BLD-Aging Inspection | 12/14/2017 | 12/14/2017 | 12/19/2017 | | PEND |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 12/13/2017 | 12/13/2017 | 12/19/2017 | | PEND |
Dave Hannah
|
|
|
|
BLD-Concrete | 9/14/2017 | 9/15/2017 | 9/15/2017 | P | PEND |
Dave Hannah
|
|
|
Rebar inspection request for the suspended slab on deck. Placement is from grid 7.5 to 11 and from grid A to E. Please call Dan with any issues. Phone #: ###-#### Inspection requested via web by Dan Koski ok after spec inspection sign off
|
BLD-Foundation | 8/15/2017 | 8/15/2017 | 8/18/2017 | P | PEND |
Dave Hannah
|
|
|
Final reinforcement sign off for the perimeter walls at LL3. These are along grids 1-11 and A-E. Please call Dan with any questions. Phone #: ###-#### Inspection requested via web by Dan Koski
|
BLD-Concrete | 8/1/2017 | 8/1/2017 | 8/1/2017 | A | DONE |
Dave Hannah
|
|
|
Rebar inspection of structural mat slab. Grids 5 to 11 from A to E. Phone #: ###-#### Inspection requested via web by Dan Koski
|
BLD-Foundation | 7/28/2017 | 7/28/2017 | 8/1/2017 | P | PASS |
Dave Hannah
|
|
|
Rebar inspection of structural mat slab. Grids 5 to 11 from A to E. Phone #: ###-#### Inspection requested via web by Dan Koski
|
BLD-Foundation | 7/18/2017 | 7/18/2017 | 7/18/2017 | A | PART |
Brandon Shaw
|
|
|
5.5 to 11, between A & E
|
BLD-Foundation | 6/26/2017 | 6/29/2017 | 7/12/2017 | A | DONE |
Dave Hannah
|
|
|
Inspection of LL3 foundation reinforcement complete - 1,900cy concrete placement scheduled for 0100hr start on 7/1 Phone #: ###-#### Inspection requested via web by Jamal Nelson
|
BLD-Foundation | 7/11/2017 | 7/11/2017 | 7/12/2017 | P | PEND |
Dave Hannah
|
|
|
Rebar // Dan Phone #: ###-####
|
BLD-Foundation | 6/21/2017 | 6/22/2017 | 6/23/2017 | P | PEND |
Dave Hannah
|
|
|
Bottom mat reinforcement - mat slab @ level LL3 Phone #: ###-#### Inspection requested via web by Jamal Nelson
|
BLD-Foundation | 6/14/2017 | 6/15/2017 | 6/16/2017 | P | PASS |
Dave Hannah
|
|
|
Elevator pit reinforcement Phone #: ###-#### Inspection requested via web by Jamal Nelson
|
BLD-Footing | 6/1/2017 | 6/2/2017 | 6/5/2017 | P | PASS |
Dave Hannah
|
|
|
Concrete reinforcement at tower crane foundation Phone #: ###-#### Inspection requested via web by Jamal Nelson
|
BLD-Conference | 5/23/2017 | 5/30/2017 | 5/30/2017 | A | PASS |
Dave Hannah
|
|
|
Meeting requested with Dave Hannah to discuss start of construction activities specific to this permit. Phone #: ###-#### Inspection requested via web by Jamal Nelson
|
Issue PAID IN FULL permit | | | 5/5/2017 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Bld | | | 5/5/2017 | | DONE |
Christina Prado
|
|
|
|
OVERRIDE | | | 3/30/2017 | | |
|
|
|
|
Permit Ready to Issue | | | 3/30/2017 | | DONE |
Christina Prado
|
|
|
***we still need everything listed but i put the fee amounts in because St Lukes needed to get a check cut-i emailed the fees due sheet for them***Need - ACHD (are they paying here, or ACHD? Fee calcualtion in docs) , GC Form & Revised Certificate of Value for issuance
|
Plan assigned to (AJS) | 2/9/2017 | 2/9/2017 | 3/29/2017 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
Childrens Pavilion
|
Routing - PLAN CHECK | 3/22/2017 | | 3/29/2017 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
Routing - PLANNING Land Div | 3/22/2017 | | 3/29/2017 | | PASS |
Todd Tucker
|
|
|
|
Routing Off Site - STRUCTURAL | 3/22/2017 | | 3/29/2017 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/29/2017 | | DONE |
|
|
|
|
Routing Off Site - STRUCTURAL | 3/10/2017 | | 3/22/2017 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
|
Routing - PLAN CHECK | 3/10/2017 | | 3/22/2017 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
|
Routing - PLANNING Land Div | 3/10/2017 | | 3/20/2017 | | FAIL |
Todd Tucker
|
|
|
Cannot issue building permit until ROS17-00017 is finaled.
|
Routing - Design Review | 3/10/2017 | | 3/16/2017 | | PASS |
Sarah Schafer
|
|
|
Approved per DRH.
|
Routing PW Sewer Design | 3/10/2017 | | 3/15/2017 | | PASS |
Kyle S. Rosenmeyer
|
|
|
|
Routing - FIRE | 3/10/2017 | 3/10/2017 | 3/10/2017 | | PASS |
Katie Marron
|
|
|
Revised report attached to case.
|
Route to Impact Fee Review | 3/3/2017 | 3/6/2017 | 3/6/2017 | | PASS |
Tonya Wallace
|
|
|
Review requested for Commercial Permit
|
1st review completed | | | 3/3/2017 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
|
Routing Off Site - STRUCTURAL | 2/9/2017 | | 3/3/2017 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
|
Routing - PLAN CHECK | 2/9/2017 | | 3/3/2017 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
|
Routing - PLANNING | 2/9/2017 | | 3/2/2017 | | PASS |
David Moser
|
|
|
David Moser
|
Routing PW Sewer Rating | 2/9/2017 | | 3/2/2017 | | PASS |
Morgan Webb
|
|
|
|
Routing PW Drainage | 2/9/2017 | | 2/27/2017 | | PASS |
Brian Murphy
|
|
|
|
Routing PW Environmental | 2/9/2017 | | 2/21/2017 | | PASS |
Rick Christenson
|
|
|
|
Routing - FIRE | 2/9/2017 | 2/9/2017 | 2/14/2017 | | FAIL |
Katie Marron
|
|
|
Report attached to case and emailed to architect.
|
Routing - Erosion and Sediment | 2/9/2017 | | 2/13/2017 | | PASS |
Melissa Jannusch
|
|
|
ESC narrative is located under GRD16-00079. RP TBD. De-watering will occur. BMPs include. Stabilized construction entrance, waste management, concrete washout, street sweeping as needed, fiber rolls at bottom of perimeter fence, staging area, inlet protection.
|
Routing - PLUMBING | 2/9/2017 | | 2/13/2017 | | PASS |
Daryl Spivey
|
|
|
Per plan and ISPC.
|
Routing - PLANNING Land Div | 2/9/2017 | | 2/10/2017 | | FAIL |
Todd Tucker
|
|
|
The proposed building crosses over an existing property line. Prior to issuance of the building permit, the parcels must be combined into one parcel through the Record of Survey Parcel Consolidation process.
|
Routing PW Solid Waste | 2/9/2017 | | 2/10/2017 | | PASS |
Evan Carpenter
|
|
|
Solid waste is OK as planned.
|
Routing PW Sewer Design | 2/9/2017 | | 2/10/2017 | | FAIL |
Kyle S. Rosenmeyer
|
|
|
New sewer services required to be "Type D" connections. Contant Boise Public Works 48 Hours prior to sewer work in Public R/W to obtain tap permits and schedule inspection. Excavate and abandon/cap 6 sewer services in the alley that previously served the Children's Pavilion property.
|
Routing PW Street Lights | 2/9/2017 | | 2/9/2017 | | PASS |
Tom Marshall
|
|
|
|
Routing - Addressing | 2/9/2017 | | 2/9/2017 | | PASS |
Laura Hunter
|
|
|
|
Routing - PUBLIC WORKS | 2/9/2017 | | 2/9/2017 | | PASS |
Rachael Beierle
|
|
|
will review rating by m_b
|
Intake Approval | | | 2/9/2017 | | PASS |
David Ferguson
|
|
|
plan review fees paid 2/9/2017
|
Intake Approval | | | 1/24/2017 | | FAIL |
David Ferguson
|
|
|
Please upload a completed, #310 Statement of Special Inspections form.
|
CHANGE STATUS TO (REV) | | | 1/24/2017 | | DONE |
|
|
|
changed status to REV-plan review has not been done yet-
|
Intake Approval | | | 1/23/2017 | | FAIL |
David Ferguson
|
|
|
Please upload a completed, with stamp and signature, #310 Statement of Special Inspections form. Also, a Zoning Certificate from our Planning Department.
|
Permit Ready to Issue | | | 1/20/2017 | | DONE |
|
|
|
|
Application received | | | 1/19/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Jan 19 2017 4:19PM
|
Routing - Design Review | 2/9/2017 | | 2/14/2016 | | FAIL |
Sarah Schafer
|
|
|
See David Mosers comments.
|