BLD-Aging Inspection | 12/13/2018 | 12/13/2018 | 12/21/2018 | | CANC |
Jim Storey
|
|
|
|
BLD-Final | 7/26/2018 | 7/31/2018 | 7/31/2018 | P | PASS |
Jim Storey
|
|
|
Kevin Phone #: ###-#### final ok oupon all others that did not sign oc card.
|
FIRE-Final Inspection | 7/26/2018 | 7/30/2018 | 7/30/2018 | A | PART |
Jim Page
|
|
|
Partial life fire safety inspection complete, fire sprinkler inspection complete, fire alarm inspection for addition is complete (fire alarm permit is for a complete fire alarm upgrade for the whole school, fire alarms are active through school and new addition, TCO is authorized for 60 days per conversation with Ron Johnson, when FIR permit for fire alarms is finaled then life fire safety for this permit can be finaled), fire exitnguishers are in place with current inspection tags. TCO authorized for 60 days contingent on the fire alarm panel upgrade being completed.
Kevin Phone #: ###-####
|
BLD-Other | 7/24/2018 | 7/25/2018 | 7/25/2018 | P | PASS |
Jim Storey
|
|
|
Kevin-Ceiling cover Phone #: ###-####
|
BLD-Framing/Rough-in | 7/2/2018 | 7/3/2018 | 7/3/2018 | A | PART |
Dave Hannah
|
|
|
Daniel Phone #: ###-#### ok to cover specal ed area
|
BLD-Framing/Rough-in | 6/18/2018 | 6/19/2018 | 6/19/2018 | A | PASS |
Jim Storey
|
|
|
Ken Phone #: ###-#### 2nd floor link.
|
BLD-Aging Inspection | 6/12/2018 | 6/12/2018 | 6/12/2018 | | PASS |
Jim Storey
|
|
|
|
BLD-Ceiling Grid Inspection | 3/29/2018 | 3/30/2018 | 3/30/2018 | A | PASS |
Jim Storey
|
|
|
Kent Phone #: ###-####-first floor ceilling ok
|
BLD-Ceiling Grid Inspection | 3/28/2018 | 3/29/2018 | 3/29/2018 | P | CANC |
Jim Storey
|
|
|
Kent-first floor Phone #: ###-####
|
BLD-Ceiling Grid Inspection | 3/14/2018 | 3/15/2018 | 3/15/2018 | A | PASS |
Jim Storey
|
|
|
Phone #: 2089723063 >> Inspection requested via mobile web by Kevin Antonucci
|
BLD-Conference | 2/22/2018 | 2/23/2018 | 2/23/2018 | P | PASS |
Jim Storey
|
|
|
Phone #: 2089723063 >> Inspection requested via mobile web by Kevin Antonucci hard lids ok to cover.
|
BLD-Energy code compliance | 1/26/2018 | 1/29/2018 | 1/29/2018 | P | PASS |
Jim Storey
|
|
|
Kevin Phone #: ###-####1st and 2nd
|
BLD-Framing/Rough-in | 1/17/2018 | 1/18/2018 | 1/18/2018 | A | CANC |
Mike Jordan
|
|
|
Second level - Andrew Phone #: ###-####
|
BLD-Energy code compliance | 1/18/2018 | 1/18/2018 | 1/18/2018 | A | PASS |
Mike Jordan
|
|
|
Second level - Andrew Phone #: ###-####. 2nd. floor exterior walls only. No stairwells at this time.
|
BLD-Framing/Rough-in | 1/12/2018 | 1/16/2018 | 1/16/2018 | A | CANC |
Jim Storey
|
|
|
Second floor // Kevin Phone #: ###-#### PER ANDREW VIA EMAIL (BLH)
|
Inspection Record Card- Bld | | | 1/12/2018 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 12/13/2017 | 12/13/2017 | 12/13/2017 | P | PASS |
Jim Storey
|
|
|
Russell Phone #: ###-#### 2nd floor fireprooffing ok framing ok trade work in progess.
|
BLD-Framing/Rough-in | 11/14/2017 | 11/15/2017 | 11/16/2017 | P | PART |
Jim Storey
|
|
|
Russel Phone #: ###-#### exterior walls ok pending fireprooffing exterior beams ok to sheet.
|
BLD-Framing/Rough-in | 11/8/2017 | 11/13/2017 | 11/13/2017 | A | PASS |
Jim Storey
|
|
|
Kevin Phone #: ###-#### exterior wall framing in progress// ok for pannel mock up north east corner.
|
Reopen Permit (ISS) | | | 11/8/2017 | | DONE |
|
|
|
|
OVERRIDE | | | 11/6/2017 | | |
|
|
|
|
Permit Ready to Issue | | | 11/6/2017 | | DONE |
|
|
|
PLEASE DO NOT RE ISSUE-as per CDM no fees due for plan mod
|
Plan assigned to (CDM) | 11/1/2017 | 11/1/2017 | 11/5/2017 | | PASS |
Carl D Madsen
|
|
|
|
Routing - PLAN CHECK | 11/5/2017 | | 11/5/2017 | | PASS |
Carl D Madsen
|
|
|
|
Plan Modification Accepted | | | 11/1/2017 | | DONE |
Christina Prado
|
|
|
Plan mod requested to change the second floor roof/ceiling assembly to spray on fireproofing
|
BLD-Framing/Rough-in | 10/27/2017 | 10/30/2017 | 10/30/2017 | A | PASS |
Jim Storey
|
|
|
Kevin Phone #: ###-#### roof paripet framing ok/ need r 28 for roof deck insulation.
|
CHANGE STATUS TO (ISS) | | | 10/18/2017 | | DONE |
|
|
|
plan mod fees paid
|
OVERRIDE | | | 10/17/2017 | | |
|
|
|
|
Plan assigned to (CDM) | 10/13/2017 | 10/13/2017 | 10/17/2017 | | PASS |
Carl D Madsen
|
|
|
|
Routing - PLAN CHECK | 10/16/2017 | | 10/17/2017 | | PASS |
Carl D Madsen
|
|
|
|
Permit Ready to Issue | | | 10/17/2017 | | DONE |
|
|
|
All Met for Plan Mod
DO NOT REISSUE
|
Routing - PLUMBING | 10/16/2017 | | 10/16/2017 | | PASS |
Bill VanDegrift
|
|
|
Per plan and ISPC.
|
Issue PAID IN FULL permit | | | 6/20/2017 | | DONE |
|
|
|
|
Print Occupancy Form | | | 6/20/2017 | | DONE |
|
|
|
|
OVERRIDE | | | 5/9/2017 | | |
|
|
|
|
Permit Ready to Issue | | | 5/9/2017 | | DONE |
Christina Prado
|
|
|
Need GC Form & Revised Certificate of Value for issuance
*** REFER TO STATE FEE SCHEDULE WHEN CALCULATING REVISED PLAN CHECK FEES ***
|
Plan assigned to (CDM) | 4/14/2017 | 4/14/2017 | 5/8/2017 | | PASS |
Carl D Madsen
|
|
|
1st comp. Timberline High school
|
Routing Off Site - STRUCTURAL | 5/3/2017 | | 5/8/2017 | | PASS |
Carl D Madsen
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/8/2017 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 5/3/2017 | | 5/8/2017 | | PASS |
Carl D Madsen
|
|
|
|
Routing - ELECTRICAL | 5/3/2017 | | 5/5/2017 | | PASS |
Javier Guzman
|
|
|
|
Routing - MECHANICAL | 5/3/2017 | | 5/4/2017 | | PASS |
Troy James
|
|
|
|
Route to Impact Fee Review | 4/25/2017 | 4/28/2017 | 4/25/2017 | | PASS |
Tonya Wallace
|
|
|
Review requested for Commercial Permit
|
1st review completed | | | 4/25/2017 | | FAIL |
|
|
|
|
Routing Off Site - STRUCTURAL | 4/14/2017 | | 4/25/2017 | | FAIL |
Carl D Madsen
|
|
|
|
Routing - PLAN CHECK | 4/14/2017 | | 4/22/2017 | | FAIL |
Carl D Madsen
|
|
|
Plan review report attached.
|
Routing - ELECTRICAL | 4/14/2017 | | 4/22/2017 | | FAIL |
Javier Guzman
|
|
|
|
Routing - PLANNING | 4/14/2017 | | 4/21/2017 | | PASS |
Susan Riggs
|
|
|
|
Routing PW Drainage | 4/14/2017 | | 4/21/2017 | | PASS |
Brian Murphy
|
|
|
|
Routing - FIRE | 4/14/2017 | 4/14/2017 | 4/19/2017 | | PASS |
Scott Arellano
|
|
|
Attached review comment to plans.
|
Routing - Erosion and Sediment | 4/14/2017 | | 4/19/2017 | | PASS |
Andy J. Long
|
|
|
ESC plan with site map and narrative approved. Valid PD, need to designate RP at time of permit issue. Site preparation and BMP installation required prior to construction. Call ###-#### to schedule.
|
Routing - MECHANICAL | 4/14/2017 | | 4/18/2017 | | FAIL |
Troy James
|
|
|
|
Routing - PLUMBING | 4/14/2017 | | 4/17/2017 | | PASS |
Bill VanDegrift
|
|
|
per plans and ISPC
|
Routing - Addressing | 4/14/2017 | | 4/17/2017 | | PASS |
Laura Hunter
|
|
|
|
Routing PW Street Lights | 4/14/2017 | | 4/17/2017 | | PASS |
Tom Marshall
|
|
|
|
Routing PW Environmental | 4/14/2017 | | 4/14/2017 | | PASS |
Rick Christenson
|
|
|
On-site Inspection for Dark Room BMP's
|
Routing - PUBLIC WORKS | 4/14/2017 | | 4/14/2017 | | PASS |
Rachael Beierle
|
|
|
|
Intake Approval | | | 4/14/2017 | | PASS |
|
|
|
|
Routing - PLANNING Land Div | 4/14/2017 | | 4/14/2017 | | PASS |
Todd Tucker
|
|
|
|
Intake Approval | | | 4/13/2017 | | FAIL |
Julie Romig
|
|
|
Add description to file names on FP, M, and P sheets
|
Application received | | | 4/10/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 10 2017 2:49PM
|