BLD-Final | 2/23/2018 | 2/26/2018 | 2/26/2018 | P | PASS |
Jim Storey
|
|
|
Jason Phone #: ###-#### ex301
|
FIRE-Final Inspection | 2/23/2018 | 2/26/2018 | 2/26/2018 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed.
Jason Phone #: ###-#### ex301
|
Permanent Occupancy | | | 2/26/2018 | | DONE |
Christina Prado
|
|
|
|
BLD-Conference | 1/23/2018 | 1/23/2018 | 1/23/2018 | P | FAIL |
Jim Storey
|
|
|
Jason Phone #: ###-#### ex 301 smoke seals remove hardware 2 locations/closer it rm adj latch. landing exterior exit/latch adj
|
FIRE-Final Inspection | 1/22/2018 | 1/23/2018 | 1/23/2018 | A | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for locations of corrections needed. They include exit door hardware and emergency lighting. The fire doors also require annual inspection per NFPA 80 5.4.2.1
Ext 301 - Jason Phone #: ###-####
|
BLD-Final | 1/22/2018 | 1/23/2018 | 1/23/2018 | P | CANC |
Jim Storey
|
|
|
Ext 301 - Jason Phone #: ###-####
|
Plan assigned to (CDM) | 5/11/2017 | 5/11/2017 | 5/26/2017 | | PASS |
Carl D Madsen
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/26/2017 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/26/2017 | | DONE |
|
|
|
|
Print Occupancy Form | | | 5/26/2017 | | DONE |
|
|
|
|
Telephone call | | | 5/26/2017 | | |
|
|
|
called David to let know permit is ready-left message on his phone
|
Issue PAID IN FULL permit | | | 5/26/2017 | | DONE |
|
|
|
|
Routing - PUBLIC WORKS | 5/25/2017 | | 5/25/2017 | | PASS |
Rachael Beierle
|
|
|
no manufacturing. craft and bead supply shipping
|
Case Summary (BLD) | | | 5/24/2017 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 5/24/2017 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 5/19/2017 | | DONE |
|
|
|
|
Routing - FIRE | 5/18/2017 | 5/18/2017 | 5/18/2017 | | PASS |
Katie Marron
|
|
|
Comments attached to case.
|
Case Summary (BLD) | | | 5/18/2017 | | DONE |
|
|
|
|
1st review completed | | | 5/18/2017 | | FAIL |
|
|
|
Failed Public Works
|
Routing - PLAN CHECK | 5/12/2017 | | 5/18/2017 | | PASS |
Carl D Madsen
|
|
|
|
Routing - PUBLIC WORKS | 5/11/2017 | | 5/12/2017 | | FAIL |
Rachael Beierle
|
|
|
Need info on what warehouse is distributing and storing. attempted to contact owner and have not heard back. Unable to dind any info on distrobution co online.
|
Routing - Addressing | 5/11/2017 | | 5/11/2017 | | PASS |
Laura Hunter
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 5/11/2017 | | DONE |
|
|
|
|
Intake Approval | | | 5/11/2017 | | PASS |
Carl D Madsen
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 5/11/2017 | | DONE |
|
|
|
|
Application received | | 5/11/2017 | | | |
|
|
|
|