Permit Information
Permit NumberBLD18-02067
StatusUnder Review
Name LODGE AT CREEK BEND LLC
Site Address 1140 S COLORADO AVE
Project NameCreek Bend Apartments
Customer Number 
ePlanReviewYes
Description
(CREEK BEND APARTMENTS – NEW ENTRANCE VESTIBULES AND CANOPIES) (DRH18-00200) (3-4-19 PLAN MODIFICATION TO MAKE STRUCTURAL REVISIONS TO THE PREVIOUSLY APPROVED DRAWINGS FOR THE LOBBY AND OFFICE REMODEL. EVIDENTLY THE EXISTING STRUCTURAL CONDITION IS DIFFERENT THAN WHAT WAS ORIGINALLY ANTICIPATED. PREVIOUSLY PROPOSED FOOTINGS, COLUMNS, AND BEAM WILL NOT BE CONSTRUCTED SINCE THE EXISTING STRUCTURE IS SUFFICIENT. THE NEW STAIRWAY AND ITS SUPPORT IS REQUIRED TO COMPLY WITH THE STRUCTURAL DESIGN THAT WAS PART OF THE PLAN MODIFICATION APPROVED EARLIER.) (12-24-18 PLAN MODIFICATION TO INSTALL A NEW STEEL STAIRWAY WITHIN THE COMMON AREA IN AN EXISTING 2 STORY RESIDENTIAL APARTMENT BUILDING TO REPLACE AN EXISTING WOOD STAIRWAY. WORK IS TO INCLUDE STEEL STRINGERS, ATTACHMENTS TO EXISTING STRUCTURAL ELEMENTS, WOOD TREADS, GUARDS, AND HANDRAILS. ALL NEW WORK IS REQUIRED TO COMPLY WITH THE CURRENT CODES AND STANDARDS AND THE STRUCTURAL DESIGN. REFER TO THE CODE SECTIONS LISTED IN THE PLAN REVIEW REPORT. SPECIAL INSPECTION IS REQUIRED FOR WELDING.) This building does not have a fire sprinkler system. This building has a total existing floor area of about 44,800 square feet (21,500 square feet 1st story and 23,300 square feet 2nd story). The existing 800 square foot drive through canopy at the main entrance will be demolished. The two existing 2-hr fire-resistance-rated fire walls are required to be maintained. To construct a new 107 square foot entry vestibule with a 17 foot tall ceiling. The vestibule will be surrounded on three sides by a 449 square foot lower canopy and a 136 square foot upper canopy. Work is to include concrete continuous footings, concrete spot footings, concrete piers, concrete stem walls, a concrete slab on grade, an exterior concrete stairway, an exterior concrete ramp accessible to the disabled, a masonry wall, steel columns with steel base plates and bolts, steel beams, wood joists, steel roof deck, rigid insulation, single-ply membrane roof coverings, storefront glazing, and storefront doors. Special Inspection is required for soils, concrete, masonry, steel (including welding), and anchors post installed in hardened concrete. Interior work includes interior nonbearing walls; interior windows; interior doors; a toilet room accessible to the disabled; a gas fireplace; new carpet in the corridors; new wall finishes in the corridors; new interior cable guards; new interior handrails on existing stairways; and new interior footings, columns, and beams where the 2nd story floor will be modified. All work is required to comply as Type V-A construction. The corridor is required to be maintained as a 1-hr fire-resistance-rated corridor enclosure. Other work includes new cable guards at 2nd story apartment balconies, new exterior Hardie board siding, new standing seam metal roofing to replace wood shake siding, a horizontal sliding/folding window/door, and a gas fire pit. Except for guards at balconies, no work will be done within individual dwelling units. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. The fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. A separate fire alarm permits shall be obtained prior to beginning any modification or installation work on such system. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Routing - PLAN CHECK3/20/2019 3/21/2019 FAIL
DetailsCarl Westfall
(3-21-19) The plan modification to remove 1-hr rated interior windows W2, W3, and W4 that are located between an enclosed 1-hr rated corridor and an office was not approved. Offices are not allowed to be within the enclosure of a 1-hr corridor. The glass was required to have a 1-hr fire-resistance-rating because the area of the glass exceeds 25% of the area of the common wall between the office and the corridor. A plan modification that would replace the glass with a 1-hr wall with the area of glass in each wall having a 45 minute fire-protection-rating and limited to 25% of each common wall between the corridor and the office would be considered. CJW
Plan Modification Accepted  3/20/2019 DONE
3RD PLAN MODIFICATION: Remove 1-HR rating of interior windows W2, W3 and W4 per on-site discussions with contractor and Jim Storey. Sheet number A620
OVERRIDE  3/4/2019  
Plan assigned to (CJW)2/26/20192/26/20193/4/2019 PASS
DetailsCarl Westfall
Plan mod - Creek bend appartments (plan intake approved)
Routing - PLAN CHECK3/4/2019 3/4/2019 PASS
DetailsCarl Westfall
CHANGE STATUS TO (ISS)  3/4/2019 DONE
PLAN MOD
Plan Modification Accepted  3/4/2019 PASS
Plan intake review approved
Plan Reviewer's activity  3/4/2019 PASS
Plan mod review approved
Permit Ready to Issue  3/4/2019 DONE
PLAN MOD
Plan Modification Accepted  2/27/2019 FAIL
Plan Reviewer's activity  2/27/2019 DONE
Called Matt. Left message asking for clarification for the plan mod.
Plan resubmittals received  2/26/2019 DONE
Structural revisions related to lobby and office remodel
BLD-Energy code compliance1/22/20191/22/20191/22/2019PPASS
DetailsJim Storey
Greg Phone #: ###-####
BLD-Framing/Rough-in1/14/20191/14/20191/14/2019PPASS
DetailsJim Storey
Greg Phone #: ###-####
CHANGE STATUS TO (ISS)  12/26/2018 DONE
Print Occupancy Form  12/26/2018 DONE
OVERRIDE  12/24/2018  
Plan assigned to (CJW)12/21/201812/21/201812/24/2018 PASS
DetailsCarl Westfall
Plan mod - Creek Bend Apartments (plan intake done)
Routing - PLAN CHECK12/21/2018 12/24/2018 PASS
DetailsCarl Westfall
1st plan mod approved
Plan Reviewer's activity  12/24/2018 PASS
Plan mod review approved
Permit Ready to Issue  12/24/2018 DONE
PLAN MOD
Plan Modification Accepted  12/21/2018 DONE
Interior stair replacement
BLD-Energy code compliance12/14/201812/14/201812/14/2018PPART
DetailsJim Sly
Greg Phone #: ###-####
Witnessed drilling holes in steel columns and beams on new Vestibule.....Main Frame......Not out riggers........and filling columns and beams with closed cell foam as shown on approved plan. Intumescent fire coating to have special inspection.
BLD-Framing/Rough-in12/5/201812/6/201812/6/2018APART
DetailsJim Storey
Jeff Phone #: ###-#### parepet and wall framing ok to cover/ straps and drag struts in place for reroof/ ft ok to cover with floor framing at exterior columns.// stair and ft interior pending aproval and ft placement .
BLD-Other11/9/201811/9/201811/9/2018PPASS
DetailsJim Storey
Steel CMU - Greg Phone #: ###-####si pending
BLD-Footing11/2/201811/2/201811/2/2018PPASS
DetailsJim Storey
Greg Phone #: ###-#### placed w si
BLD-Footing10/24/201810/25/201810/25/2018PPASS
DetailsJim Storey
Jeff Phone #: ###-#### si passed
BLD-Conference9/27/20189/28/20189/28/2018ADONE
DetailsJim Storey
Greg Phone #: ###-####
Issue PAID IN FULL permit  8/31/2018 DONE
Print Occupancy Form  8/31/2018 DONE
OVERRIDE  8/24/2018  
Plan assigned to (CJW)6/13/20186/13/20188/24/2018 PASS
DetailsCarl Westfall
(3rd done) 06/29/18 (L3 - 15 days) (ePlan - 73 sheets) Creek Bend Apartments
Routing - Design Review8/23/2018 8/24/2018 PASS
DetailsAndrea Tuning
PLANS/APPL TAKEN TO FRONT DESK  8/24/2018 DONE
Permit Ready to Issue  8/24/2018 DONE
NEED
RP - met
GC - met
Rev Cert of Val - met
Routing - PUBLIC WORKS8/23/2018 8/23/2018 PASS
DetailsRachael Beierle
Plan resubmittals received  8/23/2018 DONE
Routing - PLAN CHECK8/23/2018 8/23/2018 PASS
DetailsCarl Westfall
Drawings approved and plan review report uploaded. Drawings routed.
Routing PW Flood Plain8/21/2018 8/22/2018 PASS
DetailsJason C. Taylor
Project is 1 ft above BFE and does not meet the Substantial Improvements section of Boise Floodplain Ordinance (B.C.C. 11-08). No floodplain requirements. If you have any questions, please call Jason Taylor at ###-####.
Plan resubmittals requested  8/20/2018 DONE
Routing Off Site - STRUCTURAL8/8/2018 8/14/2018 PASS
DetailsCarl Westfall
Dave Haugland (AHJ)
Routing - Design Review8/8/2018 8/9/2018 FAIL
DetailsAndrea Tuning
Obtain a Floodplain Permit for the new improvements located on the site.
Plan resubmittals received  8/8/2018 DONE
Routing - PLAN CHECK8/8/2018 8/8/2018 PASS
DetailsCarl Westfall
Pending structural (remember to upload report)
Plan resubmittals requested  8/2/2018 DONE
Routing Off Site - STRUCTURAL7/26/2018 8/1/2018 FAIL
DetailsCarl Westfall
Dave Haugland (AHJ)
Routing - FIRE7/26/2018 7/30/2018 PASS
DetailsErika Akin
Attached revised comments to case
Routing - PLAN CHECK7/25/2018 7/26/2018 PASS
DetailsCarl Westfall
Pending structural
Routing - Design Review7/26/2018 7/26/2018 FAIL
DetailsAndrea Tuning
a. Install one (1) Class II tree within each of the interior planter islands throughout the parking area.
b. Obtain a Floodplain Permit for the new improvements located on the site.
Plan resubmittals received  7/25/2018 DONE
Route to Impact Fee Review7/20/20187/23/20187/23/2018 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
Routing - PLAN CHECK6/26/2018 7/20/2018 FAIL
DetailsCarl Westfall
Revised drawings required
Routing - FIRE6/27/2018 7/20/2018 FAIL
DetailsErika Akin
Attached comments to plans and emailed architect
1st review completed  7/20/2018 DONE
Plan resubmittals requested  7/20/2018 DONE
Routing PW Drainage6/28/2018 6/28/2018 PASS
DetailsBrian Murphy
Routing - PLANNING6/14/2018 6/28/2018  
DetailsSusan Riggs
No review required
Routing Off Site - STRUCTURAL6/13/2018 6/28/2018 FAIL
DetailsCarl Westfall
Dave Haugland (AHJ)
Routing - MECHANICAL6/13/2018 6/26/2018 PASS
DetailsTroy James
Routing - PLUMBING6/13/2018 6/19/2018 PASS
DetailsBill VanDegrift
verify Suez Water required premise protection
Routing - Erosion and Sediment6/14/2018 6/15/2018 PASS
DetailsMichael Zawacki
Waiver requested. Good housekeeping and management required. Will keep creek area free of trash, building materials, and other waste.
Routing - Addressing6/13/2018 6/14/2018 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS6/13/2018 6/14/2018 PASS
DetailsRachael Beierle
Routing PW Drainage6/14/2018 6/14/2018 PASS
DetailsBrian Murphy
Routing PW Sewer Rating6/14/2018 6/14/2018 PASS
DetailsRachael Beierle
Routing - Design Review6/13/2018 6/14/2018 FAIL
DetailsAndrea Tuning
a. Install one (1) Class II tree within each of the interior planter islands throughout the parking area.
b. Obtain a Floodplain Permit for the new improvements located on the site.
Pending Assignment by CDM6/11/2018 6/13/2018 DONE
DetailsCarl D Madsen
Plans ACCEPTED BY PLAN TECH  6/11/2018 DONE
Intake Approval  6/11/2018 PASS
DetailsJavier Guzman
Recd Pcfee & Taken To Pln CK  6/11/2018 DONE
Plan assigned to (CJW)3/20/20193/20/2019   
DetailsCarl Westfall
plan mod - Creekbend apartment (plan mod intake rejected and sent back to the applicant)
Application received 6/11/2018