BLD-Final | 6/22/2018 | 6/25/2018 | 6/25/2018 | A | PASS |
Mike Jordan
|
|
|
Cecil Phone #: ###-####. OK for perm oc.
|
DOC - Permit Finaled | | | 6/25/2018 | | DONE |
|
|
|
final done on 6/25/18
|
Letter of compliance/Occupancy | | | 6/25/2018 | | DONE |
|
|
|
|
FIRE-Final Inspection | 6/21/2018 | 6/22/2018 | 6/22/2018 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
Cecil Phone #: ###-####
|
BLD-Final | 5/17/2018 | 5/17/2018 | 5/17/2018 | P | PART |
Mike Jordan
|
|
|
Cecil-wants a partial-sleep room and lactation Phone #: ###-####. ok for temp occ, these two rooms only.
|
FIRE-Final Inspection | 5/17/2018 | 5/17/2018 | 5/17/2018 | P | PART |
Troy Cobbley
|
|
|
Sleep room and lactation room life safety passed
|
CHANGE STATUS TO (ISS) | | | 3/21/2018 | | DONE |
|
|
|
|
(F) Reprint permit | | | 3/21/2018 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 3/21/2018 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 3/12/2018 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/12/2018 | | DONE |
|
|
|
DO NOT REISSUE -plan mod, fees due
|
Plan assigned to (JAR) | 12/22/2017 | 12/22/2017 | 3/11/2018 | | DONE |
Julie Romig
|
|
|
**1st Rev Comp - 2nd Rec'd 02/28 - Plan Mod - SARMC NICU
|
Routing - PLAN CHECK | 2/28/2018 | | 3/11/2018 | | PASS |
Julie Romig
|
|
|
|
Routing - PLUMBING | 1/26/2018 | | 2/2/2018 | | PASS |
Bill VanDegrift
|
|
|
Plan Mod per plans and ISPC
|
Routing - PLAN CHECK | 1/29/2018 | | 1/29/2018 | | FAIL |
Julie Romig
|
|
|
Emailed architect corrections
|
Routing - MECHANICAL | 1/24/2018 | | 1/24/2018 | | PASS |
Troy James
|
|
|
added smoke damper to transfer grille
|
Route to Impact Fee Review | 12/22/2017 | 12/25/2017 | 12/26/2017 | | PASS |
Eric Bilimoria
|
|
|
Review requested for Commercial Permit
|
Plan Modification Accepted | | | 12/22/2017 | | DONE |
Christina Prado
|
|
|
Per attached Plan Mod application
|
FIRE-Final Inspection | 12/20/2017 | 12/20/2017 | 12/20/2017 | P | FAIL |
Troy Cobbley
|
|
|
Inspection turned into a conference. I noted that in the new Sleeping Room and Lactation Room the fire alarm/notification needs to be modified for the new use. The city approved plans also showed an existing wall mount horn/strobe to be relocated in another remodeled area.
Cecil Phone #: ###-####
|
Issue PAID IN FULL permit | | | 6/19/2017 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 6/19/2017 | | DONE |
|
|
|
|
Plan assigned to (JAR) | 4/14/2017 | 4/14/2017 | 5/22/2017 | | DONE |
Julie Romig
|
|
|
05/11 - L2 SARMC NICU T.I. ePlan
|
Routing - PLAN CHECK | 4/14/2017 | | 5/22/2017 | | PASS |
Julie Romig
|
|
|
|
1st review completed | | | 5/22/2017 | | DONE |
Julie Romig
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/22/2017 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/22/2017 | | DONE |
|
|
|
**MET** Need GC Form and Revised Cert of Value
|
Plan Reviewer's activity | | | 4/21/2017 | | |
Julie Romig
|
|
|
Due to I occupancy, project will be reviewed as a 520 Level 3 TI. Spoke with Mark Hirschi and let him know that it would be the Level 3 timeline instead of Level 2.
|
Routing - PLUMBING | 4/14/2017 | | 4/18/2017 | | PASS |
Bill VanDegrift
|
|
|
per plans and ISPC
|
Routing - Addressing | 4/14/2017 | | 4/17/2017 | | PASS |
Laura Hunter
|
|
|
|
Routing - MECHANICAL | 4/14/2017 | | 4/17/2017 | | PASS |
Troy James
|
|
|
|
Intake Approval | | | 4/14/2017 | | PASS |
Javier Guzman
|
|
|
|
Routing - PUBLIC WORKS | 4/14/2017 | | 4/14/2017 | | PASS |
Rachael Beierle
|
|
|
|
Application received | | | 4/7/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 7 2017 3:06PM
|