Permit Information
Permit NumberBLD17-00282
StatusFinaled
Name RM MECHANICAL
Site Address 3201 W AIRPORT WAY
Project NameBOI - Air Terminal - Solar Sys
Customer Number 
ePlanReviewYes
Description
(BOI – BOISE CITY AIR TERMINAL – SOLAR HOT WATER SYSTEM) The building fire sprinkler system is used for fire area. To install solar racks on the roof of the Boise City Air Terminal Building to support glazed, flat plat solar thermal collector panels tilted at a 35 degree angle for a pressurized, closed-loop, solar water heating system with glycol freeze protection. The solar water heating system will serve the building’s domestic hot water system. Solar thermal collector panels will be installed in 3 sets of 4 panels each. Each panel is 9.75 feet by 4 feet and weighs about 140 pounds. Work is to include installing vertical support columns and panel support rails. Work within Mechanical Room #326 on the 3rd story includes a concrete housekeeping pad for new equipment, two new 100 gallon high efficiency gas water heaters (about 835 pounds water weight each), two 320 gallon solar storage tanks (about 2,671 pounds water weight each), heat exchangers, circulator pumps, control valves, pipes, etc. Special Inspection is required for welding and to verify the screw installation into the metal roof deck. The roof covering is required to be adequately patched in accordance with the manufacturer’s instructions to adequately protect the building and to restore the function of the roof covering. The work is required to comply with the approved drawings, with the structural calculations, with the plan review report, and with all applicable codes and ordinances. This is a scope of work permit only and does not establish a Certificate of Occupancy for any portion of this building. This building already has a Certificate of Occupancy. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice 10/17/201711/14/2017 DONE
Mailed 11-15-17
Second Notice 10/5/201710/12/2017 DONE
Mailed 10-13-17
First Notice8/24/20178/24/20179/25/2017 DONE
DetailsJim Storey
BLD-Final8/21/20178/22/20178/24/2017PPASS
DetailsJim Storey
Josh Phone #: ###-#### si report ok
DOC - Permit Finaled8/24/20178/24/20178/24/2017PPASS
DetailsJim Storey
FIRE-Final Inspection8/23/20178/24/20178/24/2017PPASS
DetailsTroy Cobbley
Life safety passed. These are hot water panels not solar/electric panels. I noted no electrical except for a temperature sensor.

Josh Phone #: ###-####
Issue PAID IN FULL permit  7/17/2017 DONE
Plan assigned to (CJW)4/28/20174/28/20177/13/2017 PASS
DetailsCarl Westfall
(1st done) (May 18 - 15 days) (11 sheets) BOI - Boise City Air Terminal - Solar Hot Water
Routing Off Site - STRUCTURAL7/11/2017 7/13/2017 PASS
DetailsCarl Westfall
Dave Haugland (AHJ)
PLANS/APPL TAKEN TO FRONT DESK  7/13/2017 DONE
Permit Ready to Issue  7/13/2017 DONE
Need GC Form and Revised Cert of Value
Routing - PLAN CHECK7/7/2017 7/11/2017 PASS
DetailsCarl Westfall
Plan resubmittals received  7/7/2017 DONE
Routing - PLAN CHECK6/19/2017 6/20/2017 FAIL
DetailsCarl Westfall
Neither of the Consultant Structural Engineers concerns were addressed. The workflow was sent back to the applicant so that documents resolving those concerns could be uploaded.
Plan resubmittals requested  6/20/2017 DONE
Plan resubmittals received  6/19/2017 DONE
Route to Impact Fee Review6/9/20176/12/20176/9/2017 PASS
DetailsMarissa Taylor
Review requested for Commercial Permit
Routing - PLAN CHECK4/28/2017 6/9/2017 FAIL
DetailsCarl Westfall
Additional information required
1st review completed  6/9/2017 DONE
Plan resubmittals requested  6/9/2017 DONE
Routing Off Site - STRUCTURAL4/28/2017 5/11/2017 FAIL
DetailsCarl Westfall
Dave Haugland (AHJ)
Routing - Design Review4/28/2017 5/9/2017 PASS
DetailsSusan Riggs
Routing - ELECTRICAL4/28/2017 5/4/2017 CANC
DetailsJavier Guzman
No review required
Routing - FIRE4/28/20174/28/20175/1/2017 PASS
DetailsKatie Marron
Comments attached to case.
Routing - MECHANICAL4/28/2017 5/1/2017 PASS
DetailsTroy James
Intake Approval  4/28/2017 PASS
DetailsJavier Guzman
Routing - PLUMBING4/28/2017 4/28/2017 PASS
DetailsDaryl Spivey
Per plan and ISPC.
Routing - Addressing4/28/2017 4/28/2017 PASS
DetailsLaura Hunter
Routing - PUBLIC WORKS4/28/2017 4/28/2017 PASS
DetailsMorgan Webb
Routing - Erosion and Sediment4/28/2017 4/28/2017 PASS
DetailsAndy J. Long
No ESC permit required. No earth disturbance or excavation required for project.
Intake Approval  4/11/2017 FAIL
DetailsJavier Guzman
Incomplete prescreen submittals, please upload the required remaining requested additional documents below:
• The uploaded engineering is stamped and signed by a California engineer and not accepted in the state of Idaho, please provide Structural calculations and details stamped and signed by an Idaho licensed engineer for new the solar panels on the roof.
Intake Approval  4/5/2017 FAIL
DetailsJavier Guzman
Incomplete prescreen submittals, please upload the required remaining requested additional documents below:
• Please provide a Site specific fire flow at hydrants letter from Suez Water or other public water provider. Include static pressure if sprinklers are to be installed
• Please provide a cover sheet with the building Code Analysis/Building Data on front sheet of plans which includes: code year, occupancy group, construction type, fire suppression system.
-2012 International Building Code
-Idaho State Plumbing Code (Including Chapter 13 – Medical Gas); based on the 2009 Uniform Plumbing Code
-2012 International Mechanical Code and Appendix A
-2012 International Fuel Gas Code and Appendices A, B, C, and D
-2012 International Fire Code
-Occupancies include A-2, A-3, B, M, and S-1.
-Construction type IA
-Fully fire sprinklered
• Please provide Structural calculations and details stamped and signed by an Idaho licensed engineer for new the solar panels on the roof.
• Please provide solar panel manufacturer specifications. Specifications need to show panels and modules as listed and labeled.
• Please provide ICC-ES Evaluation Services Report for all solar mounting brackets used to attach the solar panels to the roof structure.
• Please provide Fire resistive assembly penetrations details for any new or existing rated conditions and proposed changes to rated wall(s) & ceiling(s)
Intake Approval  2/16/2017 FAIL
DetailsJavier Guzman
Incomplete prescreen submittals, please upload or revise the requested additional documents below:
• Form #304 – Registered Design Professional form
• Site specific fire flow at hydrants letter from Suez Water or other public water provider. Include static pressure if sprinklers are to be installed
• Plan sheets shall be uploaded individually and in the landscape position per ePlan submittal standards found at http://pds.cityofboise.org/media/105041/electronicstandards.pdf
• Individual plan sheet drawing file names must include the first characters of the discipline name, followed by the sheet number and name per ePlan submittal standards found at http://pds.cityofboise.org/media/105041/electronicstandards.pdf
• All plan sheets must reserve a space on the bottom right corner for City approval stamps per ePlan submittal standards found at http://pds.cityofboise.org/media/105041/electronicstandards.pdf
• Code Analysis/Building Data on front sheet of plans which includes: code year, occupancy group, construction type, fire suppression system.
-2012 International Building Code
-Idaho State Plumbing Code (Including Chapter 13 – Medical Gas); based on the 2009 Uniform Plumbing Code
-2012 International Mechanical Code and Appendix A
-2012 International Fuel Gas Code and Appendices A, B, C, and D
-2012 International Fire Code
-Occupancies include A-2, A-3, B, M, and S-1.
-Construction type IA
-Fully fire sprinklered
• Structural calculations and details stamped and signed by an Idaho licensed engineer.
• Provide solar panel manufacturer specifications. Specifications need to show panels and modules as listed and labeled.
• ICC-ES Evaluation Services Report for all mounting brackets used to attach the panels to the roof structure.
• Fire resistive assembly penetrations details for any new or existing rated conditions and proposed changes to rated wall(s) & ceiling(s)
Application received  2/15/2017 DONE
Application submitted via PDS Online on Feb 15 2017 3:03PM