Permit Information
Permit NumberBLD16-03574
StatusFinaled
Name CHAMISA BUILDING CO INC
Site Address 7500 W MOSSY CUP ST
Project NameNxEdge
Customer Number 
ePlanReviewYes
Description
(NXEDGE) Permit for the installation of 3 new acoustic spray booths and the associated make-up air untis to the roof on new curbs. There are minor modifications required to be made to the existing roof trusses per the attached engineer and engineering details. This building has both H-3 and F-1 occupancies. All new work will occur in the F-1 area with no modifications being made to the H-3 portion of the building. This is a fully fire sprinklered building for area increase and the H occupancy and has an alarm system. Any alterations to the sprinkler system will require a separate permit and shall comply with NFPA 13 nad 72 as regulated by the fire department. There is no change in occupant loads or occupancy classification. A certificate of compliance is to be issued upon approval and completion of this project. CDM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice1/23/20171/23/20172/13/2017 DONE
DetailsMike Jordan
Mailed 2-14-17
BLD-Final1/23/20171/23/20171/23/2017PPASS
DetailsMike Jordan
Jack Phone #: ###-####
DOC - Permit Finaled1/23/20171/23/20171/23/2017PPASS
DetailsMike Jordan
FIRE-Final Inspection1/13/20171/13/20171/13/2017PPASS
DetailsTroy Cobbley
Life safety passed
FIRE-Final Inspection1/11/20171/11/20171/11/2017PFAIL
DetailsTroy Cobbley
Need the project related fire alarm permit inspected. Need to verify the exit signs and emergency lights and need verification of an "operation permit for hot work" as per review note #3.
BLD-Framing/Rough-in12/27/201612/27/201612/27/2016PPASS
DetailsMike Jordan
Jack Phone #: ###-####. Truss modifications ok. Curb detail deleted. New manufactured curbs installed with booths.
Issue PAID IN FULL permit  11/1/2016 DONE
Inspection Record Card- Bld  11/1/2016 DONE
Plan assigned to (CDM)10/18/201610/18/201610/31/2016 PASS
DetailsCarl D Madsen
NxEdge first review completed
Routing - PLAN CHECK10/28/2016 10/31/2016 PASS
DetailsCarl D Madsen
Routing - MECHANICAL10/28/2016 10/31/2016 PASS
DetailsTroy James
PLANS/APPL TAKEN TO FRONT DESK  10/31/2016 DONE
Permit Ready to Issue  10/31/2016 DONE
need GC & rev cert of val
Routing PW Environmental10/18/2016 10/21/2016 PASS
DetailsRick Christenson
1st review completed  10/21/2016 FAIL
Routing - PLAN CHECK10/18/2016 10/21/2016 PASS
DetailsCarl D Madsen
Routing - FIRE10/18/201610/18/201610/20/2016 PASS
DetailsKatie Marron
Comments attached to case.
Routing - Design Review10/18/2016 10/20/2016 PASS
DetailsSarah Schafer
Routing - MECHANICAL10/18/2016 10/18/2016 FAIL
DetailsTroy James
Routing - Addressing10/18/2016 10/18/2016 PASS
DetailsLaura Hunter
Routing - PUBLIC WORKS10/18/2016 10/18/2016 PASS
DetailsRachael Beierle
Intake Approval  10/18/2016 PASS
DetailsDavid Ferguson
Intake Approval  10/17/2016 FAIL
DetailsDavid Ferguson
See the #520 checklist that I uploaded into your ePlan project to see where I've clouded some items that you will need to provide.

Also, I deleted the three new mechanical sheets that were uploaded. They were upload vertically and they need to be horizontal. So, please upload those in a horizontal orientation.
Intake Approval  9/28/2016 FAIL
DetailsDavid Ferguson
This is a Major TI not a minor and other documents for a # 520 will be required. Mechanical cannot be submitted as a design build. Cut sheets for the pre-fab spray booths will be required.
Application received  9/27/2016 DONE
Application submitted via PDS Online on Sep 27 2016 3:30PM