Permit Information
Permit NumberBLD17-04370
StatusIssued
Name CARLSON MATERIAL HANDLING
Site Address 2929 S COLE RD Unit: STE 110
Project NameSentry - Suite #110 - Racking
Customer Number 
ePlanReviewNo
Description
(SENTRY – SUITE #110 – **RACKING**) Permit to install steel storage racking exceeding 8' in height within the warehouse space per approved plans and structural engineering. Tenant improvement work was done under permit BLD17-01358. Approval of this permit is contingent on adhering to approved plans and engineering. Work to include: installation of prefabricated 12-foot storage racking, including seismic bolting to existing slab, the design, testing and utilization of industrial steel storage racks shall be in accordance with the RMI Specification for the Design, Testing and Utilization of Industrial Steel Storage Racks. The structural design by Structural Seizmic Inc. Engineering is attached. Note: Special inspections required on the anchor bolts are required per ICC/ESR – 1917. **JG**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Conference11/6/201811/7/201811/6/2018ADONE
DetailsTroy Cobbley
I stopped at the job site and let the tenant know that a sprinkler analysis will be required. After further discussion with the plan reviewer the column protection will not be required unless the storage height exceeds 15'
BLD-Other10/31/201811/5/201811/2/2018ACANC
DetailsMike Jordan
Pallet racking >> Inspection requested via web by Jeff Higgins Inspection cancelled from web by: Jeff Higgins
FIRE-Final Inspection10/31/201811/2/201811/2/2018AFAIL
DetailsTroy Cobbley
Provide revised plans showing all racking requiring permits, provide sprinkler protection of the columns in the double row racking as per NFPA 13 16.1.4

Inspection requested via web by Jeff Higgins
Issue PAID IN FULL permit  12/27/2017 DONE
Plan assigned to (JG)12/4/201712/4/201712/18/2017 PASS
DetailsJavier Guzman
L2 12/13 Sentry Racking paper, pend fire
Routing - PLAN CHECK12/15/2017 12/18/2017 PASS
DetailsJavier Guzman
1st review completed  12/18/2017 DONE
DetailsJavier Guzman
PLANS/APPL TAKEN TO FRONT DESK  12/18/2017 DONE
Permit Ready to Issue  12/18/2017 DONE
NEED
GC FORM
Inspection Record Card- Bld  12/18/2017 DONE
Telephone call  12/18/2017 DONE
called Jeff and told him permit is ready and fee due
Routing - FIRE12/15/2017 12/15/2017 PASS
DetailsScott Arellano
Plans are approved. However, this building is fully fire sprinklered and it is recommeded that the building owner have an Idaho licensed fire sprinkler contractor confirm the existing fire sprinkler system design is appropriate for the proposed new storage. Any necessary modifications will require a separate fire sprinkler permit.
Case Summary (BLD)  12/14/2017 DONE
DetailsJavier Guzman
Routing - PLAN CHECK12/4/2017 12/14/2017 PASS
DetailsJavier Guzman
Pending Assignment by CDM12/1/2017 12/4/2017 DONE
DetailsCarl D Madsen
Plans ACCEPTED BY PLAN TECH  11/30/2017 DONE
DetailsTisha Gallop
Intake Approval  11/30/2017 PASS
DetailsCarl Westfall
Recd Pcfee & Taken To Pln CK  11/30/2017 DONE
Application received 11/30/2017