Print Statement | | | 12/16/2019 | | DONE |
|
|
|
|
Telephone call | | | 12/16/2019 | | DONE |
|
|
|
emailed Jamie Walter in AP at Andersen Construction to let her know that final fees are due and emailed her the statement.
|
Telephone call | | | 12/16/2019 | | DONE |
|
|
|
Jamie Walters responded to my email saying that she is working on it.
|
Print Statement | | | 11/27/2019 | | DONE |
|
|
|
2nd notice
|
Print Statement | | | 11/14/2019 | | DONE |
|
|
|
|
Print Statement | | | 8/22/2019 | | DONE |
|
|
|
|
Third Notice | | 7/15/2019 | 8/13/2019 | | DONE |
|
|
|
mailed 8-13 with second follow up
|
Second Follow up | | | 8/13/2019 | | DONE |
|
|
|
|
Third Notice | | 6/12/2019 | 7/10/2019 | | DONE |
|
|
|
mailed 7-11 with first follow up
|
First Follow up | | | 7/10/2019 | | DONE |
|
|
|
|
Third Notice | | 5/11/2019 | 6/7/2019 | | DONE |
|
|
|
mailed 6-10
|
Second Notice | | 4/18/2019 | 5/6/2019 | | DONE |
|
|
|
mailed 5-10-19
|
First Notice | | 4/8/2019 | 4/8/2019 | | DONE |
|
|
|
mailed 4-11-19
|
Permanent Occupancy | | | 3/29/2019 | | DONE |
|
|
|
|
BLD-Final | 3/18/2019 | 3/18/2019 | 3/18/2019 | P | PASS |
Dave Hannah
|
|
|
Pete Phone #: ###-#### ok mfor perm occ
|
BLD-Final | 3/5/2019 | 3/5/2019 | 3/5/2019 | P | PEND |
Dave Hannah
|
|
|
Pete Phone #: ###-#### needs mec final
|
FIRE-Final Inspection | 3/5/2019 | 3/5/2019 | 3/5/2019 | P | PASS |
Jim Page
|
|
|
Final life fire safety inspection for area of work complete.
Pete Phone #: ###-####
|
BLD-Aging Inspection | 1/9/2019 | 1/9/2019 | 1/9/2019 | | PEND |
Dave Hannah
|
|
|
|
Temporary Occupancy | 11/26/2018 | 2/24/2019 | 11/26/2018 | | DONE |
Candy A. Nichols
|
|
|
Jason Blias ok'd 90 day ext from 12-31-18 for the temp c of o
|
BLD-Aging Inspection | 10/29/2018 | 10/29/2018 | 11/2/2018 | | PEND |
Dave Hannah
|
|
|
|
Temporary Occupancy | 10/5/2018 | 1/3/2019 | 10/5/2018 | | DONE |
Candy A. Nichols
|
|
|
per Jason Blais-ok to extend temp c of o thru Dec 25th
|
Temporary Occupancy | 10/5/2018 | 1/3/2019 | 10/5/2018 | | DONE |
Candy A. Nichols
|
|
|
per Jason Blais extension of the temp c of o is granted thru 12/31/18 not 12/25/18
|
Telephone call | | | 10/5/2018 | | DONE |
|
|
|
called Tyler- Tem C of O is expired-left message on his cell
|
Temporary Occupancy | 6/28/2018 | 9/26/2018 | 6/28/2018 | | DONE |
Candy A. Nichols
|
|
|
|
Temporary Occupancy | 6/28/2018 | 9/26/2018 | 6/28/2018 | | DONE |
Candy A. Nichols
|
|
|
as per Jason Blais-ext granted thru 10/2/18
|
BLD-Aging Inspection | 6/5/2018 | 6/5/2018 | 6/11/2018 | | PEND |
Dave Hannah
|
|
|
|
BLD-Conference | 4/5/2018 | 4/6/2018 | 4/6/2018 | A | PEND |
Dave Hannah
|
|
|
Tyler Phone #: ###-#### ada sales counter
|
Temporary Occupancy | 4/5/2018 | 7/4/2018 | 4/5/2018 | | DONE |
Candy A. Nichols
|
|
|
as per Jim Page ok to have no inspection results in the Fire permit attached
|
BLD-Final | 4/2/2018 | 4/3/2018 | 4/3/2018 | P | PART |
Dave Hannah
|
|
|
Pete Phone #: ###-#### ok for temp
|
FIRE-Final Inspection | 4/2/2018 | 4/3/2018 | 4/3/2018 | A | PART |
Jim Page
|
|
|
Final life fire safety inspection complete for TCO in requested area of this permit, fire extinguisher is in break room with a current inspection tag, fire alarm and fire sprinkler work to be completed with core and shell remodel. Per conversation with Romeo TCO is authorized for 90 days.
|
FIRE-Conference | 3/27/2018 | 3/27/2018 | 3/27/2018 | P | DONE |
Jim Page
|
|
|
Fire conference complete, a formal TCO request will need to be submitted to the fire code official and the building code official.
|
FIRE-Conference | 2/16/2018 | 2/20/2018 | 2/20/2018 | A | DONE |
Jim Page
|
|
|
Fire conference complete.
|
BLD-Framing/Rough-in | 2/14/2018 | 2/15/2018 | 2/15/2018 | A | PASS |
Dave Hannah
|
|
|
Pete Phone #: ###-####
|
Telephone call | | | 1/24/2018 | | DONE |
|
|
|
emailed Tyler that if he doesn't email the signed permit back to me today before noon, he will need to reply to myself and Christina so one of us can attach to Tidemark and sign off in the e plan system when we get it so they can print the approved plans
|
Issue PAID IN FULL permit | | | 1/23/2018 | | DONE |
|
|
|
|
Print Occupancy Form | | | 1/23/2018 | | DONE |
|
|
|
|
Telephone call | | | 1/18/2018 | | DONE |
|
|
|
Spoke with Lindsay informing her that this permit is going to expire in 3 days and is welcome to send in a request for a 180 extension.
|
Expiration Notice | 1/2/2018 | 1/23/2018 | 1/2/2018 | | DONE |
Brittany Hill
|
|
|
|
Plan assigned to (CDM) | 8/1/2017 | 8/1/2017 | 9/22/2017 | | PASS |
Carl D Madsen
|
|
|
Hue Salon 1st done
|
Routing - PLAN CHECK | 9/7/2017 | | 9/22/2017 | | PASS |
Carl D Madsen
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/22/2017 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/22/2017 | | DONE |
Christina Prado
|
|
|
Need:
GC Form-met
Revised Cert of Value-met
|
Route to Impact Fee Review | 8/24/2017 | 8/27/2017 | 9/14/2017 | | PASS |
Eric Bilimoria
|
|
|
Review requested for Commercial Permit
|
1st review completed | | | 8/24/2017 | | FAIL |
|
|
|
|
Routing - PLAN CHECK | 8/1/2017 | | 8/24/2017 | | FAIL |
Carl D Madsen
|
|
|
|
Routing - Erosion and Sediment | 8/1/2017 | | 8/8/2017 | | PASS |
Andy J. Long
|
|
|
No review required. No ESC permit required due to no exterior work or buildign sq. ft. addition.
|
Routing - FIRE | 8/1/2017 | 8/1/2017 | 8/7/2017 | | PASS |
Scott Arellano
|
|
|
Attached comments to plans.
|
Routing - MECHANICAL | 8/1/2017 | | 8/2/2017 | | PASS |
Troy James
|
|
|
|
Routing - PLUMBING | 8/1/2017 | | 8/2/2017 | | PASS |
Daryl Spivey
|
|
|
1) All plumbing to be installed by licensed plumbing contractor including setting plumbing fixtures.
2) Install DCVA on water service in basement instead of RPBP.
|
Routing - Addressing | 8/1/2017 | | 8/2/2017 | | PASS |
Doug Chausow
|
|
|
|
Routing - PUBLIC WORKS | 8/1/2017 | | 8/2/2017 | | PASS |
Rachael Beierle
|
|
|
|
Intake Approval | | | 8/1/2017 | | FAIL |
Julie Romig
|
|
|
The Form 304 uploaded is blank. Please upload the document again.
Once the Form 304 is uploaded, I can accept the application without the Suez fire flow letter (this is needed regardless of sprinklers). When you have the letter, email the plan reviewer assigned to the project and they will upload it to the case.
|
Plan Reviewer's activity | | | 8/1/2017 | | DONE |
|
|
|
Applicant waiting for Suez water flow letter. Will email plan reviewer when letter is received.
|
Plan Modification Accepted | | | 8/1/2017 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
Lindsay, Please make sure that you reach out to ACHD for review on this change of use/occupancy. If additional fees are due they will need to be paid or paid when the permit is issued. If no fees are do please submit the documentation from ACDH as such.
Thank you
Adele Schaffeld-Griffin
Assistant Building Official
Planning & Development Services Department
City of Boise - 150 N. Capitol Blvd.
P.O. Box 500
Boise, ID 83701
Office ###-####
Email – aschaffeldgriffin@cityofboise.org
“Building Boise Together.”
|
Intake Approval | | | 8/1/2017 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
Julie accepted pre screen
|
Intake Approval | | | 7/26/2017 | | FAIL |
Julie Romig
|
|
|
Need
1. Site specific fire flow at hydrants letter - indicated on checklist but not uploaded.
2. Interior lighting compliance COMcheck.
3. Mechanical COMcheck for new mechanical units.
4. Rotate Mechanical and Plumbing sheets to horizontal.
5. Provide hardware schedule/description for existing front exit door.
6. Form 304 Registered Design Professional should be for the design professional in responsible charge of the project, Lindsay Erb.
|
Application received | | | 7/25/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 25 2017 1:01PM
|