Permit NumberBLD18-00429
StatusIssued
Name CORY ADAMSON
Site Address 507 N PARTRIDGE PL
Project NameLTS Motors
Customer Number 
ePlanReviewYes
Description
(LTS MOTORS) Permit for a 3,000 sq. ft. one story, pre-engineered metal building shop addition to an existing 2,890 sq. ft. pre-engineered metal building to make a total 5,890 sq. ft. repair garage building and related site improvements. Approval is contingent upon adhering to the DRH18-00178, approved plans on file and attached engineering. Work to include: Select new site work, construction of footing/foundation, concrete slab, pre-engineered metal building, metal siding, metal roofing, new door/door frames, new overhead doors, new light fixtures, electrical work and mechanical work. Note: special inspection is required, see form #310 attached. This building is Not Fire Sprinklered. **JG**
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Plan Reviewer's activity  6/26/2020 DONE
DetailsJoe Bruce
Fire Hydrant distance has been extended per email from Todd Callahan (Asst Fire Marshal). Existing fire hydrant is adequate and new fire hydrant is not required to be installed.
BLD-Framing/Rough-in5/14/20205/15/20205/15/2020APART
DetailsMike Jordan
screened // Cory Phone #: ###-####. Framing on pre engineered structure. Needs bolting inspection from 3rd. party. Also noted west set back not per plans. Needs to resubmit updated setbacks for approval. Plans show 15ft set back, addition is currently at 11ft. 1 inch. Should not affect construction of exterior wall. Also needs to send special inspection reports for footing and foundation inspections.
BLD-Conference10/22/201910/22/201910/22/2019PDONE
DetailsMike Jordan
Please call ahead for inspection/site question - Cory Phone #: ###-####
Print Occupancy Form  10/3/2019 DONE
Issue PAID IN FULL permit  9/18/2019 DONE
Print Occupancy Form  9/18/2019 DONE
OVERRIDE  8/20/2019  
Plan assigned to (JG)2/21/20192/28/20198/20/2019 PASS
DetailsJavier Guzman
3rd rev, 04/03 (6wks) - 502 LTS Motors Shop Addition ePlan
Routing - PLAN CHECK8/20/2019 8/20/2019 PASS
DetailsJavier Guzman
Routing PW Drainage8/20/2019 8/20/2019 PASS
DetailsBrian Murphy
PLANS/APPL TAKEN TO FRONT DESK  8/20/2019 DONE
Permit Ready to Issue  8/20/2019 DONE
all met-NEED
RP-met
GC FORM-met
REVISED VALUE-met
still need the RP but emailed Cory Adamson the fees that are due
CAN
Routing - FIRE7/31/20197/31/20198/13/2019 PASS
DetailsMark Scharfen
08/13-LTS Motors resubmittal review completed 08.13.2019. Uploaded rev_fire 08.13.2019.pdf.
Routing - PLAN CHECK7/31/2019 8/5/2019 PASS
DetailsJavier Guzman
Routing - FIRE7/9/20197/9/20197/15/2019 FAIL
DetailsMark Scharfen
07.15.2019-Completed review of resbumittal. Uploaded rev_fire 07.15.2019.pdf and emailed to applicant.
Routing - PLAN CHECK7/9/2019 7/12/2019 PASS
DetailsJavier Guzman
Routing - PUBLIC WORKS7/12/2019 7/12/2019 PASS
DetailsAngela Hardy
revised C1 grading plan sheet
Routing - PLUMBING7/12/2019 7/12/2019 PASS
DetailsDaryl Spivey
revised C1 grading plan sheet
Routing - MECHANICAL7/9/2019 7/10/2019 PASS
DetailsTroy James
Route to Impact Fee Review4/3/20194/6/20194/4/2019 PASS
DetailsShannon Cade
Review requested for Commercial Permit
Routing - FIRE2/21/20192/28/20194/3/2019 FAIL
DetailsMark Scharfen
IFC 1st review 04.03.2019.pdf uploaded and emailed to applicant.
Routing Off Site - STRUCTURAL2/28/2019 4/3/2019 PASS
DetailsJavier Guzman
signed off in ePlan by AHJ Engineers Dave Haugland

Routing - PLAN CHECK2/28/2019 4/3/2019 PASS
DetailsJavier Guzman
1st review completed  4/3/2019 FAIL
DetailsJavier Guzman
Routing - PLANNING2/28/2019 4/3/2019 CANC
DetailsJeff Lowe
No review required as stated in ePlan by Current Planning Jeff Lowe

Routing PW Environmental3/1/2019 3/18/2019 PASS
DetailsRick Christenson
Dry shop no drains shown
Routing PW Drainage3/1/2019 3/13/2019 PASS
DetailsBrian Murphy
Routing - MECHANICAL2/28/2019 3/4/2019 FAIL
DetailsTroy James
See Eplan
Routing - Erosion and Sediment2/28/2019 3/4/2019 PASS
DetailsMichael Zawacki
RP needed before work begins. Site prep inspection required.
Routing - Addressing2/28/2019 3/1/2019 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS2/28/2019 3/1/2019 PASS
DetailsMorgan Webb
Routing PW Street Lights3/1/2019 3/1/2019 PASS
DetailsTom Marshall
Routing PW Sewer Design3/1/2019 3/1/2019 PASS
DetailsDeAnn Brown
Routing PW Solid Waste3/1/2019 3/1/2019 PASS
DetailsEvan Carpenter
Routing - Design Review2/28/2019 2/28/2019 PASS
DetailsAndrea Tuning
Intake Approval  2/21/2019 PASS
DetailsJoe Bruce
Intake Approval  2/19/2019 FAIL
DetailsJoe Bruce
1) The metal building drawings (Sheets 1 through 25) do not have the required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” space located 3” off the right sheet edge to allow for the title block. See our ePlanReview submittal standards: https://pds.cityofboise.org/media/464072/pdox86_electronic_standards_full_050718.pdf
Intake Approval  11/30/2018 FAIL
DetailsJoe Bruce
1) Plan sheets do not have the required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” (4"x4" on cover) space located 3” off the right sheet edge to allow for the title block. Verify ALL plan sheets have the required space for city approval stamp. See our ePlanReview submittal standards: https://pds.cityofboise.org/media/464072/pdox86_electronic_standards_full_050718.pdf
2) Steel erection drawings and calculations are required to be stamped and signed by an Idaho Licensed Structural Engineer. Resubmit drawings with required stamp/signature.
3) Form #310 - Statement of Special Inspections is required for the Structural Steel since the seismic resistance coefficient R value is more than (3) three. See 2015 IBC Section 1705.12.1. Fill out the entire form #310 (with engineers stamp/signature) and include any additional sections as required by the special inspections table on page 2 of the form. Sheet "GN" lists additional special inspections in the notes.
4) The drawing index on sheet A0.0 does not list all the plan sheets submitted. List all the sheets (including the metal building drawings & fire extinguishers) in the drawing index.
5) Fire hydrants could not be located on the site plan. Please indicate the page that the fire hydrants are located on.
6) Upload ESC plans in the drawings folder. These could not be located.
7) Provide details of insulation on the building sections as noted in the checklist. The walls sections do not identify the details for insulation or specify the type of insulation to be installed. The building section on sheet A7.1 does reference the ComCheck report, however it does not match the Energy Compliance COMCheck which calls out a continuous insulation R-Value of R-10. Provide details/sections on how the continuous insulation is attached to the roof and walls.
8) Lighting Compliance (COMCheck) could not be located in the drawings or sheet EN0.1 as stated in the checklist. Provide a lighting compliance (COMCheck) certificate for the new light fixtures.
9) Provide a panel load schedule and summary for the new electrical load of the lights, heater, receptacles, and motorized overhead door.
Intake Approval  11/14/2018 FAIL
DetailsJoe Bruce
1. The "Structural calculations.pdf" and "S1.4 Structural.pdf" are not documents and should not be uploaded in the documents folder. These belong in the drawings folder and need to be individually uploaded.
2. Fire extinguisher locations is uploaded sideway. - Upload in the correct direction. Sheet has been deleted from the folder.
3. The complete set of drawings has not been uploaded individually. A majority of the drawings are missing. All sheets need to be individually uploaded and follow the electronic plan submittal standards with naming convention. "Complete Set (1).pdf" needs to have each sheet individually uploaded with a file name that lists the sheet number and sheet title. Refer to this document link: https://pds.cityofboise.org/media/464072/pdox86_electronic_standards_full_050718.pdf
4. Building Calculations Page (1) (2).pdf is upload sideways. Revise and upload the correct direction.
5. Plan sheets do not have the required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” (4"x4" on cover) space located 3” off the right sheet edge to allow for the title block. Verify ALL plan sheets have the required space for city approval stamp.
6. Documents shall be multiple pages as noted in our electronic plan submittal standards. Please upload the checklist as a multiple page PDF.
Intake Approval  10/23/2018 FAIL
DetailsJoe Bruce
Pre-screen #3 - Joe Bruce - ###-####
1. Fill out and upload checklist #502 into the documents folder. The form must be filled out completely. The items that do not apply to your project need to have the "N/A" boxed checked. Locations of all items must be noted with the location of the plans sheets. This is mandatory and must be uploaded. I could not locate the checklist in the documents folder.
2. All documents need to be uploaded in the correct direction. All documents that were uploaded upside down have been deleted. Please upload these documents in the correct direction.
3. The "Structural calculations.pdf" and "S1.4 Structural.pdf" are not documents and should not be uploaded in the documents folder. These belong in the drawings folder and need to be individually uploaded.
4. All plan sheets are required to be individually uploaded with a minimum sheet size of 18 x 24. These steel building structural drawings do not meet our minimum requirement. Revised and upload.
5. The verification of legal lot form is missing the signature from a subdivision planner. Please contact: Sue Cummings ###-#### for information on how to obtain this signature. This form was also uploaded individually and upside down. Upload the entire document as a single PDF in the documents folder. - I am deleting the individual/upside down sheets from the case.
6. Fire extinguisher locations is uploaded sideway. - Upload in the correct direction. Sheet has been deleted from the folder.
7. All sheets need to be individually uploaded and follow the electronic plan submittal standards with naming convention. "Complete Set (1).pdf" needs to have each sheet individually uploaded with a file name that lists the sheet number and sheet title. Refer to this document link: https://pds.cityofboise.org/media/464072/pdox86_electronic_standards_full_050718.pdf
Intake Approval  8/24/2018 FAIL
DetailsJoe Bruce
This prescreen has failed due to the following:
1.Fill out and upload form #520 into the documents folder.
2.Structural calculations need to be stamped and signed by an Idaho licensed engineer.
3.All “A-sheets” need to be individually uploaded and follow the electronic plan submittal standards with naming convention.
4.Provide verification of Legal Lot or Parcel form signed and approved by PDS Subdivision Staff.
5.Provide site specific fire flow at hydrants letter from Suez Water or other public water provider.
6.Provide and ESC Plan designed for the specific project, and be prepared and signed by a plan designer certified by Boise City.
7.Provide foundation plan & details stamped and signed by an Idaho licensed engineer.
8.Provide electrical plans stamped and signed by and Idaho licensed engineer with required items on checklist.
Intake Approval  8/23/2018 FAIL
Application received  2/7/2018 DONE
Application submitted via PDS Online on Feb 7 2018 11:27AM
Routing PW Drainage7/12/2019   FAIL
DetailsBrian Murphy
revised C1 grading plan sheet/ keynote 2 is wrong
Routing PW Drainage7/31/2019   FAIL
DetailsBrian Murphy
OLD PLAN NOTE 2