Permit EXPIRED | | | 2/25/2019 | | DONE |
|
|
|
tucker enterprises is no longer in the space per parcel owner
|
BLD-Final | 1/30/2019 | 2/6/2019 | 2/6/2019 | P | NR |
Jim Storey
|
|
|
Ann Phone #: ###-####
|
FIRE-Final Inspection | 1/30/2019 | 2/6/2019 | 2/6/2019 | A | FAIL |
Troy Cobbley
|
|
|
I left message on contacts voice mail that I was on the way. I went to project site but was only able to make contact with the tenant (troy). No inspection was performed.
Ann Phone #: ###-####
|
BLD-Final | 1/29/2019 | 1/31/2019 | 1/31/2019 | P | CANC |
Jim Storey
|
|
|
Ann Phone #: ###-####
|
FIRE-Final Inspection | 1/29/2019 | 1/31/2019 | 1/31/2019 | A | CANC |
Troy Cobbley
|
|
|
Cancel per Ann Phone #: ###-####
|
BLD - Request for Extension | 1/9/2019 | 1/10/2019 | 1/10/2019 | P | DEFR |
Jim Storey
|
|
|
Call for access- Ann Phone #: ###-#### Adele Schaffeld-Griffin Assistant Building Official
Planning and Development Services
Office: ###-####
aschaffeldgriffin@cityofboise.org
|
FIRE-Final Inspection | 1/8/2019 | 1/10/2019 | 1/10/2019 | A | CANC |
Troy Cobbley
|
|
|
please call 1 hr ahead // Ann Moffat Phone #: ###-####
|
BLD-Final | 1/8/2019 | 1/10/2019 | 1/10/2019 | P | CANC |
Jim Storey
|
|
|
please call 1 hr ahead // Ann Moffat Phone #: ###-####
|
BLD-Aging Inspection | 11/23/2018 | 11/23/2018 | 11/23/2018 | | PASS |
Jim Storey
|
|
|
Attn Carl Madsen; 223 Roedel and Extendobed would like to request an extension on building permits for the following properties located at 4242 Eagleson Road, Boise, ID 83705 and 5498 W Albatros, Boise, ID 83705. The permits numbers are as follows; £-ep .A.c..k. 4s oJ. 7 .. 1 ~ -1 Y BLD17- 02434 1- I 1-1 ~ BLDl 7- 02435 , ..... I t-1 (' BLD17-02436 1-11,1t' BLD17- 02437 . Z-- "'2.s-1 V BLD17- 02438 z..,. L.S-- ll( BLD17- 02439 1,--i:S-- IY We have been working on the modifications for the fire suppression system for the past 11 months due to an unpermitted mezzanine in one of the buildings. The tenant has removed the mezzanine and we are proceeding forward with the sprinkler system.
|
BLD-Aging Inspection | 11/22/2018 | 11/22/2018 | 11/23/2018 | | PASS |
Jim Storey
|
|
|
Attn Carl Madsen; 223 Roedel and Extendobed would like to request an extension on building permits for the following properties located at 4242 Eagleson Road, Boise, ID 83705 and 5498 W Albatros, Boise, ID 83705. The permits numbers are as follows; £-ep .A.c..k. 4s oJ. 7 .. 1 ~ -1 Y BLD17- 02434 1- I 1-1 ~ BLDl 7- 02435 , ..... I t-1 (' BLD17-02436 1-11,1t' BLD17- 02437 . Z-- "'2.s-1 V BLD17- 02438 z..,. L.S-- ll( BLD17- 02439 1,--i:S-- IY We have been working on the modifications for the fire suppression system for the past 11 months due to an unpermitted mezzanine in one of the buildings. The tenant has removed the mezzanine and we are proceeding forward with the sprinkler system.
|
Extend Review Timeline | | | 7/13/2018 | | DONE |
|
|
|
1st approved 180 day extension per Adele. see documents
|
BLD-Aging Inspection | 1/11/2018 | 1/11/2018 | 1/12/2018 | | PASS |
Jim Storey
|
|
|
wip with fire
|
BLD-Final | 8/25/2017 | 8/29/2017 | 8/29/2017 | P | NR |
Jim Storey
|
|
|
Chad Phone #: ###-#### fire sent back to planreview resch.
|
FIRE-Final Inspection | 8/25/2017 | 8/29/2017 | 8/29/2017 | A | FAIL |
Troy Cobbley
|
|
|
Provide correct building address and suite number, remove thumbturn deadbolts and provide single action hardware. Keyed is ok at main exit. Sprinklers are too low in both Rest Rooms. Provide sprinkler coverage under the Mezzanine and under the overhead door. Provide racking permit for racks over 8' and storage over 12' in height.
Provide annual inspection of the fire sprinkler system and provide fire sprinkler monitoring. Chad Phone #: ###-####
|
Issue PAID IN FULL permit | | | 8/25/2017 | | DONE |
|
|
|
|
Print Occupancy Form | | | 8/25/2017 | | DONE |
|
|
|
|
Plan assigned to (JG) | 7/18/2017 | 7/18/2017 | 7/26/2017 | | PASS |
Javier Guzman
|
|
|
1st rev comp, 7/24 L2 Tucker Enterprises Suite 102 Occ eval ePlan
|
Routing - PLAN CHECK | 7/26/2017 | | 7/26/2017 | | PASS |
Javier Guzman
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/26/2017 | | DONE |
Javier Guzman
|
|
|
|
Permit Ready to Issue | | | 7/26/2017 | | DONE |
Christina Prado
|
|
|
All requirements met, fees due (#528 application)
|
Routing - PLAN CHECK | 7/18/2017 | | 7/25/2017 | | FAIL |
Javier Guzman
|
|
|
Pending response from architect regarding requested areas of fabrication not shown on plans
|
1st review completed | | | 7/25/2017 | | FAIL |
Javier Guzman
|
|
|
|
Routing - FIRE | 7/18/2017 | 7/18/2017 | 7/19/2017 | | PASS |
Scott Arellano
|
|
|
No comments attached. Final approval will be subject to satisfactory field inspection of existing tenant spaces by the PDS/Fire inspector.
|
Routing - Addressing | 7/18/2017 | | 7/19/2017 | | PASS |
Doug Chausow
|
|
|
|
Routing - PUBLIC WORKS | 7/18/2017 | | 7/18/2017 | | PASS |
Rachael Beierle
|
|
|
|
Intake Approval | | | 7/18/2017 | | PASS |
Javier Guzman
|
|
|
|
Application received | | | 7/15/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 15 2017 2:55PM
|