Permit Information
Permit NumberBLD17-01058
StatusFinaled
Name SLETTEN CONSTRUCTION
Site Address 150 N 8TH ST Unit: STE 217
Project NameRamen Sho
Customer Number 
ePlanReviewYes
Description
(RAMEN SHO) **Permit is to remodel an existing 1,417 sq. ft. restaurant for new restaurant tenant (including 488 sq. ft. patio the total area is 1,905 sf). Work to include: new kitchen equipment, disconnect existing grille top and build new plastic laminate counter over grille. Maximum occupant load to be posted on sign near main exit. Work is required to comply with the approved drawings, plan review report, and with all applicable codes and ordinances. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JAR**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Telephone call  7/25/2017 DONE
called Dustin to see how he wants me to proceed with the first notice. He sent it saying that 2390.00 was the val for Buss PLM17-01638 and 3992.00 was final val for Anfinson PLM17-01653. Buss had there permit voided-said they didn't do the work after all-left message on his work phone
Second Notice 6/23/20177/12/2017 DONE
Mailed 7-13-17
First Notice 5/29/20176/13/2017 DONE
sent in mail 6-14-17
BLD-Final5/18/20175/19/20175/19/2017PPASS
DetailsDave Hannah
Dustin Phone #: ###-####
FIRE-Final Inspection5/18/20175/19/20175/19/2017APASS
DetailsJim Page
Previously noted items have been addressed, escutchions for fire sprinkler heads will be installed before final builing inspection. Final life fire safety inspection passed/complete
Permanent Occupancy  5/19/2017 DONE
DetailsChristina Prado
FIRE-Final Inspection5/10/20175/10/20175/10/2017PFAIL
DetailsJim Page
Exit sign located above south exit needs to be serviced, hood suppression system needs to be serviced/inspected and tagged before final life fire safety inspection, class K fire extinguisher needs to be inspected/serviced and a current inspection tag placed, fire extinguisher with a current inspection tag needs to be installed in seating area, existing grill tops that will be used for seating need to be disconnected from energy source (gas and or electrical power), surface mount slide bolt locks on northeast interior door needs to be removed, padlock clasp on interior office door needs to be removed, signage for exterior gate needs to be installed reading "Gate to remain unlocked while occupied" per approved drawings note, fire sprinkler head next to northwest door needs to be replaced due to excessive external loading, missing escutcheons need to be installed on fire sprinkler heads.
Print Occupancy Form  5/10/2017 DONE
Issue PAID IN FULL permit  5/10/2017 DONE
Route to Impact Fee Review5/8/20175/11/20175/9/2017 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
Plan assigned to (JAR)4/25/20174/25/20175/9/2017 DONE
DetailsJulie Romig
1st Review Complete. DUE 05/08 - L2. Ramen Sho.
Routing - PLAN CHECK5/9/2017 5/9/2017 PASS
DetailsJulie Romig
PLANS/APPL TAKEN TO FRONT DESK  5/9/2017 DONE
Permit Ready to Issue  5/9/2017 DONE
Need Revised Cert of Value
1st review completed  5/8/2017 FAIL
DetailsJulie Romig
Routing - PLAN CHECK4/25/2017 5/8/2017 FAIL
DetailsJulie Romig
Routing - FIRE4/25/20174/25/20174/28/2017 PASS
DetailsKatie Marron
Comments attached to case.
Routing PW Environmental4/25/2017 4/26/2017 PASS
DetailsRick Christenson
Routing - MECHANICAL4/25/2017 4/25/2017 PASS
DetailsTroy James
Routing - Addressing4/25/2017 4/25/2017 PASS
DetailsLaura Hunter
Ste 217
Routing - PUBLIC WORKS4/25/2017 4/25/2017 PASS
DetailsMorgan Webb
Intake Approval  4/24/2017 PASS
Missed on original routing
Intake Approval  4/17/2017 FAIL
DetailsJulie Romig
Need the following: 1. CDHD stamped approval on new plan sheet (there are multiple changes from the plans approved on 3/17/17).
2. A101 needs to be minimum 24"x18" sheet size.
3. Plans indicate attached sketches for new laminate top, but no plans included in submittal.
4. Plans indicate cutsheets for equipment, but not included in submittal.
5. Code analysis.
6. Key plan.
7. Vicinity Map.
8. Portable fire extinguisher location.
9. Location of any (E) fire rated construction (including floor/ceiling rating if applicable).
10. Location of (E) exit signs and emergency lighting.
11. Door hardware schedule for existing doors, including gate.
Application received  4/14/2017 DONE
Application submitted via PDS Online on Apr 14 2017 3:35PM