Permit Information
Permit NumberBLD17-03441
StatusIssued
Name BAINBRIDGE ENGINEERED SOLUTIONS & T
Site Address 7500 W MOSSY CUP ST
Project NameNxEdge - Equipment Enclosure
Customer Number 
ePlanReviewYes
Description
(NXEDGE – EQUIPMENT ENCLOSURE) The fire sprinkler system is used for building area increase, for story increase, to allow the H-3 Occupancy, and for fire area. Permit to construct a new 900 sq. ft. semi-heated attached pre-engineered metal building addition on the east side of the existing building. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select equipment for new structure, the construction of a new manufactured steel building, new unit heater, new light fixtures, electrical work, plumbing work and mechanical work. Note: special inspection required see attached form #310. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection2/22/20182/23/20182/23/2018APASS
DetailsTroy Cobbley
life safety passed

tim Phone #: ###-####
BLD-Final2/20/20182/20/20182/20/2018PNR
DetailsJim Sly
Tim Phone #: ###-####
As an observation......Need fire/life final and noticed landing for 36 inch door needed.
BLD-Foundation12/6/201712/7/201712/7/2017APASS
DetailsMike Jordan
(mud at 9) Zach Phone #: ###-####
Issue PAID IN FULL permit  11/9/2017 DONE
Inspection Record Card- Bld  11/9/2017 DONE
OVERRIDE  11/8/2017  
Plan assigned to (JG)10/6/201710/6/201711/8/2017 PASS
DetailsJavier Guzman
1st rev comp, 10/26 NxEdge Addition ePlan pend eng
Routing Off Site - STRUCTURAL11/2/2017 11/8/2017 PASS
DetailsJavier Guzman
signe off in ePlan by AHJ Engineers Chris Holladay
PLANS/APPL TAKEN TO FRONT DESK  11/8/2017 DONE
Permit Ready to Issue  11/8/2017 DONE
NEED
GC -Met
RP -Met
Rev Cert of Val- Met
Routing - PLAN CHECK11/2/2017 11/4/2017 PASS
DetailsJavier Guzman
Route to Impact Fee Review10/27/201710/30/201710/27/2017 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
Routing - PLAN CHECK10/6/2017 10/27/2017 PASS
DetailsJavier Guzman
1st review completed  10/27/2017 FAIL
DetailsJavier Guzman
Routing Off Site - STRUCTURAL10/6/2017 10/26/2017 FAIL
DetailsJavier Guzman
Failed in ePlan by AHJ Engineers Chris Holladay
Routing - FIRE10/6/201710/6/201710/16/2017 PASS
DetailsScott Arellano
Attached review comments to case
Routing - MECHANICAL10/6/2017 10/12/2017 PASS
DetailsTroy James
No mechanical plans
Routing - Erosion and Sediment10/6/2017 10/11/2017 PASS
DetailsAndy J. Long
ESC plan waiver approved. RP to be designated.
Routing PW Environmental10/6/2017 10/11/2017 PASS
DetailsRick Christenson
Routing - PLUMBING10/6/2017 10/9/2017 PASS
DetailsBill VanDegrift
No plumbing review required.
Intake Approval  10/6/2017 PASS
Routing PW Drainage10/6/2017 10/6/2017 PASS
DetailsBrian Murphy
less than 1000 sq ft
Routing - PLANNING10/6/2017 10/6/2017 PASS
DetailsKatelyn Menuge
Approved by Design Review
Routing - Addressing10/6/2017 10/6/2017 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS10/6/2017 10/6/2017 PASS
DetailsRachael Beierle
Routing - Design Review10/6/2017 10/6/2017 PASS
DetailsKatelyn Menuge
CZC17-00225
Intake Approval  10/3/2017 FAIL
Please provide the owners signature on the special inspection form 310
All plan sheets are required to be a minimum 18 x 24 with the required city stamping area in the lower right hand corner of the sheet. Please review the submittal standard for the size and location of the stamping area.
Upload any required planning and zoning approval letters.
Indicate the type of heating to be installed and provide a heating equipment schedule.
Please provide an ESC plan or a plan waiver request letter.
Provide a grading and drainage plan or documentation that it is not required from public works.
Application received  9/25/2017 DONE
Application submitted via PDS Online on Sep 25 2017 3:53PM