Print Statement | | | 12/21/2017 | | DONE |
|
|
|
|
First Notice | | 12/9/2017 | 12/12/2017 | | DONE |
|
|
|
Mailed 12-13-17
|
Permanent Occupancy | | | 11/29/2017 | | DONE |
|
|
|
|
BLD-Final | 11/27/2017 | 11/28/2017 | 11/28/2017 | P | PASS |
Dave Hannah
|
|
|
Marva Phone #: ###-####
|
FIRE-Final Inspection | 11/27/2017 | 11/28/2017 | 11/28/2017 | A | PASS |
Jim Page
|
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection for area of work passed/complete.
|
Plan assigned to (JG) | 11/7/2017 | 11/7/2017 | 11/17/2017 | | PASS |
Javier Guzman
|
|
|
11/13 L1 NYK Line TI Suite 430 ePlan*
|
Routing - PLAN CHECK | 11/7/2017 | | 11/17/2017 | | PASS |
Javier Guzman
|
|
|
|
1st review completed | | | 11/17/2017 | | DONE |
Javier Guzman
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/17/2017 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/17/2017 | | DONE |
|
|
|
NEED
GC FORM - met
REVISED CERT - met
|
Issue PAID IN FULL permit | | | 11/17/2017 | | DONE |
|
|
|
|
Print Occupancy Form | | | 11/17/2017 | | DONE |
|
|
|
|
Routing - Addressing | 11/7/2017 | | 11/8/2017 | | PASS |
Doug Chausow
|
|
|
Suite 430
|
Routing - PUBLIC WORKS | 11/7/2017 | | 11/8/2017 | | PASS |
Morgan Webb
|
|
|
NO NEW FEES. CREDIT FOR DEMO
|
Intake Approval | | | 11/7/2017 | | PASS |
Javier Guzman
|
|
|
|
Intake Approval | | | 11/6/2017 | | FAIL |
Michael Hanson
|
|
|
Provide individually uploaded sheets.
|
Intake Approval | | | 10/30/2017 | | FAIL |
Michael Hanson
|
|
|
Gary,
This permit application has failed prescreen due to the following:
1. Construction documents do not meet he minimum drawings size of 18" x 24"
2. Missing demo plan showing current locations of walls and doors to be relocated / removed.
3. Dimensioned finished floor plan
4. Elevations of coffee bar area denoting counter and sink heights
5. Exit sign and emergency lighting locations
6. Portable fire extinguisher locations
7. Lighting information. If "no change" then add note on the drawings.
Please upload the missing information for this application to proceed.
Thank You,
Michael Hanson
Boise City
###-####
|
Application received | | | 10/27/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 27 2017 2:49PM
|