Permit NumberBLD17-04285
StatusIssued
Name ST LUKES HEALTH SYSTEM LTD
Site Address 2619 W FAIRVIEW AVE
Project NameSt. Luke's - Phase I
Customer NumberBLD18-01027
ePlanReviewYes
Description
(ST. LUKE’S – 27TH STREET DEVELOPMENT – HOSPITAL AND MEDICAL OFFICE BUILDING – CONCRETE AND STRUCTURAL STEEL PHASE) (DRH17-00427) (CUP17-00057) The fire sprinkler system is used for occupancy. To construct the concrete and structural steel phase (Package I) for a new 4 story hospital and medical office building (3 story hospital portion and 4 story medical office portion) having a total floor area of about 229,500 square feet. The shell and tenant improvement phase (Package II) will be under a separate permit (BLD18-01027). Work is to include concrete spread footings, concrete continuous footings, concrete mat footings, concrete piers, concrete foundation walls including mechanical pits and elevator pits, concrete slabs on grade including mechanical pits and elevator pits, steel columns, steel base plates, steel girders, steel beams, concrete filled steel floor decks, steel roof decks, steel braced frames, steel moment frames, and steel stairways with steel pan concrete filled treads. Other drawings that show work beyond this phase are not approved and are for reference only. The several land parcels are required to be consolidated before this permit is issued. Special Inspection is required for soils, concrete, steel including welding and bolting, masonry, wind resistance, seismic resistance, and the application of fire-resistance coatings. This permit is not intended to establish a Certificate of Occupancy for any portion of this building. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system and the fire alarm system will be installed in conjunction with a future phase permit. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection2/19/20202/19/20202/19/2020 PASS
DetailsDave Hannah
BLD-Concrete10/8/201910/8/201910/8/2019PPASS
DetailsDave Hannah
rebar // Ken Phone #: ###-####
BLD-Foundation10/7/201910/7/201910/8/2019PPEND
DetailsDave Hannah
rebar // Ken Phone #: ###-####
BLD-Concrete8/16/20198/19/20198/27/2019APASS
DetailsDave Hannah
Ken- Rebar inspection Phone #: ###-####
BLD-Concrete8/8/20198/8/20198/8/2019PDONE
DetailsDave Hannah
ken Phone #: ###-####
BLD-Foundation7/16/20197/16/20197/18/2019PPASS
DetailsDave Hannah
Ken Phone #: ###-####
BLD-Footing7/11/20197/11/20197/11/2019PPASS
DetailsMike Jordan
slab on deck // Ken Phone #: ###-####
BLD-Foundation4/30/20194/30/20194/30/2019PPEND
DetailsDave Hannah
Ken-slab on deck Phone #: ###-#### ok after spec inspection
BLD-Foundation4/23/20194/24/20194/25/2019PPART
DetailsDave Hannah
Ken-concrete rebar Phone #: ###-#### second pour of second floor ok
BLD-Concrete4/17/20194/18/20194/19/2019APART
DetailsBrandon Shaw
structural slab on deck...
Special Instion was on site at time of pour, pending report...
BLD-Foundation1/23/20191/23/20191/23/2019PPEND
DetailsBrandon Shaw
rebar- ok after spec inspection sign offs...
BLD-Foundation12/19/201812/20/201812/20/2018PPEND
DetailsDave Hannah
Ken Phone #: ###-#### ok after spec inspection sign offs
BLD-Foundation12/6/201812/6/201812/6/2018PPART
DetailsDave Hannah
rebar- Ken Phone #: ###-#### ok after al oks
BLD-Concrete12/3/201812/3/201812/5/2018PPASS
DetailsDave Hannah
Ken Phone #: ###-####
BLD-Concrete12/4/201812/4/201812/4/2018APASS
DetailsDave Hannah
Ken Phone #: ###-####
BLD-Foundation11/27/201811/27/201811/27/2018PPEND
DetailsDave Hannah
Ken-foundation reinforcing Phone #: ###-#### ok after spec inspection
BLD-Foundation11/19/201811/20/201811/20/2018APASS
DetailsDave Hannah
rebar // Justin Phone #: ###-#### meet with al and walked project
Extend Permit 90/180 days11/20/201811/20/201811/20/2018PCANC
DetailsDave Hannah
rebar // Justin Phone #: ###-####
Issue PAID IN FULL permit  9/12/2018 DONE
Inspection Record Card- Bld  9/12/2018 DONE
Plan assigned to (CJW)12/1/201712/1/20179/10/2018 PASS
DetailsCarl Westfall
(3rd done) 12/14/17 (new - 14 days) (ePlan - 108 sheets then increased to 153 sheets) St. Lukes Orthopedic
Routing - PLUMBING9/4/2018 9/10/2018 PASS
DetailsDan Ediger
See red line corrections
PLANS/APPL TAKEN TO FRONT DESK  9/10/2018 DONE
Permit Ready to Issue  9/10/2018 DONE
MET
Routing - PUBLIC WORKS9/4/2018 9/4/2018 PASS
DetailsRachael Beierle
Routing - PLANNING9/4/2018 9/4/2018 PASS
DetailsCody Riddle
Routing - Design Review9/4/2018 9/4/2018 PASS
DetailsAndrea Tuning
Routing - PLAN CHECK8/31/2018 9/4/2018 PASS
DetailsCarl Westfall
Routing PW Drainage9/4/2018 9/4/2018 PASS
DetailsBrian Murphy
Brian needs to add his approval stamp to the most recent drawing
Plan resubmittals received  8/31/2018 DONE
Routing PW Sewer Design3/24/2018 4/3/2018 PASS
DetailsMike Sheppard
Plan resubmittals requested  4/3/2018 DONE
Routing Off Site - STRUCTURAL3/24/2018 4/2/2018 PASS
DetailsCarl Westfall
Jared Bauder (CH2MHill)
Routing - FIRE3/24/20183/30/20183/29/2018 PASS
DetailsScott Arellano
3/30 St. Lukes Ortho Structural Resubmittal Eplan
Routing - PLANNING3/24/2018 3/28/2018 FAIL
DetailsCody Riddle
The record of survey has not been completed and the required easement provided (site specific conditions 2 and 3 from CUP approval).
Routing PW Solid Waste3/24/2018 3/27/2018 PASS
DetailsEvan Carpenter
The solid waste enclosure location is approved as shown.
Routing - Design Review3/24/2018 3/26/2018 FAIL
DetailsAndrea Tuning
Prior to issuance of building permits, a record of survey for a parcel consolidation shall be completed to demonstrate compliance with building code requirements for any construction over or adjacent to property lines.

Stripe the parking stall adjacent to 27th Street to be 20-feet in depth or identify these spaces as compact spaces.

Reduce the proposed screen wall located around the loading area to meet the 10-foot building setback.

Install a minimum of 41 accessible parking stalls on the site.

Provide a minimum of 47 bicycle parking spaces with a minimum of 24 of the bicycle spaces being covered.
for the parking structure.

Obtain a license agreement for landscaping located within the public right-of-way.

Construct the screen wall adjacent to the loading area as a 4-foot tall CMU base with the metal railing extending between the 6-foot columns the additional 2-feet.

Provide additional transparency within the fencing along Fairview Avenue.

Locate all pole lights to be outside of the required setbacks and outside of any required landscape planters.
Routing PW Drainage3/24/2018 3/26/2018 PASS
DetailsBrian Murphy
Routing - PLAN CHECK3/23/2018 3/24/2018 PASS
DetailsCarl Westfall
Pass pending structural
Plan resubmittals received  3/23/2018 DONE
DetailsCarl Westfall
Route to Impact Fee Review1/13/20181/16/20181/16/2018 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
1st review completed  1/13/2018 DONE
Plan resubmittals requested  1/13/2018 DONE
Routing - PLAN CHECK12/1/2017 1/13/2018 PASS
DetailsCarl Westfall
Routing Off Site - STRUCTURAL12/1/2017 12/18/2017 FAIL
DetailsCarl Westfall
Jared Bauder (CH2M Hill)
Routing - FIRE12/1/201712/1/201712/8/2017 FAIL
DetailsScott Arellano
Emailed report to architect. Attached report to case.
Routing PW Drainage12/8/2017 12/8/2017 FAIL
HOLD PERMIT
Routing PW Sewer Design12/1/2017 12/8/2017 FAIL
DetailsMike Sheppard
Coordinate with Boise City Public Works for sewer service.
Routing PW Solid Waste12/1/2017 12/8/2017 FAIL
DetailsEvan Carpenter
The solid waste enclosure gates must have at least 12 feet of unobstructed clearance between gate posts for each enclosure. Current bollard placement restricts this clearance to less than 10 feet for each enclosure gate.
Routing - Erosion and Sediment12/1/2017 12/8/2017 PASS
DetailsMichael Zawacki
Dewatering stated in SWPPP. Plan will need to be reviewed and approved before any dewatering activity begins.
Routing PW Drainage12/1/2017 12/6/2017 PASS
DetailsBrian Murphy
Routing PW Environmental12/1/2017 12/5/2017 PASS
DetailsRick Christenson
Routing PW Street Lights12/1/2017 12/4/2017 PASS
DetailsTom Marshall
Routing - Addressing12/1/2017 12/1/2017 PASS
DetailsDoug Chausow
Intake Approval  12/1/2017 PASS
Routing - PLANNING12/1/2017 12/1/2017 FAIL
DetailsCody Riddle
Site specific conditions 2 and 3 require an access easement and record of survey be complete prior to issuance. Emailed applicant requesting additional information.
Routing - PUBLIC WORKS12/1/2017 12/1/2017 PASS
DetailsRachael Beierle
STEEL AND CONCRETE PHASE ONLY. NO IMPACT FEES ASSESSED UNTIL TI PHASE.
Routing - Design Review12/1/2017 12/1/2017 FAIL
DetailsAndrea Tuning
Prior to issuance of building permits, a record of survey for a parcel consolidation shall be completed to demonstrate compliance with building code requirements for any construction over or adjacent to property lines.

Stripe the parking stall adjacent to 27th Street to be 20-feet in depth or identify these spaces as compact spaces.

Reduce the proposed screen wall located around the loading area to meet the 10-foot building setback.

Install a minimum of 41 accessible parking stalls on the site.

Provide a minimum of 47 bicycle parking spaces with a minimum of 24 of the bicycle spaces being covered.
for the parking structure.

Obtain a license agreement for landscaping located within the public right-of-way.

Construct the screen wall adjacent to the loading area as a 4-foot tall CMU base with the metal railing extending between the 6-foot columns the additional 2-feet.

Provide additional transparency within the fencing along Fairview Avenue.

Locate all pole lights to be outside of the required setbacks and outside of any required landscape planters.
Intake Approval  11/24/2017 FAIL
Please provide the owners signature on form 310.
Application received  11/21/2017 DONE
Application submitted via PDS Online on Nov 21 2017 5:06PM