Permit Information
Permit NumberBLD17-03299
StatusVoid/No Violation
Name Penelope Riley
Site Address 1250 S DIVISION AVE
Project NameCrunch Fitness
Customer Number 
ePlanReviewNo
Description
(CRUNCH FITNESS – EXISTING BUILDING REMODEL FOR A WHOLE BUILDING FITNESS TENANT) (DRH17-00491) (BLD17-01520) The fire sprinkler system is used for story increase, for building area increase, for fire area, and for code trade-offs. To remodel an existing 34,887 square foot building (25,779 square feet 1st story and 9,108 square feet 2nd story) for a new fitness tenant. Permit BLD17-01520 was issued to perform interior nonstructural demolition. A portion of the floor of the 2nd story will be removed. According to the Project Structural Engineer “the removed floor does not provide structural support to any remaining building elements”. Work includes compacted fill in the existing swimming pool and spa and a concrete slab on grade over the fill; new roof coverings at sloped roofs; sloped roof extensions at removed skylights; new exterior windows; concrete footings, steel columns, wood beams, and wood roof deck to support a new exterior wall and attic above the main entry; repair of finishes within the 2nd story toilet/shower rooms; new finishes for two existing single-user toilet/shower rooms accessible to the disabled on the 1st story; a single-user toilet room accessible to the disabled on the 1st story; modifications to the existing steel roof trusses to support new roof top HVAC units; millwork, and finishes. Special Inspection is required for soils, concrete, and steel (including welding of existing roof trusses). The work is required to comply with the approved drawings, with the structural design and analysis, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Meeting  2/25/2019 DONE
sent email to don informing permit is going to expire and has had the two extensions. see documents
VOIDED CHANGE STATUS  2/25/2019 DONE
void permit per Don. see documents
Meeting  2/12/2019 DONE
sent email to Don (don@kalpacific.com) informing permit is going to expire and there has already been two extensions
BLD-Conference10/4/201810/4/201810/4/2018PDONE
DetailsBob Archibald
Structure secured against entry
BLD-Conference10/2/201810/2/201810/2/2018ADONE
DetailsBob Archibald
Complaint that strucure is not secured against entry. Visual verification and email to owner has been performed by email.
Extend Review Timeline  9/5/2018 DONE
Final Approved 180 day extension per Adele. See documents
Telephone call  8/31/2018 DONE
Left message for Penelope recommending that an extension request be sent in if not ready to pick up. Number for contracting company seems to be a fax number. Stated that this would be the final extension that they would be able to have
Expiration Notice8/17/20189/10/20188/17/2018 DONE
DetailsBrittany Hill
Extend Review Timeline  3/28/2018 DONE
1st approved 180 day extension per Adele. See documents
Telephone call  3/26/2018 DONE
Spoke with Penelope recommending that an extension request be sent in if not ready to pick up the permit since it looks like the review went a bit longer
Plan assigned to (CJW)11/17/201711/17/20173/8/2018 PASS
DetailsCarl Westfall
(3rd done) (Dec 7 - 15 days) (41 sheets) Crunch Fitness
Routing Off Site - STRUCTURAL3/7/2018 3/8/2018 PASS
DetailsCarl Westfall
Dave Haugland (AHJ)
PLANS/APPL TAKEN TO FRONT DESK  3/8/2018 DONE
Permit Ready to Issue  3/8/2018 DONE
NEED
GC FORM
REVISED VALUE
Routing - PLAN CHECK3/7/2018 3/7/2018 PASS
DetailsCarl Westfall
Plan resubmittals received  3/7/2018 DONE
Plan resubmittals requested  2/26/2018 DONE
Routing Off Site - STRUCTURAL2/14/2018 2/22/2018 FAIL
DetailsCarl Westfall
Dave Haugland (AHJ)
Routing - MECHANICAL2/14/2018 2/15/2018 PASS
DetailsTroy James
Routing - PLAN CHECK2/13/2018 2/14/2018 PASS
DetailsCarl Westfall
Pending approval by structural - remember to upload the plan review report
Plan resubmittals received  2/13/2018 DONE
Route to Impact Fee Review1/6/20181/9/20181/8/2018 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
1st review completed  1/6/2018 DONE
Plan resubmittals requested  1/6/2018 DONE
Routing - PLAN CHECK11/17/2017 1/6/2018 FAIL
DetailsCarl Westfall
Routing Off Site - STRUCTURAL11/17/2017 12/3/2017 FAIL
DetailsCarl Westfall
Dave Haugland (AHJ)
Routing - FIRE11/17/201711/17/201711/21/2017 PASS
DetailsErika Akin
Attached comments to case
Routing - Erosion and Sediment11/17/2017 11/21/2017 PASS
DetailsMichael Zawacki
No ESCP needed.
Intake Approval  11/17/2017 PASS
DetailsAdele J Schaffeld-Griffin
Michael accepted pre screen, javier notified owner this would be a major TI
Routing - MECHANICAL11/17/2017 11/17/2017 FAIL
DetailsTroy James
Need mechanical ventilation analysis
Routing - PLUMBING11/17/2017 11/17/2017 PASS
DetailsBill VanDegrift
per plans and ISPC
Routing - Addressing11/17/2017 11/17/2017 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS11/17/2017 11/17/2017 PASS
DetailsMorgan Webb
NO NEW PLUMBING
Routing - Design Review11/17/2017 11/17/2017 PASS
DetailsAndrea Tuning
Intake Approval  9/18/2017 FAIL
DetailsMichael Hanson
Penelope,
Prescreen has been failed please provide the following:
1. Completed form #304
2. Design review approval required - Contact Sarah Schafer ###-####
3. U-values for new doors and windows on plans
4. Lighting compliance COMcheck incorrectly lists Jimmy Johns as project.
5. Mechanical compliance COMcheck incorrectly lists Jimmy Johns as project.
6. Heating and cooling load calculations are not provided for RTU's
7. Idaho mechanical engineer to stamp and sign mechanical sheets when new mechanical system is being installed.
8. New RTU will require gas piping. Provide design and calculations stamped and signed by Idaho mechanical engineer.
9. RTU schedule to provide gas heating capacity information and be stamped and signed by Idaho mechanical engineer.
10. Form #518 to be signed.
11. Provide structural calculations for new framing, structural details, new stair railing, new RTU locations and demonstrate existing roof can support weight of new RTU's at replacement locations.
12. Special inspection form #304 (any welding or epoxy at new structural columns) if required per structural engineer.
Thank You,
Michael Hanson
Boise City PDS plan review dept.
###-####
Application received  9/14/2017 DONE
Application submitted via PDS Online on Sep 14 2017 12:31PM