Permit Information
Permit NumberBLD17-02865
StatusFinaled
Name ANDERSEN CONSTRUCTION COMPANY IDAHO
Site Address 1055 N CURTIS RD
Project NameSt Als - Communication Room
Customer Number 
ePlanReviewYes
Description
(ST. ALPHONSUS HOSPITAL – COMMUNICATION ROOM – 2ND STORY – SOUTH TOWER) The fire sprinkler system is used for high-rise and for occupancy. To remodel a 162 square foot room located on the 2nd story of the South Tower to be used as a telecommunications room with low voltage infrastructure and racking. Work shown on the drawings but NOT associated with the 2nd story work is NOT covered under this permit. Work is to include extending an existing stud wall to the underside of the floor deck above to create a fire-resistance-rated separation, to install fire-retardant-treated plywood backing panels on existing walls, and to install a new door and frame with access control in an existing I-2 rated corridor enclosure. Equipment racks, UPS units, cable trays, and fan coil cooling units will be installed within the room. A dry-type transformer will be installed in an adjacent mechanical room. A new 2,250 pound condensing unit will be installed on the adjacent roof of the 1st story. The existing floors and roof are not allowed to be overstressed beyond the limits of the 2012 IBC. The work is required to comply with the approved drawings, with the structural analysis, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice 3/24/20184/3/2018 DONE
This permit finaled on the web by Andrew Stewart
First Notice 3/3/20183/14/2018 DONE
Mailed 3-15-18
Permanent Occupancy UNPAID FEE  2/21/2018 DONE
BLD-Final2/20/20182/20/20182/20/2018PPASS
DetailsMike Jordan
If you could meet me in the Andersen offices. Call ahead, so I can be there.
Thanks! Phone #: ###-#### Inspection requested via web by Andrew Stewart
FIRE-Final Inspection2/15/20182/15/20182/15/2018PPASS
DetailsTroy Cobbley
Life safety passed

Andrew Phone #: ###-####
Issue PAID IN FULL permit  1/25/2018 DONE
Print Occupancy Form  1/25/2018 DONE
Expiration Notice1/18/20182/8/20181/18/2018 DONE
DetailsBrittany Hill
Permit Ready to Issue  1/3/2018 DONE
Need:
GC Form
Revised Cert of Value
Plan assigned to (CJW)10/6/201710/6/20171/2/2018 PASS
DetailsCarl Westfall
(2nd done) (Oct 26 - 15 days) (27 sheets) St Als Communication Room
Routing - PLAN CHECK1/2/2018 1/2/2018 PASS
DetailsCarl Westfall
Remember to upload plan review report to ePlanReview.
Plan resubmittals received  1/2/2018 DONE
PLANS/APPL TAKEN TO FRONT DESK  1/2/2018 DONE
Routing - PLAN CHECK11/30/2017 12/11/2017 FAIL
DetailsCarl Westfall
Was hoping that the last remaining issue could be resolved behind the scenes but to no avail. The workflow was routed back to the applicant in hopes that he would resolve remaining issue. What is the total weight of the UPS rack including all equipment and batteries? Evaluate the floor capacity to determine if the floor can support the added load. Design structural upgrades if needed.
Plan resubmittals requested  12/11/2017 DONE
Was hoping that the last remaining issue could be resolved behind the scenes but to no avail. The workflow was routed back to the applicant in hopes that he would resolve remaining issue.
Plan resubmittals received  11/30/2017 DONE
Routing - PLAN CHECK11/16/2017 11/17/2017 FAIL
DetailsCarl Westfall
Need more information. See the 2nd IBC plan review report.
Plan resubmittals requested  11/17/2017 DONE
Plan resubmittals received  11/16/2017 DONE
Route to Impact Fee Review11/4/201711/7/201711/6/2017 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
1st review completed  11/4/2017 DONE
Plan resubmittals requested  11/4/2017 DONE
Routing - PLAN CHECK10/6/2017 11/4/2017 FAIL
DetailsCarl Westfall
Revised drawings required
Routing - FIRE10/6/201710/6/201710/11/2017 PASS
DetailsScott Arellano
Attached review comments to case. The aggregate of the stationary battery storage systems do not exceed 50 liquid gallons of electrolyte capacity for the UPS systems.
Routing - MECHANICAL10/6/2017 10/11/2017 PASS
DetailsChad Schwendiman
Routing - Addressing10/6/2017 10/6/2017 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS10/6/2017 10/6/2017 PASS
DetailsRachael Beierle
Intake Approval  10/6/2017 PASS
DetailsAdele J Schaffeld-Griffin
Javier approved pre screen
Intake Approval  8/28/2017 FAIL
DetailsJavier Guzman
Please provide and upload the following:
• A completed #520 Checklist. Checklist can be found at our website at http://pds.cityofboise.org/media/103678/520-major-ti-submittal-checklist_7-6-16.pdf
• The checklist is not complete unless all information is filled out, all appropriate boxes are checked and all plan page numbers are listed.
• Any items on the checklist that has only one checkbox on the left column of the checklist is required. Please provide and upload a completed item listed.
Application received  8/11/2017 DONE
Application submitted via PDS Online on Aug 11 2017 12:05PM