Zoning Approval | 8/1/2018 | 8/1/2018 | 8/1/2018 | | DONE |
Andrea Tuning
|
|
|
Approved per Cody Riddle and Hal Simmons
|
Permanent Occupancy | | | 8/1/2018 | | DONE |
|
|
|
|
Temporary Occupancy | 7/30/2018 | 8/2/2018 | 7/30/2018 | | DONE |
Christina Prado
|
|
|
|
Print Occupancy Form | | | 7/30/2018 | | DONE |
|
|
|
|
BLD-Final | 7/10/2018 | 7/10/2018 | 7/10/2018 | P | PASS |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by David Scaggs. Ok for temp oc. Will be ok for perm occ. once zoning signs perm. No card on site to sign.
|
BLD-Final | 7/9/2018 | 7/9/2018 | 7/9/2018 | P | CANC |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by David Scaggs Inspection cancelled from web by: David Scaggs
|
BLD-Final | 7/3/2018 | 7/3/2018 | 7/3/2018 | P | FAIL |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by David Scaggs. Noted some 20 min doors not installed, all 20 min doors need to be self closing. Fire caulk all penetrations in garages. Still need to verifiy 1 hr. wall continuity in garage to bottom of roof deck.
|
BLD-Final | 7/2/2018 | 7/2/2018 | 7/2/2018 | P | NR |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by David Scaggs. Needs mech. final.
|
FIRE-Final Inspection | 6/28/2018 | 6/28/2018 | 6/28/2018 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
Phone #: ###-#### Inspection requested via web by David Scaggs
|
Zoning Approval Temp | 5/15/2018 | 5/15/2018 | 5/15/2018 | | DONE |
Andrea Tuning
|
|
|
|
PubWorks Occupancy Approval | 5/3/2018 | 5/3/2018 | 5/3/2018 | | DONE |
Tiffany Lowery
|
|
|
|
Print Occupancy Form | | | 4/23/2018 | | DONE |
|
|
|
|
BLD-Energy code compliance | 4/12/2018 | 4/12/2018 | 4/12/2018 | P | PASS |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by David Scaggs
|
BLD-Energy code compliance | 4/11/2018 | 4/11/2018 | 4/11/2018 | P | NR |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by David Scaggs
|
BLD-Framing/Rough-in | 4/10/2018 | 4/10/2018 | 4/10/2018 | P | FAIL |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by David Scaggs. Provide revised truss engineering, fireblock double common walls at 2nd. floor.
|
BLD-Framing/Rough-in | 4/9/2018 | 4/9/2018 | 4/9/2018 | P | NR |
Mike Jordan
|
|
|
Pending fire sprinkler inspection Phone #: ###-#### Inspection requested via web by David Scaggs
|
BLD-Wall Bracing | 3/29/2018 | 3/29/2018 | 3/29/2018 | P | PASS |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by David Scaggs
|
BLD-Wall Bracing | 3/28/2018 | 3/28/2018 | 3/28/2018 | P | NR |
Dave Hannah
|
|
|
Will have approved set of plans onsite. Phone #: ###-#### Inspection requested via web by David Scaggs
|
BLD-Wall Bracing | 3/27/2018 | 3/27/2018 | 3/27/2018 | P | FAIL |
Mike Jordan
|
|
|
Phone #: ###-#### Inspection requested via web by David Scaggs
|
BLD-Footing | 2/15/2018 | 2/15/2018 | 2/15/2018 | A | PASS |
Mike Jordan
|
|
|
Interior footings, concrete is scheduled for 9am Phone #: ###-#### Inspection requested via web by Marty Short
|
BLD-Footing | 2/2/2018 | 2/2/2018 | 2/2/2018 | P | DEFR |
Mike Jordan
|
|
|
Interior footings, concrete is scheduled for 1pm Phone #: ###-#### Inspection requested via web by Marty Short. Concrete already placed when on site.
|
BLD-Energy code compliance | 1/24/2018 | 1/24/2018 | 1/24/2018 | A | PASS |
Mike Jordan
|
|
|
Foundation insulation Phone #: ###-#### Inspection requested via web by Marty Short
|
BLD-Foundation | 1/22/2018 | 1/22/2018 | 1/22/2018 | P | PASS |
Mike Jordan
|
|
|
Concrete is scheduled for 2pm Phone #: ###-#### Inspection requested via web by Marty Short
|
BLD-Footing | 1/12/2018 | 1/12/2018 | 1/12/2018 | A | PASS |
Mike Jordan
|
|
|
Concrete scheduled for 10am Phone #: ###-#### Inspection requested via web by Marty Short
|
Issue PAID IN FULL permit | | | 10/23/2017 | | DONE |
|
|
|
|
Print Occupancy Form | | | 10/23/2017 | | DONE |
|
|
|
|
OVERRIDE | | | 10/19/2017 | | |
|
|
|
|
Plan assigned to (JAR) | 7/26/2017 | 7/26/2017 | 10/19/2017 | | DONE |
Julie Romig
|
|
|
1st Rev Comp - 506 Cimarron Apartments - 1363 6-plex
|
Routing PW Sewer Rating | 10/19/2017 | | 10/19/2017 | | PASS |
Morgan Webb
|
|
|
|
Routing - PLAN CHECK | 10/16/2017 | | 10/19/2017 | | PASS |
Julie Romig
|
|
|
|
Routing Off Site - STRUCTURAL | 10/16/2017 | | 10/19/2017 | | PASS |
Julie Romig
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/19/2017 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/19/2017 | | DONE |
|
|
|
NEED
ACHD
Revised Cert of Value - MET
RP - MET
GC Form - MET
|
Routing - PLAN CHECK | 10/3/2017 | | 10/10/2017 | | FAIL |
Julie Romig
|
|
|
|
Routing Off Site - STRUCTURAL | 10/3/2017 | | 10/10/2017 | | FAIL |
Julie Romig
|
|
|
2nd Review - AHJ
|
Routing - FIRE | 10/3/2017 | 10/3/2017 | 10/6/2017 | | PASS |
Scott Arellano
|
|
|
IFC plan review report attached to BLD17-02417.
|
Routing PW Sewer Design | 10/4/2017 | | 10/5/2017 | | PASS |
Kyle S. Rosenmeyer
|
|
|
Passed per ePlanReview and main permit BLD17-02410 by KSR
|
Routing - Design Review | 10/3/2017 | | 10/4/2017 | | PASS |
Andrea Tuning
|
|
|
|
Routing - PUBLIC WORKS | 10/3/2017 | | 10/4/2017 | | PASS |
Rachael Beierle
|
|
|
|
Route to Impact Fee Review | 9/20/2017 | 9/23/2017 | 9/21/2017 | | PASS |
Eric Bilimoria
|
|
|
Review requested for Commercial Permit
|
Routing PW Solid Waste | 7/27/2017 | | 9/21/2017 | | PASS |
|
|
|
|
Routing - MECHANICAL | 7/26/2017 | | 9/21/2017 | | PASS |
Troy James
|
|
|
|
Routing - PLANNING Land Div | 7/26/2017 | | 9/21/2017 | | PASS |
Todd Tucker
|
|
|
|
Routing PW Drainage | 7/27/2017 | | 9/21/2017 | | PASS |
Brian Murphy
|
|
|
|
Routing - PLAN CHECK | 7/26/2017 | | 9/20/2017 | | FAIL |
Julie Romig
|
|
|
Corrections required per ePlanReview
|
1st review completed | | | 9/20/2017 | | DONE |
Julie Romig
|
|
|
|
Routing Off Site - STRUCTURAL | 7/26/2017 | | 8/10/2017 | | FAIL |
Julie Romig
|
|
|
Corrections required per ePlanReview
|
Routing - Erosion and Sediment | 7/26/2017 | | 8/7/2017 | | PASS |
Andy J. Long
|
|
|
ESC plan submitted and approved under main site ESC/GRD permit, see GRD17-00007/ESC17-00102. Need to designate valid RP. (not Jerry Fairbank - no longer onsite)
|
Routing - Design Review | 7/26/2017 | | 8/4/2017 | | FAIL |
Andrea Tuning
|
|
|
|
Routing - Addressing | 7/26/2017 | | 7/31/2017 | | PASS |
Doug Chausow
|
|
|
|
Routing PW Street Lights | 7/27/2017 | | 7/31/2017 | | PASS |
Tom Marshall
|
|
|
|
Routing - FIRE | 7/26/2017 | 7/26/2017 | 7/28/2017 | | FAIL |
Scott Arellano
|
|
|
See BLD17-02410 for plan review report.
|
Routing PW Sewer Design | 7/27/2017 | | 7/28/2017 | | FAIL |
Kyle S. Rosenmeyer
|
|
|
Need to include civil sheets showing connections to public sewer.
|
Routing - PLUMBING | 7/26/2017 | | 7/28/2017 | | PASS |
Bill VanDegrift
|
|
|
|
Routing - PLANNING | 7/26/2017 | | 7/27/2017 | | PASS |
Cody Riddle
|
|
|
|
Routing - PUBLIC WORKS | 7/26/2017 | | 7/27/2017 | | PASS |
Rachael Beierle
|
|
|
|
Intake Approval | | | 7/26/2017 | | PASS |
Julie Romig
|
|
|
|
Application received | | | 7/14/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 14 2017 1:22PM
|
First Notice | | 8/11/2018 | | | |
|
|
|
|
Routing PW Sewer Rating | 7/27/2017 | | | | CANC |
Beverly Mountain
|
|
|
No dimensioned site plan
|