Permit Information
Permit NumberBLD17-00058
StatusFinaled
Name KIER CONSTRUCTION CORPORATION
Site Address 7353 W VICTORY RD
Project NameMaverik #565
Customer Number 
ePlanReviewYes
Description
(MAVERIK #565) //Plan modification to structural canopy framing, structural side entry footing, structural heavy timber, storefront area overhead beams, structural overhead beam at beer cooler, structural connection to HSS, structural joist bearing on beam, sink support, select interior and exterior finishes, men’s and women’s accessible restroom layout, kitchen equipment layout, relocation and added floor sinks, floor drains and sinks at kitchen area, millwork, exterior air barrier type, interior and exterior lighting, plumbing, mechanical, electrical, exterior work and site work. 11-28-2017 JG// Permit to construct a new 5,524 sq., ft. building one story metal stud framed convenience store, two fuel canopies (auto canopy is 207’ x 26’ and RV canopy 64’ x 26’), three trellis’s and related site improvements. Scope of work includes: construction of a slab on grade concrete, foundation, construction of steel stud framed exterior envelope walls, roof construction, construction of interior non-bearing walls to create a retail area, an office, an electrical room, men’s and women’s accessible restrooms, kitchen area, and storage areas, (4) coolers, new windows and doors, new electrical, new mechanical, new plumbing, site work, and interior finishes to be in compliance with Ch. 8 of the 2012 IBC. The building is not fire sprinklered. Note: Special Inspections Required see form 310. **JG**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice 7/15/20187/27/2018 DONE
This permit finaled on the web by Monica Hurst
Third Notice 6/16/20187/10/2018 DONE
MAILED 7-11-18
Second Notice 5/21/20186/11/2018 DONE
Mailed 6-12
First Notice 4/26/20185/11/2018 DONE
mailed 5-14
Permanent Occupancy  4/16/2018 DONE
BLD-Final4/3/20184/3/20184/3/2018PPASS
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Roger Graves. All issues have been resolved. Ok for perm occ.
Zoning Approval4/3/20184/3/20184/3/2018 DONE
DetailsSarah Schafer
Final Approval - curb installed.
BLD-Final3/20/20183/21/20183/21/2018APART
DetailsMike Jordan
late am please Phone #: ###-#### Inspection requested via web by Roger Graves. Ok for temp occ. Needs smoke and flame spread values for foam plastics on walk in cooler and can not verify tempered glazing in door to office.
Temporary Occupancy3/21/20186/19/20183/21/2018 DONE
DetailsBrittany Hill
PubWorks Occupancy Approval3/21/20183/21/20183/21/2018 DONE
DetailsTiffany Lowery
Zoning Approval Temp3/21/20183/21/20183/21/2018  
DetailsSarah Schafer
A bond for $1760 was posted for the improvements within Sorenson. The improvements were from direction of City Council via the rezone and annexation. ACHD inspector STEVE had told contractor the work wasn't needed per their requirements so they removed the work, not realizing it was a COB/DR requirement. Sub has been contacted but it will be a couple of days before they can be back on the job site.
BLD-Final3/19/20183/19/20183/19/2018PNR
DetailsMike Jordan
Needs zonimg and public works finals.
BLD-Final3/16/20183/19/20183/19/2018ACANC
DetailsMike Jordan
Requesting a late am inspection Phone #: ###-#### Inspection requested via web by Roger Graves
FIRE-Final Inspection3/13/20183/15/20183/15/2018PPASS
DetailsTroy Cobbley
Life safety passed.

Phone #: ###-#### Inspection requested via web by Roger Graves
BLD-Final3/13/20183/15/20183/13/2018PCANC
DetailsMike Jordan
I will have an electrician and HVAC rep available in the afternoon for the inspection. A scheduled time of inspection would be appreciated. Phone #: ###-#### >> Inspection requested via web by Roger Graves Inspection cancelled from web by: Roger Graves
FIRE-Final Inspection3/12/20183/13/20183/13/2018AFAIL
DetailsTroy Cobbley
Provide sign off from Boise FIre Dept, repair exit sign at west end of corridor, repair exit discharge light at west main exit, provide testing of communication, emergency stops and duct smoke detectors, remove dead bolt on the beer cooler, provide address numbers facing Cole Rd.

Phone #: ###-#### Inspection requested via web by Roger Graves
BLD-Ceiling Grid Inspection2/13/20182/14/20182/14/2018APASS
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Roger Graves
BLD-Ceiling Grid Inspection2/12/20182/13/20182/13/2018PFAIL
DetailsJim Storey
Phone #: ###-#### Inspection requested via web by Roger Graves not per plan with seicmic pods and wires
BLD-Energy code compliance1/11/20181/12/20181/12/2018PPASS
DetailsMike Jordan
Early afternoon inspection please Phone #: ###-#### Inspection requested via web by Roger Graves
BLD-Framing/Rough-in1/11/20181/12/20181/12/2018PPASS
DetailsMike Jordan
Early afternoon inspection please Phone #: ###-#### Inspection requested via web by Roger Graves. All framing issues have been resolved.
BLD-Framing/Rough-in1/9/20181/10/20181/10/2018APART
DetailsMike Jordan
Late am inspection please Phone #: ###-#### Inspection requested via web by Roger Graves. Add additional steel stud under joist for full bearing. 5/8 through bolts on side entry need to penetrate through osb, and stud back and connected with 1/4 inch washers and nut. ok to insulate. Also inspected in progress work on heavy timber connections on ground.
CHANGE STATUS TO (ISS)  1/9/2018 DONE
Plan Mod
(F) Reprint permit  1/9/2018 DONE
OVERRIDE  1/5/2018  
Plan assigned to (JG)11/1/201711/1/20171/5/2018 PASS
DetailsJavier Guzman
1st rev comp, Plan Mod Maverik #565 ePlan
Routing Off Site - STRUCTURAL12/27/2017 1/5/2018 PASS
DetailsJavier Guzman
Signed off in ePlan by Stapley Engineering Jan Welch
Permit Ready to Issue  1/5/2018 DONE
PLAN MOD DO NOT REISSUE - all met, fees due (PRK fees due also)
Routing - PLAN CHECK12/27/2017 1/3/2018 PASS
DetailsJavier Guzman
Routing Off Site - STRUCTURAL12/5/2017 12/19/2017 FAIL
DetailsJavier Guzman
Failed in ePlan by Stapley Engineering Jan Welch
Routing Off Site - C.D.H12/9/2017 12/15/2017 PASS
DetailsJavier Guzman
signed off in ePlan by Central District Health Department Natasha Ferney
BLD-Framing/Rough-in12/12/201712/13/201712/13/2017ACANC
DetailsMike Jordan
Roger Phone #: ###-####
BLD-Framing/Rough-in12/13/201712/13/201712/13/2017PPART
DetailsMike Jordan
Interior walls only. No cover on exterior or storefront. Waiting for structural reveiw.
BLD-Framing/Rough-in12/12/201712/12/201712/12/2017PFAIL
DetailsMike Jordan
Needs to pull electrical permit from boise city. Also noted sheet rock installed and coolers, no cover or energy code inspctions have been done at this time.
BLD-Framing/Rough-in12/8/201712/11/201712/11/2017PDEFR
DetailsJim Storey
Roger Phone #: ###-#### out of time rolled to mike am
Routing PW Environmental12/6/2017 12/11/2017 PASS
DetailsTerry Alber
1500-gallon GI approved. Sample manhole optional.
Routing - PLAN CHECK12/5/2017 12/11/2017 FAIL
DetailsJavier Guzman
Routing PW Drainage12/11/2017 12/11/2017 PASS
DetailsBrian Murphy
Routing - MECHANICAL12/5/2017 12/9/2017 PASS
DetailsJavier Guzman
signed off in ePlan by Troy James
Routing - PLUMBING12/5/2017 12/8/2017 PASS
DetailsBill VanDegrift
added a toilet a urinal and removed two sinks
per plans and ISPC
Routing PW Sewer Design12/8/2017 12/8/2017 PASS
DetailsMike Sheppard
BLD-Framing/Rough-in12/5/201712/6/201712/6/2017PCANC
DetailsMike Jordan
Roger Phone #: ###-####
BLD-Wall Bracing12/6/201712/6/201712/6/2017PPASS
DetailsMike Jordan
Roger Phone #: ###-####. The south exteror wall below the low roof has been corrected.
Routing - PUBLIC WORKS12/5/2017 12/6/2017 PASS
DetailsMorgan Webb
BLD-Framing/Rough-in12/1/201712/5/201712/5/2017ACANC
DetailsMike Jordan
Roger Phone #: ###-####
BLD-Wall Bracing12/5/201712/5/201712/5/2017APART
DetailsMike Jordan
Roger Phone #: ###-####. Exterior walls. South exterior wall below low roof not completed.
Routing - PLAN CHECK11/4/2017 11/9/2017 FAIL
DetailsJavier Guzman
Route to Impact Fee Review11/1/201711/4/201711/3/2017 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
Plan Modification Accepted  11/1/2017 DONE
DetailsChristina Prado
ASI 1 covers:
Coordination of civil site lighting with electrical
Coordination of the plumbing drainage of the back sloped roof.
An alternate for 2 PSI Gas, HW Recirculation and pex piping

ASI 2 covers:
The faux timber system changed to a glulam timber system at the front and side canopies.
Revising the restrooms to accommodate an additional stall.
Revising the restroom sinks to be an undermount variety and providing Dyson airblade db for hand drying and Ecolab Classic touch-less as the soap dispenser.
Offering the zip 7/16” sheathing system as an alternate to the sheathing/air barrier.
Providing a sealed concrete finish instead of tile in the electrical room 103, 35 beverage cooler 115, vendor receiving 107 and the storage room 110 and providing Schluter-Reno-Ramp as the transition.
Changing the CT-2 tile from “Muddy Waters” to Metropolitan Ceramics, Quarrybasics Clear Tones – Chestnut Brown 108.
Providing the rough in for a potential future dishwasher including electrical, plumbing and an exhaust fan.
Clarifying the freezer slab on grade as 99’-7 ½” instead of 99’-7 7/8”.
Removing the goose neck lights from the front of the building.
Stopping the central canopy and side canopy roofs flush with the edge of the truss below.
Changing the fresh foods case to Hillphoenix CF-4SC 60.
Removing the glass door merchandizer is being omitted from the cashwrap.
Providing a data oulet and isolated ground duplex receptacle for the cashwrap.
Replacing the GFI receptacles for the outdoor ice bin with standard receptacles.

ASI 3 covers:
Providing a framed podium for the timber pilasters at the side entrance.
Piping the irrigation in the swale on the east side of the site.
BLD-Footing10/30/201710/31/201710/31/2017APASS
DetailsMike Jordan
Requesting canopy footing inspection. Concrete is scheduled to pour at 2 PM Phone #: ###-#### Inspection requested via web by Roger Graves. Canopy footings for North canopy ok.
BLD-Footing10/24/201710/25/201710/25/2017APART
DetailsBrandon Shaw
Diesel fuel canopy
BLD-Foundation10/18/201710/19/201710/19/2017PPASS
DetailsMike Jordan
Requesting an afternoon inspection. Concrete pour is set up for Friday morning Phone #: ###-#### Inspection requested via web by Roger Graves. Perimeter stemwalls. Will have special ionspection.
BLD-Footing10/13/201710/16/201710/16/2017APASS
DetailsMike Jordan
Requesting 9:00am inspection. Have mud scheduled for 10 am. Will have city stamped approved plans on site. Phone #: ###-#### Inspection requested via web by Roger Graves. Perimeter footings ok.
BLD-Footing10/12/201710/13/201710/13/2017PNR
DetailsMike Jordan
Building footings. QAA set for 12:00. Mud set for delivery at 2:00 PM. Please try to accommodate a noon inspection. Phone #: ###-#### x801 Inspection requested via web by Roger Graves. No city approved plans on site. Will reschedule.
Issue PAID IN FULL permit  9/29/2017 DONE
Print Occupancy Form  9/29/2017 DONE
OVERRIDE  8/7/2017  
Plan assigned to (JG)3/1/20173/1/20178/7/2017 PASS
DetailsJavier Guzman
1st rev comp, 3/21 L3 Maverick #565 ePlan, Pend 180 day acceptance (expired 7/16 180 day letter sent)
PLANS/APPL TAKEN TO FRONT DESK  8/7/2017 DONE
Permit Ready to Issue  8/7/2017 DONE
DetailsChristina Prado
Need
ACHD,

Met
RP, GC & Revised Certificate of Value for issuance
Extend Review Timeline  8/4/2017 DONE
180 day extension approved by Adele. See documents
Routing - PLAN CHECK7/26/2017 7/29/2017 PASS
DetailsJavier Guzman
Routing PW Street Lights7/26/2017 7/27/2017 PASS
DetailsTom Marshall
Plan Reviewer's activity  7/26/2017 DONE
DetailsJavier Guzman
180 day notice sent
Routing PW Street Lights7/19/2017 7/20/2017 FAIL
DetailsTom Marshall
Routing - PLAN CHECK7/19/2017 7/19/2017 PASS
DetailsJavier Guzman
Routing - PLAN CHECK6/7/2017 6/12/2017 FAIL
DetailsJavier Guzman
Routing PW Street Lights6/7/2017 6/7/2017 FAIL
DetailsTom Marshall
Routing PW Drainage6/7/2017 6/7/2017 PASS
DetailsBrian Murphy
Plan resubmittals received  5/24/2017 DONE
resubmittal recieved 1 appendix J and took to Brian Murphy
Routing PW Drainage5/9/2017 5/12/2017 FAIL
need hydrocarbon filter apdx j
Routing Off Site - STRUCTURAL4/19/2017 5/4/2017 PASS
DetailsJavier Guzman
Signed off in ePlan by Stapley Engineering Jan Welch
Routing - PLAN CHECK4/19/2017 4/30/2017 FAIL
DetailsJavier Guzman
Routing - PLUMBING4/22/2017 4/24/2017 PASS
DetailsBill VanDegrift
1) additional cross connection may be required
2) floor sinks must be half exposed at cabinet toe kick.


Routing PW Sewer Design4/19/2017 4/19/2017 PASS
DetailsKyle S. Rosenmeyer
Routing PW Solid Waste4/19/2017 4/19/2017 PASS
DetailsEvan Carpenter
Solid waste enclosure is OK as planned.
Routing PW Street Lights4/19/2017 4/19/2017 FAIL
DetailsTom Marshall
Routing - PLAN CHECK3/1/2017 3/20/2017 FAIL
DetailsJavier Guzman
1st review completed  3/20/2017 FAIL
DetailsAdele J Schaffeld-Griffin
Routing Off Site - STRUCTURAL3/1/2017 3/16/2017 FAIL
DetailsJavier Guzman
failed in ePlan by Stapley Engineering Jan Welch
Routing PW Street Lights3/2/2017 3/16/2017 FAIL
DetailsTom Marshall
failed in ePlan by PW Street Lights Tom Marshall
Routing PW Drainage3/2/2017 3/16/2017 FAIL
DetailsBrian Murphy
failed in ePlan by PW Drainage Brian Murphy
Routing - Erosion and Sediment3/1/2017 3/7/2017 PASS
DetailsMelissa Jannusch
No earth disturbing activity will occur. All interior Tis.
Site preparation inspection required before construction begins Call ###-####. Plans looks ok. BMPs: 25’x20’ construction entrance on Cole rd, and Victory, Perimeter silt fence on all sides but Sorensen dr, inlet protection, concrete washout. RP needs to be specified. The plan designer is out of state and not a valid City of Boise PD. Okay, but PD should get certification if continuing to design ESC plans in Boise.
Routing - Design Review3/1/2017 3/7/2017 PASS
DetailsSarah Schafer
Approved per the conditions in DRH16-00288.
Routing - FIRE3/1/20173/1/20173/6/2017 PASS
DetailsKatie Marron
Comments attached to case.
Routing PW Sewer Design3/2/2017 3/6/2017 FAIL
DetailsKyle S. Rosenmeyer
Utilize existing 6" sewer service to the property, approximtley 53 feet from existing manhole SW19114.

Label existing manhole SW19101. Label second manhole approximtaley 195 feet to the east of this manhole, SW 19114. Existing sewer line shown on drawing may not be accurate, contact Kyle at krosenmeyer@cityofboise.org to request GIS sewer map.
Routing - MECHANICAL3/1/2017 3/6/2017 PASS
DetailsChad Schwendiman
Routing - PLUMBING3/1/2017 3/6/2017 PASS
DetailsBill VanDegrift
1) additional cross connection may be required
2)
provide drainage for 2 1/2" R.P. or install DCVA
3) asse 1070 mixing valve required at the public lavs
4) floor sinks must be half exposed at cabinet toe kick.
Routing PW Solid Waste3/2/2017 3/3/2017 FAIL
DetailsEvan Carpenter
Enclosure must have at least 18 ft of unobstructed clearance between outer gate posts; suggest removal of center partition.
Routing PW Environmental3/2/2017 3/2/2017 PASS
DetailsRick Christenson
Routing - PLANNING Land Div3/1/2017 3/2/2017 PASS
DetailsTodd Tucker
Routing - PUBLIC WORKS3/1/2017 3/2/2017 PASS
DetailsMorgan Webb
Routing - Addressing3/1/2017 3/1/2017 PASS
DetailsLaura Hunter
Changed address to 7353 W Victory Rd
Intake Approval  3/1/2017 PASS
DetailsJavier Guzman
Intake Approval  1/19/2017 FAIL
DetailsJavier Guzman
Incomplete prescreen submittal, Applicants with incomplete submittals must upload additional documents or upload revised documents (new revised uploaded files shall have the same file naming convection so that the new revised sheet/document will version) below is what is required:
•The uploaded structural calculations are required to be stamped/signed/dated by an Idaho licensed engineer
•Provide a completed Food Establishment License application form (you had only uploaded the Food Establishment Plan Review and Approval form) Food Establishment License application Form is available at: www.cdhd.idaho.gov/EH/food/forms.htm.
•The uploaded Drainage System Operation & Maintenance Plan is required to be stamped/signed/dated by an Idaho licensed design professional including descriptive narrative and calculations
•Exterior Lighting compliance for the site, building, canopy, trellis lighting (COMcheck signed & uploaded)
•In a quick review of the submitted documents I did not notice engineering calculation for the canopy, I also did not notice any engineering calculations for the trellis’s, please upload the required engineering calculations
Application received  1/17/2017 DONE
Application submitted via PDS Online on Jan 17 2017 9:13AM
Routing - Design Review12/5/2017 12/13/2013 PASS
DetailsSarah Schafer