Permit Information
Permit NumberBLD17-02477
StatusFinaled
Name BILTMORE COMPANY
Site Address 3022 S OWYHEE ST
Project NameOwyhee Park Aprtments
Customer NumberBLD17-02478 (FOUNDATION BLD17-03918
ePlanReviewYes
Description
(OWYHEE PARK APARTMENTS) Bldg 1 units (101-108, 201-208, 301-308) THERE ARE TWO PERMITS ASSOCIATED WITH THIS E-PLAN. Permit for the construction of a new 27,135 sq. ft., 3 story 24 unit, wood framed apartment building with 8 units per story per the approved plans. Utilities and Drainage approved under GRD17-00010. Project approved under PUD16-00028 & DRH16-00444. This building is fully fire sprinklered with a NFPA 13r system for story increase. CDM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Zoning Approval11/26/201811/26/201811/26/2018 DONE
DetailsBrent Moore
Permanent Occupancy  11/26/2018 DONE
BLD-Final11/15/201811/15/201811/15/2018PPASS
DetailsJim Storey
Cody Phone #: ###-####
Temporary Occupancy11/15/20182/13/201911/15/2018 DONE
DetailsTisha Gallop
Temp occ approved for all units. Perm pending p&z approval
FIRE-Final Inspection11/13/201811/14/201811/14/2018APASS
DetailsMike Jordan
Cody Phone #: ###-####/. Remaining units ok. 107,108,207,208,307,308. Final life /safety ok.
BLD-Final11/9/201811/9/201811/9/2018PPASS
DetailsJim Storey
Cody Phone #: ###-#### 03 05
Temporary Occupancy11/9/20182/7/201911/9/2018 DONE
DetailsTisha Gallop
temp occ for 105, 106, 205, 206, 305, 306
FIRE-Conference11/6/201811/6/201811/6/2018PDONE
DetailsTroy Cobbley
I spoke to Cody about needing more clearance for the FDC. I have involved Ron with the Boise Fire Dept with this issue.
BLD-Final11/2/201811/2/201811/2/2018PPASS
DetailsJim Storey
Cody Phone #: ###-#### 103 - 305
FIRE-Final Inspection11/1/201811/2/201811/2/2018APART
DetailsTroy Cobbley
Life safety passed for apartments 103, 104, 203, 204, 303, 304, 105, 106, 205, 206, 305, 306

Cody Phone #: ###-####
Temporary Occupancy11/2/20181/31/201911/2/2018 DONE
DetailsTisha Gallop
units 103, 104, 203, 204, 303, 304
BLD-Final10/29/201810/30/201810/30/2018APASS
DetailsJim Storey
Cody Phone #: ###-#### // 01 02
Temporary Occupancy10/30/20181/28/201910/30/2018 DONE
DetailsBrittany Hill
PubWorks Occupancy Approval10/30/201810/30/201810/30/2018 DONE
DetailsTiffany Lowery
Zoning Approval Temp10/25/201810/25/201810/25/2018 PASS
DetailsJosh Wilson
Temp occ ok until 3/29/19 per recorded bonding agreement for landscaping, etc.
FIRE-Final Inspection10/23/201810/23/201810/24/2018PPART
DetailsTroy Cobbley
The six apartments at the north end of the building life safety's are complete. Apartments 101, 102, 201, 202, 103, 203.

Cody Phone #: ###-####
BLD-Other10/11/201810/12/201810/12/2018APASS
DetailsJim Storey
Cody-RCI channel Phone #: ###-####
BLD-Energy code compliance10/4/201810/4/201810/4/2018PPASS
DetailsJim Sly
Pat-STE 107, 108, 207, 208, 307 & 308 Phone #: ###-####
BLD-Framing/Rough-in10/1/201810/2/201810/2/2018APASS
DetailsJim Storey
Cody Phone #: ###-####
BLD-Framing/Rough-in10/1/201810/1/201810/1/2018PDEFR
DetailsJim Storey
Cody Phone #: ###-####
BLD-Wall cover9/21/20189/21/20189/21/2018PPASS
DetailsJim Storey
Cody Phone #: ###-#### rc ok
BLD-Energy code compliance9/14/20189/14/20189/17/2018PPASS
DetailsJim Storey
3rd set of six units- cody Phone #: ###-####
BLD-Framing/Rough-in9/12/20189/12/20189/12/2018PPART
DetailsJim Storey
Cody Phone #: ###-#### finsh fire wall at exit// ok to insulate
BLD-Framing/Rough-in9/11/20189/11/20189/11/2018PNR
DetailsJim Storey
Cody Phone #: ###-####
BLD-Wall Bracing9/7/20189/7/20189/7/2018PPART
DetailsJim Storey
Cody Phone #: ###-#### rc ok 12/03/04
BLD-Wall Bracing8/30/20188/30/20188/30/2018PPART
DetailsBrandon Shaw
Hat channel, units- 101, 102, 201, 202
BLD-Energy code compliance8/28/20188/29/20188/29/2018APASS
DetailsJim Storey
Cody Phone #: ###-####
BLD-Framing/Rough-in8/24/20188/24/20188/24/2018PPASS
DetailsJim Storey
Cody Phone #: ###-####
BLD-Energy code compliance8/20/20188/20/20188/21/2018PPASS
DetailsJim Storey
suties 101,102,201,202,301,302- Pat Phone #: ###-####
BLD-Framing/Rough-in8/14/20188/15/20188/15/2018PPASS
DetailsJim Storey
Cody Phone #: ###-#### north units west building 1/2/3 frame ok//
BLD-Wall Bracing7/19/20187/20/20187/20/2018APASS
DetailsJim Storey
Cody Phone #: ###-#### ok to wrap exterior
Issue PAID IN FULL permit  2/14/2018 DONE
Print Occupancy Form  2/14/2018 DONE
Print Occupancy Form  2/14/2018 DONE
Print Occupancy Form  1/12/2018 DONE
OVERRIDE  1/11/2018  
Routing - PLAN CHECK1/11/2018 1/11/2018 PASS
DetailsCarl D Madsen
PLANS/APPL TAKEN TO FRONT DESK  1/11/2018 DONE
Extend Review Timeline  1/11/2018 DONE
1st approved 180 day extension per adele. see documents
Permit Ready to Issue  1/11/2018 DONE
ALL MET

Need DO NOT ISSUE WITHOUT BLD17-02478
ACHD - met
Cert of value (need one with correct address on it)
RP (which person)
Close out foundation permit Bld17-03918 when this permit is issued.
Routing - PLAN CHECK12/15/2017 12/15/2017 FAIL
DetailsCarl D Madsen
Plan Modification Accepted  12/11/2017 DONE
new manual j reports
Routing - MECHANICAL12/11/2017 12/11/2017 PASS
DetailsTroy James
resubmitted manual j report
Routing - PLANNING10/23/2017 11/6/2017 PASS
DetailsTodd Tucker
Routing Off Site - STRUCTURAL10/23/2017 11/5/2017 PASS
DetailsCarl D Madsen
Routing - PLAN CHECK10/23/2017 11/5/2017 FAIL
DetailsCarl D Madsen
Plan assigned to (CDM)8/3/20178/3/201711/2/2017 PASS
DetailsCarl D Madsen
Owyhee apartments 1st Done
Route to Impact Fee Review9/11/20179/14/20179/22/2017 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
Routing - PLANNING8/3/2017 9/11/2017 FAIL
DetailsCarl D Madsen
Routing PW Sewer Design8/3/2017 9/11/2017 PASS
DetailsMike Sheppard
Routing - PUBLIC WORKS9/11/2017 9/11/2017 PASS
DetailsMike Sheppard
1st review completed  9/11/2017 FAIL
Routing - PLANNING Land Div8/3/2017 9/10/2017 PASS
DetailsTodd Tucker
Routing Off Site - STRUCTURAL8/3/2017 9/10/2017 FAIL
DetailsCarl D Madsen
Routing - PLAN CHECK8/3/2017 9/10/2017 FAIL
DetailsCarl D Madsen
Routing - FIRE8/3/20178/3/20178/10/2017 PASS
DetailsScott Arellano
Attached review comments to plans.
Routing - Erosion and Sediment8/3/2017 8/8/2017 PASS
DetailsAndy J. Long
SWPPP/ESC plan approved. Valid stormwater team designated. BMP installation & site preparation inspection is required prior to earthwork.
Routing - Addressing8/3/2017 8/4/2017 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS8/3/2017 8/4/2017 PASS
DetailsRachael Beierle
Routing - Design Review8/3/2017 8/4/2017 PASS
DetailsSarah Schafer
Approved per DRH17-00444.
Routing - MECHANICAL8/3/2017 8/3/2017 PASS
DetailsTroy James
Routing - PLUMBING8/3/2017 8/3/2017 PASS
DetailsBill VanDegrift
See redline notes and install per plan and ISPC.
Intake Approval  8/3/2017 PASS
Routing PW Solid Waste8/3/2017 8/3/2017 PASS
DetailsEvan Carpenter
Routing PW Street Lights8/3/2017 8/3/2017 PASS
DetailsTom Marshall
Routing PW Drainage8/3/2017 8/3/2017 PASS
DetailsBrian Murphy
Intake Approval  7/31/2017 FAIL
DetailsJavier Guzman
Please provide and upload the following:
2. Please provide and upload a completely fill out form #310 which consist of ten pages (only the cover sheet was filled out plus 4 blank sheets were uploaded, on the left side on pages 2 thru 10 of form #310 please check appropriate box or appropriate section that applies to project and upload all 10 pages) 7-31-2017.
Please provide a completed Form #310 – Statement of Special Inspections must be completed by the design engineer
Intake Approval  7/20/2017 FAIL
DetailsJavier Guzman
Please provide and upload the following:
1. Please provide owner signature on the form #304
2. Please provide a completed Form #310 – Statement of Special Inspections must be completed by the design engineer
3. Please provide ESC drawing plans (EC-101 and EC-501) on a minimum 18” x 24” sheets
4. Please provide a detail to show stair tread and riser measurements
5. Please provide smoke alarm & carbon monoxide alarm locations, on plan sheet E-3 the symbol for smoke detector not found on plan sheet E-2 as stated and no symbol for carbon monoxide detector found on legend or plan sheet
6. Please show on plumbing plans the backflow protection
Application received  7/18/2017 DONE
Application submitted via PDS Online on Jul 18 2017 4:18PM
First Notice 12/6/2018