size for address numbering.
Print Occupancy Form  2/21/2018 DONE
BLD-Energy code compliance12/21/201712/21/201712/21/2017PPASS
DetailsTony Young
Steve Phone #: ###-####
BLD-Energy code compliance12/15/201712/15/201712/18/2017PPART
DetailsDave Hannah
Steve Phone #: ###-#### front office area and back two class rooms ok to cover
BLD-Framing/Rough-in12/11/201712/12/201712/12/2017APASS
DetailsDave Hannah
final framing and energy seal // Steve Ellis Phone #: ###-#### ok to insulate
CHANGE STATUS TO (ISS)  12/11/2017 DONE
plan mod paid
BLD-Framing/Rough-in12/7/201712/7/201712/7/2017PCANC
DetailsDave Hannah
.
BLD-Framing/Rough-in12/7/201712/7/201712/7/2017PPEND
DetailsDave Hannah
needs air seal package installed needs fire blocking int shear finised do not insulate framing is ok
Plan assigned to (CDM)10/25/201710/25/201712/7/2017 PASS
DetailsCarl D Madsen
Plan Mod River Academy
Routing - PLAN CHECK12/6/2017 12/7/2017 PASS
DetailsCarl D Madsen
PLANS/APPL TAKEN TO FRONT DESK  12/7/2017 DONE
Permit Ready to Issue  12/7/2017 DONE
PLAN MOD DO NOT REISSUE
BLD-Framing/Rough-in11/20/201711/20/201711/22/2017PPART
DetailsDave Hannah
call 1 hr prior // framing/conference // Victor Phone #: ###-#### ok to cover shear wall at stairs
Routing - PLAN CHECK10/26/2017 11/5/2017 FAIL
DetailsCarl D Madsen
Routing - FIRE10/30/201710/30/201711/1/2017 PASS
DetailsScott Arellano
Revised to add Type I hood
Routing - MECHANICAL10/30/2017 10/30/2017 PASS
DetailsTroy James
Routing PW Environmental10/26/2017 10/27/2017 PASS
DetailsRick Christenson
Routing - PUBLIC WORKS10/26/2017 10/26/2017 PASS
DetailsRachael Beierle
Routing - PLUMBING10/26/2017 10/26/2017 PASS
DetailsBill VanDegrift
Per plan and ISPC.
Plan Modification Accepted  10/25/2017 DONE
Plan mod accepted thru e plan-new lamont (?) to kitchen-sheets M1.00, M2.00, M3.00 & P3.00-assigned to Carl M
BLD-Wall Bracing9/20/20179/21/20179/21/2017PPASS
DetailsTony Young
Shear // Victor Phone #: ###-####
BLD-Wall Bracing9/19/20179/20/20179/20/2017PPART
DetailsTony Young
Shear // Victor Phone #: ###-####,, work in progress,, ok
BLD-Wall Bracing9/19/20179/19/20179/19/2017PPART
DetailsTony Young
Victor Phone #: ###-####,, work in progress, ok so far
BLD-Wall Bracing9/18/20179/19/20179/19/2017APART
DetailsTony Young
Victor Phone #: ###-####,, work in progress
BLD-Wall Bracing9/15/20179/18/20179/18/2017APART
DetailsTony Young
Victor Phone #: ###-####,, on site conf,, work in progress east side,, ok so far
BLD-Wall cover9/15/20179/15/20179/15/2017PNR
DetailsTony Young
Victor Phone #: ###-####,, walk around part,, needs too much,, re-nail and re-call
BLD-Framing/Rough-in9/15/20179/15/20179/15/2017PNR
DetailsTony Young
Victor Phone #: ###-####
BLD-Wall Bracing9/6/20179/7/20179/7/2017ACANC
DetailsJim Sly
left off piece of shear to see fire wall blocking // Victor Phone #: ###-####
BLD-Framing/Rough-in9/6/20179/7/20179/7/2017APART
DetailsJim Sly
left off piece of shear to see fire wall blocking // Victor Phone #: ###-####
Verified fireblocking in place........OK to cover 2nd story Mechanical area.......Both sides of walls.
Print Occupancy Form  8/17/2017 DONE
BLD-Aging Inspection7/13/20177/13/20177/14/2017 PASS
DetailsTony Young
BLD-Aging Inspection7/12/20177/12/20177/12/2017 PEND
DetailsTony Young
Telephone call  5/5/2017 DONE
DetailsScott Arellano
Spoke with General Contractor (John Andry w/ Wright Bros) and informed John that the underground fire sprnkler supply must be installed under an issued fire sprinkler permit holding a valid fire sprinkler contrctor license through the State of Idaho. John said he will contact a license fire sprinkler contractor to right away.
BLD-Foundation2/27/20172/28/20172/28/2017APASS
DetailsTony Young
Mark-rebar-trash enclosure Phone #: ###-####,, also verified stem wall insulation,, and pier for south entry canopy
CHANGE STATUS TO (ISS)  2/27/2017 DONE
Plan mod
(F) Reprint permit  2/27/2017 DONE
Plan assigned to (CDM)12/21/201612/21/20161/20/2017 PASS
DetailsCarl D Madsen
Routing - PLAN CHECK12/23/2016 1/20/2017 PASS
DetailsCarl D Madsen
PLANS/APPL TAKEN TO FRONT DESK  1/20/2017 DONE
Permit Ready to Issue  1/20/2017 DONE
DO NOT RE- ISSUE This is a PLAN MOD
Routing PW Environmental12/27/2016 1/19/2017 PASS
DetailsRick Christenson
Routing - PLUMBING12/27/2016 12/27/2016 PASS
DetailsBill VanDegrift
Per plan and ISPC.
Routing - PUBLIC WORKS12/23/2016 12/27/2016 PASS
DetailsRachael Beierle
Routing PW Drainage12/27/2016 12/27/2016 PASS
DetailsBrian Murphy
Plan Modification Accepted  12/21/2016 DONE
DetailsChristina Prado
Plan Modification to add grease interceptor to building
BLD-Foundation12/19/201612/20/201612/20/2016APART
DetailsTony Young
Mark Phone #: ###-####,, special inspector on site.. ok,, pending final report
BLD-Footing12/13/201612/14/201612/14/2016APART
DetailsTony Young
Mark Phone #: ###-####,, ok pending special inspection
Issue PAID IN FULL permit  12/13/2016 DONE
Print Occupancy Form  12/13/2016 DONE
Plan assigned to (CDM)9/1/20169/1/201612/12/2016 PASS
DetailsCarl D Madsen
First review completed
Routing - PLAN CHECK11/9/2016 12/12/2016 PASS
DetailsCarl D Madsen
Routing - PLAN CHECK12/1/2016 12/12/2016 PASS
DetailsCarl D Madsen
Routing Off Site - STRUCTURAL12/1/2016 12/12/2016 PASS
DetailsCarl D Madsen
PLANS/APPL TAKEN TO FRONT DESK  12/12/2016 DONE
Permit Ready to Issue  12/12/2016 DONE
***ACHD in docc everythoing else has been met***Need ACHD, GC Form, Revised cert of Value. Per Andy ESC16-01122 will be used on this building permit too
Routing - Design Review12/1/2016 12/1/2016 PASS
DetailsJosh Wilson
Routing Off Site - STRUCTURAL11/9/2016 11/17/2016 FAIL
DetailsCarl D Madsen
Routing - Design Review11/9/2016 11/15/2016 PASS
DetailsJosh Wilson
OK per DRH16-00490
Routing - PLAN CHECK10/21/2016 11/5/2016 FAIL
DetailsCarl D Madsen
Routing Off Site - STRUCTURAL10/21/2016 11/5/2016 FAIL
DetailsCarl D Madsen
Routing - Design Review10/21/2016 10/26/2016 FAIL
DetailsJosh Wilson
Design Review modification for revised elevations not received.
Routing PW Drainage10/24/2016 10/25/2016 PASS
DetailsBrian Murphy
Routing - FIRE10/21/201610/21/201610/24/2016 PASS
DetailsKatie Marron
Revised report attached to case.
Routing PW Solid Waste10/24/2016 10/24/2016 PASS
DetailsEvan Carpenter
Solid waste enclosure is OK as planned.
Routing - PUBLIC WORKS10/21/2016 10/24/2016 PASS
DetailsRachael Beierle
Route to Impact Fee Review10/5/201610/8/201610/10/2016 PASS
DetailsCindy M. Gould
1st review completed  10/5/2016 FAIL
Routing - PLAN CHECK9/1/2016 10/5/2016 FAIL
DetailsCarl D Madsen
Routing Off Site - STRUCTURAL9/1/2016 10/5/2016 FAIL
DetailsCarl D Madsen
Routing - MECHANICAL9/26/2016 9/26/2016 PASS
DetailsTroy James
Routing PW Drainage9/1/2016 9/19/2016 FAIL
DetailsBrian McGowan
need apdx j signed ect crossdrainage access agreement swale 3 to 1 ect
Routing PW Sewer Design9/1/2016 9/14/2016 PASS
DetailsKyle S. Rosenmeyer
Connecting to 2 existing sewer stubs into the property.
Routing PW Solid Waste9/1/2016 9/9/2016 FAIL
DetailsEvan Carpenter
Need 50' of straight line approach for truck to be able to access dumpster. This enclosure only has approx. 30' before the parking lot edge on the adjacent parcel.
Routing - Erosion and Sediment9/1/2016 9/7/2016 PASS
DetailsAndy J. Long
ESC narrative and site map submitted and approved. Valid PD designated, RP to be designated upon contract reward.
Routing - MECHANICAL9/1/2016 9/7/2016 FAIL
DetailsTroy James
Routing - FIRE9/1/20169/1/20169/6/2016 FAIL
DetailsKatie Marron
Report attached to case and emailed to architect.
Routing - ELECTRICAL9/1/2016 9/3/2016 PASS
DetailsJavier Guzman
Routing - PLUMBING9/1/2016 9/2/2016 PASS
DetailsDaryl Spivey
Per plan and ISPC.
Routing - Design Review9/1/2016 9/2/2016 FAIL
DetailsJosh Wilson
Submit a Modification to the approved Design Review for the revised elevations.
Routing - PLANNING Land Div9/1/2016 9/1/2016 PASS
DetailsTodd Tucker
Routing - Addressing9/1/2016 9/1/2016 PASS
DetailsLaura Hunter
Changed address to 7655 N Jennie Ln with 7563 N Jennie Ln being the new address for the future building pad
Routing - PUBLIC WORKS9/1/2016 9/1/2016 PASS
DetailsRachael Beierle
Routing PW Street Lights9/1/2016 9/1/2016 PASS
DetailsTom Marshall
Intake Approval  9/1/2016 PASS
Intake Approval  8/24/2016 FAIL
Please provide the following items. 1st pre-screen 8-24-16 Carl Madsen ###-####
1. Form 310 special inspections is required to be signed by the owner.
2. Registered design professional form 304 to be signed by the owner.
3. Structural calculations.
4. Central district health stamp and application.
5. Site specific fire flow letter.
6. Permanent O&M agreement (contact Brian Murphy ###-####)
7. Remove stamps from plans indicating preliminary some of the sheets in the storm water report have a preliminary stamp on the sheets.
8. Provide an ESC narrative.
9. Provide a comcheck with the correct address not Emmett Idaho.
10. Indicate the site address on the lighting compliance forms.
11. Provide matching compliance reports either Ashrae or IECC all report are required to use the same standard.
12. Please provide the commissioning report.
Application received  8/11/2016 DONE
Application submitted via PDS Online on Aug 11 2016 7:39PM