Second Notice | | 10/22/2017 | 10/25/2017 | | DONE |
|
|
|
|
Print Statement | | | 10/25/2017 | | DONE |
|
|
|
|
First Notice | | 9/29/2017 | 10/12/2017 | | DONE |
|
|
|
Mailed 10-13-17
|
Print Occupancy Form | | | 9/19/2017 | | DONE |
|
|
|
|
Permanent Occupancy | | | 9/19/2017 | | DONE |
|
|
|
|
BLD-Final | 9/13/2017 | 9/14/2017 | 9/14/2017 | P | PASS |
Jim Storey
|
|
|
Richard-please call for access code Phone #: ###-#### pass no card on site
|
FIRE-Final Inspection | 9/13/2017 | 9/14/2017 | 9/14/2017 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed.
Richard Phone #: ###-####-please call for access
|
BLD-Framing/Rough-in | 8/9/2017 | 8/10/2017 | 8/10/2017 | A | PASS |
Mike Jordan
|
|
|
Richard Phone #: ###-####
|
BLD-Energy code compliance | 8/10/2017 | 8/10/2017 | 8/10/2017 | A | PASS |
Mike Jordan
|
|
|
Richard Phone #: ###-####
|
BLD-Framing/Rough-in | 8/10/2017 | 8/10/2017 | 8/10/2017 | A | PASS |
Mike Jordan
|
|
|
Richard Phone #: ###-####
|
BLD-Framing/Rough-in | 8/3/2017 | 8/7/2017 | 8/7/2017 | A | FAIL |
Mike Jordan
|
|
|
Richard Phone #: ###-####. Seal all penetrations in draft stop. ok to insulate. Correction notice posted.
|
Issue PAID IN FULL permit | | | 8/1/2017 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/31/2017 | | DONE |
|
|
|
need GC and rev cert of val
|
Plan assigned to (CJW) | 6/6/2017 | 6/6/2017 | 7/29/2017 | | PASS |
Carl Westfall
|
|
|
(2nd done) (June 26 - 15 days) (16 sheets) Accretech America
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/29/2017 | | DONE |
|
|
|
|
Route to Impact Fee Review | 7/26/2017 | 7/29/2017 | 7/27/2017 | | PASS |
Eric Bilimoria
|
|
|
Review requested for Commercial Permit
|
Routing - PLUMBING | 7/26/2017 | | 7/27/2017 | | PASS |
Bill VanDegrift
|
|
|
per plans and ISPC
|
Routing - PLAN CHECK | 6/6/2017 | | 7/26/2017 | | PASS |
Carl Westfall
|
|
|
1st review completed. Drawings approved.
|
1st review completed | | | 7/26/2017 | | DONE |
|
|
|
|
Plan resubmittals requested | | | 7/26/2017 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/26/2017 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 7/26/2017 | | 7/26/2017 | | PASS |
Carl Westfall
|
|
|
Resubmittal routed
|
Routing - Design Review | 6/6/2017 | | 6/8/2017 | | PASS |
Sarah Schafer
|
|
|
Approved
|
Routing - FIRE | 6/6/2017 | 6/6/2017 | 6/7/2017 | | PASS |
Katie Marron
|
|
|
Building Shell was completed under BLD16-00525. Basic Life Safety. No comments required.
|
Routing - Erosion and Sediment | 6/6/2017 | | 6/7/2017 | | PASS |
Melissa Jannusch
|
|
|
|
Routing PW Environmental | 6/6/2017 | | 6/6/2017 | | PASS |
Rick Christenson
|
|
|
|
Routing - MECHANICAL | 6/6/2017 | | 6/6/2017 | | PASS |
Troy James
|
|
|
|
Routing - PLUMBING | 6/6/2017 | | 6/6/2017 | | FAIL |
Bill VanDegrift
|
|
|
1) P-4 - this seem to be a residential mobile home only water heater. Specify an appropriate water heater.
2) This mixing valve is not listed as ASSE 1070. add listed individual 1070 mixing valves at the lavs or install one in this location that is ASSE 1070 listed.
|
Routing - Addressing | 6/6/2017 | | 6/6/2017 | | PASS |
Laura Hunter
|
|
|
|
Routing - PUBLIC WORKS | 6/6/2017 | | 6/6/2017 | | PASS |
Rachael Beierle
|
|
|
|
Intake Approval | | | 6/6/2017 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
Julie completed pre screen, emailed applicant that this will be routed as majot TI for first time build out.
|
Plan Reviewer's activity | | | 6/6/2017 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
emailed applicant copy of achd letter requiring a review for TI on the building.
|
Intake Approval | | | 6/2/2017 | | FAIL |
Julie Romig
|
|
|
First time tenant build-out of a new shell/core building will be routed as a 520 application. Please submit the following to complete your application:
1. Completed 520 Checklist with any additional documentation as required in checklist.
2. Completed Form 304 with owner's signature.
3. Sign Lighting COMcheck form.
|
Plan Reviewer's activity | | | 6/2/2017 | | |
|
|
|
Route as 520 due to first time tenant build-out. Notified Architect via phone.
|
Application received | | | 6/1/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 1 2017 3:09PM
|