BLD-Aging Inspection | 8/1/2018 | 8/1/2018 | 8/1/2018 | | PEND |
Mike Jordan
|
|
|
|
Zoning Approval | 8/1/2018 | 8/1/2018 | 8/1/2018 | | DONE |
Andrea Tuning
|
|
|
Approved per Cody Riddle and Hal Simmons
|
Permanent Occupancy | | | 8/1/2018 | | DONE |
|
|
|
|
Temporary Occupancy | 6/25/2018 | 8/2/2018 | 6/25/2018 | | DONE |
Christina Prado
|
|
|
|
BLD-Final | 5/23/2018 | 5/24/2018 | 5/24/2018 | A | PASS |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by David Scaggs. All issues resolved. Ok for temp occ. will be ok for perm occ once zoning signs perm. No card to sign.
|
BLD-Final | 5/22/2018 | 5/23/2018 | 5/23/2018 | P | FAIL |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by David Scaggs. repair and complete sheet rock in fire riser room.
|
FIRE-Final Inspection | 5/22/2018 | 5/23/2018 | 5/23/2018 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
Phone #: ###-#### Inspection requested via web by David Scaggs
|
BLD-Final | 5/18/2018 | 5/18/2018 | 5/18/2018 | P | NR |
Mike Jordan
|
|
|
Mechanical and Fire Life Safety scheduled for PM as well. Phone #: ###-#### Inspection requested via web by David Scaggs
|
FIRE-Final Inspection | 5/18/2018 | 5/18/2018 | 5/18/2018 | P | FAIL |
Troy Cobbley
|
|
|
Shipping clip is on sidewall head in outside closet of 102, exhaust vent cover crosses head in down stairs closet of 101, missing celing in closet of 104, inspection stopped.
Phone #: ###-#### Inspection requested via web by David Scaggs
|
FIRE-Final Inspection | 5/16/2018 | 5/16/2018 | 5/16/2018 | P | FAIL |
Jim Page
|
|
|
FIR permits for fire sprinkler and fire alarm need to be finaled before life fire safety inspection can be performed.
Phone #: ###-#### Inspection requested via web by David Scaggs
|
Zoning Approval Temp | 5/15/2018 | 5/15/2018 | 5/15/2018 | | DONE |
Andrea Tuning
|
|
|
|
BLD-Conference | 5/3/2018 | 5/3/2018 | 5/3/2018 | P | DONE |
Tiffany Lowery
|
|
|
|
Print Occupancy Form | | | 4/23/2018 | | DONE |
|
|
|
|
BLD-Wall Bracing | 3/8/2018 | 3/9/2018 | 3/9/2018 | P | PASS |
Brandon Shaw
|
|
|
Phone #: ###-#### Inspection requested via web by Marty Short
|
BLD-Energy code compliance | 2/23/2018 | 2/23/2018 | 2/23/2018 | P | PASS |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by David Scaggs. Ok to cover interior only. Still needs wall bracing inspection
|
BLD-Framing/Rough-in | 2/22/2018 | 2/22/2018 | 2/22/2018 | P | PASS |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by David Scaggs
|
BLD-Framing/Rough-in | 2/21/2018 | 2/21/2018 | 2/21/2018 | P | NR |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by David Scaggs
|
BLD-Wall Bracing | 2/21/2018 | 2/21/2018 | 2/21/2018 | A | FAIL |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by Marty Short. Nial off floor to floor straps, missing fasteners. Due to construction debries and trenches around building, unable to complete inspection.
|
BLD-Footing | 1/8/2018 | 1/8/2018 | 1/8/2018 | A | DEFR |
Mike Jordan
|
|
|
Interior footings, concrete scheduled for 8am Phone #: ###-#### Inspection requested via web by Marty Short
|
BLD-Energy code compliance | 12/26/2017 | 12/27/2017 | 12/27/2017 | P | PASS |
Mike Jordan
|
|
|
Foundation insulation Phone #: ###-#### Inspection requested via web by Marty Short
|
BLD-Foundation | 12/17/2017 | 12/18/2017 | 12/18/2017 | A | PASS |
Mike Jordan
|
|
|
Concrete scheduled for 12pm Phone #: ###-#### Inspection requested via web by Marty Short
|
BLD-Footing | 12/8/2017 | 12/8/2017 | 12/8/2017 | A | PASS |
Brandon Shaw
|
|
|
Work in progress
Frost protection required
|
Issue PAID IN FULL permit | | | 10/23/2017 | | DONE |
|
|
|
|
Print Occupancy Form | | | 10/23/2017 | | DONE |
|
|
|
|
OVERRIDE | | | 10/19/2017 | | |
|
|
|
|
Plan assigned to (JAR) | 7/26/2017 | 7/26/2017 | 10/19/2017 | | DONE |
Julie Romig
|
|
|
1st Rev Comp - 506 Cimarron Apartments - 1345
|
Routing PW Sewer Rating | 10/19/2017 | | 10/19/2017 | | PASS |
Morgan Webb
|
|
|
|
Routing - PLAN CHECK | 10/16/2017 | | 10/19/2017 | | PASS |
Julie Romig
|
|
|
|
Routing Off Site - STRUCTURAL | 10/16/2017 | | 10/19/2017 | | PASS |
Julie Romig
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/19/2017 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/19/2017 | | DONE |
|
|
|
NEED
ACHD
Revised Cert of Value - MET
RP - MET
GC Form - MET
|
Routing - PLAN CHECK | 10/3/2017 | | 10/10/2017 | | FAIL |
Julie Romig
|
|
|
|
Routing Off Site - STRUCTURAL | 10/3/2017 | | 10/10/2017 | | FAIL |
Julie Romig
|
|
|
2nd Review - AHJ
|
Routing - FIRE | 10/3/2017 | 10/3/2017 | 10/6/2017 | | PASS |
Scott Arellano
|
|
|
IFC plan review report attached to BLD17-02417.
|
Routing PW Sewer Design | 10/4/2017 | | 10/5/2017 | | PASS |
Kyle S. Rosenmeyer
|
|
|
Passed per ePlanReview and main permit BLD17-02410 by KSR
|
Routing - PUBLIC WORKS | 10/3/2017 | | 10/4/2017 | | PASS |
Rachael Beierle
|
|
|
|
Route to Impact Fee Review | 9/20/2017 | 9/23/2017 | 9/21/2017 | | PASS |
Eric Bilimoria
|
|
|
Review requested for Commercial Permit
|
Routing PW Solid Waste | 7/27/2017 | | 9/21/2017 | | PASS |
|
|
|
|
Routing - MECHANICAL | 7/26/2017 | | 9/21/2017 | | PASS |
Troy James
|
|
|
|
Routing - PLANNING Land Div | 7/26/2017 | | 9/21/2017 | | PASS |
Todd Tucker
|
|
|
|
Routing PW Drainage | 7/27/2017 | | 9/21/2017 | | PASS |
Brian Murphy
|
|
|
|
Routing - PLAN CHECK | 7/26/2017 | | 9/20/2017 | | FAIL |
Julie Romig
|
|
|
Corrections required per ePlanReview
|
1st review completed | | | 9/20/2017 | | DONE |
Julie Romig
|
|
|
|
Routing Off Site - STRUCTURAL | 7/26/2017 | | 8/10/2017 | | FAIL |
Julie Romig
|
|
|
Corrections required per ePlanReview
|
Routing - Erosion and Sediment | 7/26/2017 | | 8/7/2017 | | PASS |
Andy J. Long
|
|
|
ESC plan submitted and approved under main site ESC/GRD permit, see GRD17-00007/ESC17-00102. Need to designate valid RP. (not Jerry Fairbank - no longer onsite)
|
Routing - Design Review | 7/26/2017 | | 8/4/2017 | | PASS |
Andrea Tuning
|
|
|
|
Routing - Addressing | 7/26/2017 | | 7/31/2017 | | PASS |
Doug Chausow
|
|
|
|
Routing PW Street Lights | 7/27/2017 | | 7/31/2017 | | PASS |
Tom Marshall
|
|
|
|
Routing - FIRE | 7/26/2017 | 7/26/2017 | 7/28/2017 | | FAIL |
Scott Arellano
|
|
|
See BLD17-02410 for plan review report.
|
Routing PW Sewer Design | 7/27/2017 | | 7/28/2017 | | FAIL |
Kyle S. Rosenmeyer
|
|
|
Need to include civil sheets showing connections to public sewer.
|
Routing - PLUMBING | 7/26/2017 | | 7/28/2017 | | PASS |
Bill VanDegrift
|
|
|
|
Routing - PLANNING | 7/26/2017 | | 7/27/2017 | | PASS |
Cody Riddle
|
|
|
|
Routing - PUBLIC WORKS | 7/26/2017 | | 7/27/2017 | | PASS |
Rachael Beierle
|
|
|
|
Intake Approval | | | 7/26/2017 | | PASS |
|
|
|
|
Application received | | | 7/14/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 14 2017 1:22PM
|
First Notice | | 8/11/2018 | | | |
|
|
|
|
Routing PW Sewer Rating | 7/27/2017 | | | | FAIL |
Beverly Mountain
|
|
|
No dimensioned site plan
|