Second Notice | | 8/18/2018 | 9/7/2018 | | DONE |
|
|
|
mailed 9-10-18
|
First Notice | 8/1/2018 | 8/1/2018 | 8/8/2018 | | DONE |
Mike Jordan
|
|
|
mailed 8-10-18
|
BLD-Aging Inspection | 8/1/2018 | 8/1/2018 | 8/1/2018 | | PASS |
Mike Jordan
|
|
|
|
DOC - Permit Finaled | 8/1/2018 | 8/1/2018 | 8/1/2018 | A | PASS |
Mike Jordan
|
|
|
This portion is completed. Permit for bld. is on temp. occ.
|
PubWorks Occupancy Approval | 4/19/2018 | 4/19/2018 | 4/19/2018 | | DONE |
Tiffany Lowery
|
|
|
Engineer letter received for drainage and bonding for street lights received.
|
BLD-Aging Inspection | 3/20/2018 | 3/20/2018 | 3/20/2018 | | PASS |
Mike Jordan
|
|
|
Foundation work completed. Will final when project is completed.
|
BLD-Concrete | 11/9/2017 | 11/9/2017 | 11/9/2017 | P | DEFR |
Mike Jordan
|
|
|
Late afternoon - Ed Phone #: ###-####. Ok pending special inspection.
|
BLD-Concrete | 11/3/2017 | 11/6/2017 | 11/6/2017 | A | PART |
Brandon Shaw
|
|
|
Pour at 3 (11-3) Special inspection on site at time of pour
|
BLD-Foundation | 10/31/2017 | 11/1/2017 | 11/1/2017 | A | NR |
Mike Jordan
|
|
|
Late, pouring at 1 - Ed Phone #: ###-####. Stemwalls, work is in progress. Concrete placement has been rescheduled for tomorrow.
|
BLD-Concrete | 10/25/2017 | 10/26/2017 | 10/26/2017 | A | PART |
Mike Jordan
|
|
|
As early as possible Phone #: 2088305327 >> Inspection requested via mobile web by Ed sloan. Work in progress on south footing line and middle footing. Ok pending special inspection.
|
BLD-Foundation | 10/17/2017 | 10/17/2017 | 10/17/2017 | P | PART |
Jim Storey
|
|
|
pouring at 3pm- Greg Phone #: ###-#### north 1/2 si on site
|
Issue PAID IN FULL permit | | | 10/16/2017 | | DONE |
|
|
|
|
Plan assigned to (CJW) | 9/26/2017 | 9/26/2017 | 10/13/2017 | | PASS |
Carl Westfall
|
|
|
(2nd done) (Oct 6 - 10 days) Sloan foundation
|
Routing Off Site - STRUCTURAL | 10/10/2017 | | 10/13/2017 | | PASS |
Carl Westfall
|
|
|
Jan Welch (Stapely)
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/13/2017 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/13/2017 | | DONE |
|
|
|
all met NEED
GC-met
Rev Cert of Val-met
|
Plan resubmittals received | | | 10/10/2017 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 10/10/2017 | | 10/10/2017 | | PASS |
Carl Westfall
|
|
|
|
Plan resubmittals requested | | | 10/4/2017 | | DONE |
|
|
|
|
Routing PW Sewer Design | 9/26/2017 | | 10/3/2017 | | PASS |
Kyle S. Rosenmeyer
|
|
|
|
Routing - FIRE | 9/26/2017 | 9/26/2017 | 10/2/2017 | | PASS |
Scott Arellano
|
|
|
Plans reviewed under BLD17-02932
|
Routing Off Site - STRUCTURAL | 9/26/2017 | | 9/29/2017 | | FAIL |
Carl Westfall
|
|
|
Jan Welch (Stapely)
|
Routing - PLAN CHECK | 9/26/2017 | | 9/29/2017 | | PASS |
Carl Westfall
|
|
|
Pending approval by structural
|
Routing - PLUMBING | 9/26/2017 | | 9/28/2017 | | PASS |
Bill VanDegrift
|
|
|
schedule 40 sewer
|
Routing PW Environmental | 9/26/2017 | | 9/28/2017 | | |
Rick Christenson
|
|
|
No review required
|
Routing PW Solid Waste | 9/26/2017 | | 9/27/2017 | | FAIL |
Evan Carpenter
|
|
|
Enclosure gates must be shown on the plans; enclosure needs to face north to ensure the requirement of 50 feet of clearance in front of enclosure is met
|
Routing PW Street Lights | 9/26/2017 | | 9/27/2017 | | PASS |
Tom Marshall
|
|
|
A 30 foot light pole with a Class B LED on the west side of the driveway entrance facing towards Melrose St. A meter cabinet is required to power this light. Need a street light plan.
|
Routing - Design Review | 9/26/2017 | | 9/27/2017 | | PASS |
Katelyn Menuge
|
|
|
|
Routing - Erosion and Sediment | 9/26/2017 | | 9/27/2017 | | PASS |
Andy J. Long
|
|
|
ESC permit for project already issued with GRD permit. See ESC17-01077. No duplicate ESC permit required.
|
Intake Approval | | | 9/26/2017 | | PASS |
|
|
|
|
Routing PW Drainage | 9/26/2017 | | 9/26/2017 | | PASS |
Brian Murphy
|
|
|
|
Routing PW Sewer Rating | 9/26/2017 | | 9/26/2017 | | PASS |
Morgan Webb
|
|
|
|
Routing - PLANNING | 9/26/2017 | | 9/26/2017 | | PASS |
Nicolette Womack
|
|
|
|
Routing - Addressing | 9/26/2017 | | 9/26/2017 | | PASS |
Doug Chausow
|
|
|
|
Routing - PUBLIC WORKS | 9/26/2017 | | 9/26/2017 | | PASS |
Rachael Beierle
|
|
|
|
Plan Reviewer's activity | | | 9/25/2017 | | PASS |
|
|
|
Plan intake approved
|
Intake Approval | | | 9/21/2017 | | FAIL |
|
|
|
(9-21-17) Please see the circled items in the plan intake checklist. Please resolve each item as directed. Please call me at ###-#### if you have questions.
|
Application received | | | 9/18/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 18 2017 2:21PM
|