DOC - Permit Finaled | | | 11/12/2019 | | DONE |
|
|
|
Per BLD Final Inspection on 9/4/19
|
BLD-Final | 9/4/2019 | 9/4/2019 | 9/4/2019 | P | DONE |
Tony Young
|
|
|
Tim Phone #: ###-####
|
BLD-Final | 9/3/2019 | 9/4/2019 | 9/4/2019 | A | PASS |
Tony Young
|
|
|
Gim Phone #: ###-####
|
BLD-Blower Door Test Results | 9/4/2019 | 9/4/2019 | 9/4/2019 | P | DONE |
Tony Young
|
|
|
Tim Phone #: ###-####/// 1.6
|
BLD-Final | 9/3/2019 | 9/3/2019 | 9/3/2019 | P | NR |
Tony Young
|
|
|
Gim Phone #: ###-####
|
BLD-Final | 8/27/2019 | 8/28/2019 | 8/28/2019 | A | FAIL |
Tony Young
|
|
|
Call to meet // Tim Phone #: ###-####,, c/n posted,, guardrail openings, firewall, smoke detector, blower door test, address posted visible from Twilight, window fall protection, plans, etc
|
PubWorks Occupancy Approval | 8/21/2019 | 8/21/2019 | 8/21/2019 | | DONE |
Melissa Jannusch
|
|
|
A bond for the sites final grading and re-vegetation has been received by Public Works. Occupancy may be approved by the building department. Melissa Jannusch ###-####.
|
CHANGE STATUS TO (ISS) | | | 8/15/2019 | | DONE |
|
|
|
change to ISS- plan mod
|
OVERRIDE | | | 8/14/2019 | | |
|
|
|
|
Plan assigned to (BJM) | 7/24/2019 | 7/24/2019 | 8/14/2019 | | DONE |
Brian McGowan
|
|
|
08/05- Check for Planning Approval- Plan Modification for Landscape stairs
|
Permit Ready to Issue | | | 8/14/2019 | | DONE |
|
|
|
plan mod-please do not re issue
|
Routing - PLANNING | 7/30/2019 | | 8/12/2019 | | PASS |
Leon Letson
|
|
|
Modified Landscape stairs
|
Routing - PLAN CHECK | 7/29/2019 | | 8/9/2019 | | PASS |
Brian McGowan
|
|
|
|
Routing PW Grading-Hillside | 7/30/2019 | | 8/5/2019 | | PASS |
Melissa Jannusch
|
|
|
PLAN MOD approved.A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable must be approved by Public Works prior to scheduling a footing inspection. Please e-mail the stamped inspection approval letter to mjannusch@cityofboise.org and allow 24 hours for subgrade approval processing. Call Melissa Jannusch at ###-#### with questions.
|
Routing - FIRE | 7/30/2019 | 7/30/2019 | 7/31/2019 | | PASS |
Lee G Meredith
|
|
|
Landscape stairs modified.
No changes required. LGM
|
Routing - PUBLIC WORKS | 7/30/2019 | | 7/30/2019 | | PASS |
Morgan Webb
|
|
|
Grading and Drainage
|
Plan assigned to (CJW) | 7/24/2019 | 7/24/2019 | 7/24/2019 | | DEFR |
Carl Westfall
|
|
|
|
Plan Modification Accepted | | | 7/24/2019 | | DONE |
|
|
|
plan mod-changes are to the grading plan-sheets C2.0, C1.0, C2.1-assigned to Carl W
|
BLD-Other | 6/10/2019 | 6/11/2019 | 6/11/2019 | A | DONE |
Tony Young
|
|
|
check on soffits,, not called in for inspection,, ok,, verified sheetrock
|
BLD-Other | 6/3/2019 | 6/4/2019 | 6/10/2019 | A | DEFR |
Tony Young
|
|
|
need to check on soffits,, not called in for inspection
|
BLD-Aging Inspection | 5/30/2019 | 5/30/2019 | 6/5/2019 | | PEND |
Tony Young
|
|
|
|
BLD-Energy code compliance | 1/14/2019 | 1/15/2019 | 1/15/2019 | A | PASS |
Tony Young
|
|
|
Tim Phone #: ###-####
|
BLD-Framing/Rough-in | 1/11/2019 | 1/14/2019 | 1/14/2019 | A | NR |
Tony Young
|
|
|
Tim Phone #: ###-####,, still needing plate lines sealed up
|
BLD-Framing/Rough-in | 1/11/2019 | 1/11/2019 | 1/11/2019 | P | PART |
Tony Young
|
|
|
Tim Phone #: ###-####,, need to seal plate lines,, maintain fire blocking
|
BLD-Other | 12/4/2018 | 12/5/2018 | 12/5/2018 | A | PART |
Tony Young
|
|
|
Tim Phone #: ###-####,, soffit work in progress,, ok
|
BLD-Framing/Rough-in | 12/4/2018 | 12/4/2018 | 12/4/2018 | P | PART |
Tony Young
|
|
|
Tim Phone #: ###-####,, needs fire blocking, seal plates.. nail hangers off,, ok to insulate
|
Plan Modification Accepted | | | 11/30/2018 | | DONE |
|
|
|
New manual j report
|
Routing - MECHANICAL | 11/30/2018 | | 11/30/2018 | | PASS |
Troy James
|
|
|
Resubmitted manual j report
|
BLD-Foundation | 7/26/2018 | 7/26/2018 | 7/26/2018 | P | PART |
Tony Young
|
|
|
Need a wall rebar inspection. Phone #: ###-#### Inspection requested via web by Tim Nau, ok to pour/grout walls after completing the rebar
|
BLD-Footing | 7/17/2018 | 7/18/2018 | 7/18/2018 | P | PART |
Tony Young
|
|
|
Phone #: ###-#### Inspection requested via web by Tim Nau,, garage footing
|
BLD-Footing | 7/17/2018 | 7/17/2018 | 7/17/2018 | P | PEND |
Tony Young
|
|
|
Need inspection on garage footing. MTI performed soil inspection and compaction tests. Hoping to pour at 3pm. Thanks Phone #: ###-#### Inspection requested via web by Tim Nau/// needs soils approval
|
PubWorks Subgrade Approval | 7/17/2018 | 7/17/2018 | 7/17/2018 | | DONE |
Melissa Jannusch
|
|
|
Garage Footings. A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable has been received by Public Works. Footing inspection may be scheduled with the Building Department. Melissa Jannusch ###-####.
|
BLD-Foundation | 6/15/2018 | 6/18/2018 | 6/18/2018 | A | PART |
Tony Young
|
|
|
Trying to pour at 10:15. Had inspection set up for last Friday afternoon and this may be a follow up inspection from that. Phone #: ###-#### Inspection requested via web by Tim Nau,, work in progress,, ok
|
BLD-Foundation | 6/15/2018 | 6/15/2018 | 6/15/2018 | P | PART |
Tony Young
|
|
|
Tim Phone #: ###-####,, work in progress on main house walls
|
BLD-Foundation | 6/15/2018 | 6/15/2018 | 6/15/2018 | P | CANC |
Tony Young
|
|
|
Looking for the latest inspection we can possibly get this afternoon in preparation for a Monday morning pour. Thanks Phone #: ###-#### >> Inspection requested via web by Tim Nau Inspection cancelled from web by: Tim Nau
|
BLD-Foundation | 5/18/2018 | 5/18/2018 | 5/18/2018 | P | PART |
Tony Young
|
|
|
Requesting concrete retaining wall inspection. Phone #: ###-#### Inspection requested via web by Tim Nau,, work in progress,, back retaining wall at the back of the basement,, front stairway to the house walls
|
BLD-Footing | 4/27/2018 | 4/27/2018 | 4/30/2018 | P | PART |
Tony Young
|
|
|
Mana Phone #: ###-####,, stair footings,, fcs blocks
|
BLD-Footing | 4/18/2018 | 4/19/2018 | 4/19/2018 | P | PART |
Tony Young
|
|
|
Mana Phone #: ###-####,, upper basement footings ok
|
PubWorks Subgrade Approval | 4/17/2018 | 4/17/2018 | 4/17/2018 | | DONE |
Melissa Jannusch
|
|
|
A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable has been received by Public Works. Footing inspection may be scheduled with the Building Department. Melissa Jannusch ###-####.
|
Issue PAID IN FULL permit | | | 4/4/2018 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 4/4/2018 | | DONE |
|
|
|
|
Telephone call | | | 4/3/2018 | | DONE |
|
|
|
emailed Rodney that we need the GC information before we can issue the permits
|
Extend Review Timeline | | | 3/16/2018 | | DONE |
|
|
|
1st Apporved 180 day extension per Adele. See documents
|
Telephone call | | | 3/9/2018 | | DONE |
|
|
|
Spoke with Rodney letting him know that this permit is going to expire in 12 days.and is welcome to send in for an extension.
|
Meeting | | | 3/9/2018 | | DONE |
|
|
|
Sent in letter requesting 180 day extension
|
Expiration Notice | 2/21/2018 | 3/14/2018 | 2/21/2018 | | DONE |
Brittany Hill
|
|
|
|
OVERRIDE | | | 11/28/2017 | | |
|
|
|
|
Plan assigned to (CDM) | 10/22/2017 | 10/22/2017 | 11/28/2017 | | PASS |
Carl D Madsen
|
|
|
SFD
|
Routing - Addressing | 9/21/2017 | | 11/28/2017 | | PASS |
Carl D Madsen
|
|
|
signed off per E-plan
|
Routing - PLAN CHECK | 11/28/2017 | | 11/28/2017 | | PASS |
Carl D Madsen
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/28/2017 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/28/2017 | | DONE |
|
|
|
ALL MET NEED
GC FORM (GC IS NO WHERE ON THE APPLICATION AND ARCHITECT APPLIED)
|
Routing - PLAN CHECK | 11/22/2017 | | 11/22/2017 | | FAIL |
Carl D Madsen
|
|
|
|
Routing - PLAN CHECK | 10/31/2017 | | 11/16/2017 | | FAIL |
Carl D Madsen
|
|
|
|
Routing - MECHANICAL | 11/8/2017 | | 11/13/2017 | | PASS |
Troy James
|
|
|
|
Routing PW Grading-Hillside | 11/8/2017 | | 11/13/2017 | | PASS |
Melissa Jannusch
|
|
|
A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable must be approved by Public Works prior to scheduling a footing inspection. Please allow 24 hours for subgrade approval processing. Call Melissa Jannusch at ###-####
Prior to obtaining a final for the permit, the roof storm drainage system must be inspected by Public Works. Call Melissa Jannusch at ###-####.
|
Routing - PUBLIC WORKS | 11/8/2017 | | 11/8/2017 | | PASS |
Rachael Beierle
|
|
|
|
Routing PW Grading-Hillside | 11/2/2017 | | 11/2/2017 | | FAIL |
Melissa Jannusch
|
|
|
Need to upload revised plans
|
Routing - PUBLIC WORKS | 10/31/2017 | | 11/2/2017 | | PASS |
Rachael Beierle
|
|
|
|
Routing - PLANNING | 9/21/2017 | | 11/1/2017 | | PASS |
Leon Letson
|
|
|
|
Routing - MECHANICAL | 10/31/2017 | | 10/31/2017 | | FAIL |
Troy James
|
|
|
Corrections have not been made to the manual j report
|
Plan assigned to (BJM) | 9/21/2017 | 9/21/2017 | 10/22/2017 | | DEFR |
Brian McGowan
|
|
|
10/11 sfd L2 ePlan
|
Routing - PLAN CHECK | 9/21/2017 | | 10/22/2017 | | FAIL |
Carl D Madsen
|
|
|
|
1st review completed | | | 10/22/2017 | | FAIL |
|
|
|
|
Routing PW Grading-Hillside | 9/21/2017 | | 9/27/2017 | | FAIL |
Melissa Jannusch
|
|
|
See changemarks in ePlan
|
Routing - Erosion and Sediment | 9/21/2017 | | 9/27/2017 | | PASS |
Andy J. Long
|
|
|
ESC plan approved. Valid stormwater & ESC team designated. Site preparation inspection required prior to excavation.
|
Routing - FIRE | 9/26/2017 | 9/26/2017 | 9/26/2017 | | PASS |
Scott Arellano
|
|
|
Updated plan review report.
|
Routing - FIRE | 9/21/2017 | 9/21/2017 | 9/26/2017 | | FAIL |
Scott Arellano
|
|
|
Attached plan review report to case. Emailed report to applicant.
|
Routing - MECHANICAL | 9/21/2017 | | 9/26/2017 | | FAIL |
Troy James
|
|
|
emailed corrections to building energy
|
Route to Impact Fee Review | 9/21/2017 | 9/24/2017 | 9/22/2017 | | PASS |
Eric Bilimoria
|
|
|
Initial residential review of new SFD permits requested for now.
|
Routing - PUBLIC WORKS | 9/21/2017 | | 9/22/2017 | | PASS |
Rachael Beierle
|
|
|
|
Application received | | | 9/21/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 21 2017 12:04PM
|
Plans ACCEPTED BY PLAN TECH | | | 9/21/2017 | | DONE |
|
|
|
|
Intake Approval | | | 9/21/2017 | | PASS |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 9/21/2017 | | DONE |
|
|
|
|