Change Expiration Date Only | | | 7/15/2020 | | DONE |
|
|
|
|
BLD-Aging Inspection | 7/13/2020 | 7/13/2020 | 7/13/2020 | | PASS |
Jim Storey
|
|
|
Upgrade Agreement attached for this permit and for permit BLD18-02699. jcb
|
Plan Reviewer's activity | | | 6/10/2020 | | DONE |
Jason Blais
|
|
|
Upgrade Agreement attached for this permit and for permit BLD18-03786.
|
Change Expiration Date Only | | | 6/1/2020 | | DONE |
|
|
|
permit extended 90 days from June 1, 2020 per Jason Blais. See DOCS
|
Change Expiration Date Only | | | 5/28/2020 | | DONE |
|
|
|
|
Telephone call | | | 5/28/2020 | | DONE |
|
|
|
emailed todd@vertical-corp.com: Your TMP for the subject permits will expire soon. Please request an extension from Jason Blais: jblais@cityofboise.org. Please provide your permit numbers and explain where you are with the draft Upgrade Agreement.
|
BLD-Aging Inspection | 5/11/2020 | 5/11/2020 | 5/11/2020 | | PASS |
Jim Storey
|
|
|
as per Jason Blais-90 temp c of o extension was approved from 3/31/19
|
BLD-Aging Inspection | 3/9/2020 | 3/9/2020 | 3/9/2020 | | PASS |
Jim Storey
|
|
|
as per Jason Blais-90 temp c of o extension was approved from 3/31/19
|
Telephone call | | | 2/25/2020 | | DONE |
|
|
|
Spoke with Julie and she and Jason are still working with the applicant.
|
Meeting | | | 2/4/2020 | | DONE |
|
|
|
expiring TCO: emailed Julie and she said she and Jason are working directly with the applicant and that I need not contact them.
|
BLD-Aging Inspection | 1/6/2020 | 1/6/2020 | 1/6/2020 | | DEFR |
Jim Storey
|
|
|
as per Jason Blais-90 temp c of o extension was approved from 3/31/19
|
BLD-Aging Inspection | 11/4/2019 | 11/4/2019 | 11/4/2019 | | DONE |
Jim Storey
|
|
|
as per Jason Blais-90 temp c of o extension was approved from 3/31/19
|
BLD-Aging Inspection | 9/2/2019 | 9/2/2019 | 9/3/2019 | | PASS |
Jim Storey
|
|
|
Expires: 06/30/19 / bo expired
|
BLD-Conference | 7/2/2019 | 7/2/2019 | 7/2/2019 | P | DONE |
Jim Storey
|
|
|
can you please verify if business has vacated building? they only have a temp c of o good to 6/30/19 Candy Phone #: ###-#### occupid
|
Telephone call | | | 7/2/2019 | | DONE |
|
|
|
sent inspector to verify if building was vacated since this is a temp c of o ONLY good through 6/30/19
|
Telephone call | | | 7/2/2019 | | DONE |
|
|
|
per Julie R-her and Jason Blais are working on a letter for this project so ok if it's expired for now-she will let me know when i need to change it
|
BLD-Aging Inspection | 6/3/2019 | 6/3/2019 | 6/3/2019 | | FAIL |
Jim Storey
|
|
|
as per Jason Blais-90 temp c of o extension was approved from 3/31/19
|
Temporary Occupancy | 4/11/2019 | 7/10/2019 | 4/11/2019 | | DONE |
Candy A. Nichols
|
|
|
as per Jason Blais-90 temp c of o extension was approved from 3/31/19
|
Temporary Occupancy | 4/11/2019 | 7/10/2019 | 4/11/2019 | | DONE |
Candy A. Nichols
|
|
|
redid the temp c of o-i forgot to do 90 days from 3/31/19
|
Plan Reviewer's activity | | | 4/11/2019 | | DONE |
Julie Romig
|
|
|
Temporary C of O extended to June 30th per Jason Blais Building Official. Email attached.
|
Plan Reviewer's activity | | | 4/8/2019 | | |
|
|
|
Left message with Blu Atwood, Fifty Flowers CMO and building owner to let him know that he needs to email Jason Blais to request a 90 day extension for the Temp CofO with reasons for needing the extension, timeline/dates Law Alternatives will finalize lease, move off of 3rd floor, etc.
|
Plan Reviewer's activity | | | 4/4/2019 | | |
|
|
|
Spoke with building owner and Fifty Flowers CEO, Blu Atwood (###-####). Law Alternatives opted to renew lease. He is negotiating with Law Alternatives to move them down to the second floor. Agreement is not yet finalized. Anticipates Law Alternatives to move to second floor in late summer/early fall. TI permit will be necessary for work on second floor. Jim Storey has been in touch with the owner, about a month ago. Told owner I'd talk with Jim and the building official to determine how we'll proceed with the Temp C of O that is expired.
|
BLD-Other | 4/1/2019 | 4/2/2019 | 4/2/2019 | A | DONE |
Jim Storey
|
|
|
Candy-Can you please verify if business has vacated-temp only c of o expired 3/31/19-thank you Phone #: ###-#### stil occ. Temp per plan review. Life safety passed.
|
Plan Reviewer's activity | | | 4/2/2019 | | DONE |
Julie Romig
|
|
|
Contacted Architect by email to see if any building permits for final occupancy were in progress. Response from Architect's office:
We are not currently working on the permit documents, and we have reminded the client of this obligation a couple of months ago but haven't been in contact since then. Amanda Bidwell - AIT, LEED AP
|
BLD-Aging Inspection | 3/13/2019 | 3/13/2019 | 3/13/2019 | | PASS |
Jim Storey
|
|
|
Temp per plan review. Life safety passed.
|
Temporary Occupancy | 1/14/2019 | 4/14/2019 | 1/14/2019 | | DONE |
Candy A. Nichols
|
|
|
|
Print Occupancy Form | | | 1/14/2019 | | DONE |
|
|
|
|
FIRE-Final Inspection | 1/11/2019 | 1/11/2019 | 1/11/2019 | P | PASS |
Troy Cobbley
|
|
|
Permit to be finaled as per plan review
|
BLD-Final | 1/9/2019 | 1/10/2019 | 1/10/2019 | A | PASS |
Jim Storey
|
|
|
Todd Phone #: ###-#### Temp per plan review. Life safety passed.
|
Temporary Occupancy | 1/10/2019 | 4/10/2019 | 1/10/2019 | | DONE |
Candy A. Nichols
|
|
|
|
CHANGE STATUS TO (ISS) | | | 1/10/2019 | | DONE |
|
|
|
put in TEMP status by mistake
|
FIRE-Final Inspection | 1/8/2019 | 1/9/2019 | 1/9/2019 | A | PART |
Troy Cobbley
|
|
|
Temp per plan review. Life safety passed.
Request inspection for after 10:00. Please call Todd 30 min prior to inspection. Phone #: ###-#### Inspection requested via web by Todd Weltner
|
BLD-Final | 1/7/2019 | 1/8/2019 | 1/8/2019 | P | CANC |
Jim Storey
|
|
|
Please call Todd 15 min prior. thx Phone #: ###-#### >> Inspection requested via web by Todd Weltner Inspection cancelled from web by: Todd Weltner
|
FIRE-Final Inspection | 1/7/2019 | 1/8/2019 | 1/8/2019 | A | FAIL |
Troy Cobbley
|
|
|
I called contacts phone number and left message that I would be there in 15 or 20 minutes. Arrived at 3rd floor project but did not make contact. I found plans for BLD18-02699 but not other plans or any small documents. Please call Todd 15 min prior. thx Phone #: ###-#### Inspection requested via web by Todd Weltner
|
FIRE-Final Inspection | 1/4/2019 | 1/4/2019 | 1/4/2019 | P | FAIL |
Jim Page
|
|
|
Fire sprinkler permit is still in issued status, fire sprinkler permit needs to be completed and in finaled status before life fire safety inspection can be performed as stated in past notes.
Please call Todd ahead 15 min Phone #: ###-#### Inspection requested via web by Todd Weltner
|
BLD-Final | 1/2/2019 | 1/4/2019 | 1/4/2019 | A | CANC |
Jim Storey
|
|
|
re-inspection Todd Phone #: ###-#### Inspection cancelled from web by: Todd Weltner
|
FIRE-Final Inspection | 1/3/2019 | 1/4/2019 | 1/4/2019 | A | FAIL |
Jim Page
|
|
|
Fire sprinkler inspection failed. All foil on fire sprinkler heads needs to be removed. Fire extinguisher is mount to high and is not code compliant, extinguisher needs to be lowered and tagged with a current inspection tag.
Call 15 minutes ahead // Todd Phone #: ###-####
|
FIRE-Final Inspection | 1/2/2019 | 1/3/2019 | 1/3/2019 | P | CANC |
Jim Page
|
|
|
Tried to call point of contact provided, left voicemail stating that FIR permit for fire sprinklers is still in issued status, installing contractor for fire sprinklers has inspection scheduled for 04JAN2019, life fire safety inspection cannot be completed before FIR permit for fire sprinklers is finaled, this request is cancelled and a new inspection will need to be generated to coincide with fire sprinkler inspection.
re-inspection Todd Phone #: ###-####
|
BLD-Wall cover | 1/2/2019 | 1/3/2019 | 1/3/2019 | P | NR |
Jim Storey
|
|
|
re-inspection Todd Phone #: ###-#### wall ok/ need east wall and west wall patched/ smoke seals/ door closers// remove all idems from stairs.
|
BLD-Wall cover | 12/28/2018 | 12/31/2018 | 12/31/2018 | A | PART |
Jim Storey
|
|
|
Need to see Fire Caulking in stairwell // Scott Phone #: ###-#### interior of stair encloser ok above ceilling and ceilling. exterior of walls not complet yet.
|
BLD-Ceiling Grid Inspection | 12/6/2018 | 12/7/2018 | 12/7/2018 | P | PASS |
Jim Storey
|
|
|
Scott Phone #: ###-#### east stair ok
|
BLD-Framing/Rough-in | 12/3/2018 | 12/4/2018 | 12/4/2018 | P | PASS |
Jim Storey
|
|
|
Scott Phone #: ###-#### east stair ok
|
CHANGE STATUS TO (ISS) | | | 11/30/2018 | | DONE |
|
|
|
plan mod
|
Plan assigned to (JAR) | 11/5/2018 | 11/5/2018 | 11/28/2018 | | DONE |
Julie Romig
|
|
|
11/27 - 3rd Rev - Plan Mod Fifty Flowers/Law Alternatives
|
Routing - PLAN CHECK | 11/21/2018 | | 11/28/2018 | | PASS |
Julie Romig
|
|
|
|
Permit Ready to Issue | | | 11/28/2018 | | DONE |
|
|
|
PLAN MOD (CHANGE BLD18-03786 BACK TO ISSUE STATUS ONCE THIS HAS BEEN PAID)
|
Routing - PLAN CHECK | 11/15/2018 | | 11/15/2018 | | FAIL |
Julie Romig
|
|
|
|
Routing - PLAN CHECK | 11/7/2018 | | 11/9/2018 | | FAIL |
Julie Romig
|
|
|
|
BLD-Framing/Rough-in | 11/2/2018 | 11/5/2018 | 11/5/2018 | A | FAIL |
Jim Storey
|
|
|
Scott Phone #: ###-#### need fire treated wood/ need listing for 1 hr if not as approved. plm c/n
|
Plan Modification Accepted | | | 11/5/2018 | | DONE |
|
|
|
The fire wall construction at the top of the stairwell walls has been modified. r revised detail is being provided
|
Issue PAID IN FULL permit | | | 10/23/2018 | | DONE |
|
|
|
|
Print Occupancy Form | | | 10/23/2018 | | DONE |
|
|
|
|
Plan assigned to (JAR) | 8/2/2018 | 8/2/2018 | 10/19/2018 | | DONE |
Julie Romig
|
|
|
10/25 - 3rd Rev - 1st Rev Comp - L3 Fifty Flowers
|
Routing - PLAN CHECK | 10/19/2018 | | 10/19/2018 | | PASS |
Julie Romig
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/19/2018 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/19/2018 | | DONE |
|
|
|
(close out BLD18-03094 early start when this permit is issued)
MET
NEED
REVISED VALUE
(close out BLD18-03094 early start when this permit is issued)
MET
GC FORM
|
Routing - PLUMBING | 10/10/2018 | | 10/16/2018 | | PASS |
Daryl Spivey
|
|
|
Per plan and ISPC
|
Routing - PLAN CHECK | 10/10/2018 | | 10/15/2018 | | FAIL |
Julie Romig
|
|
|
|
Routing - MECHANICAL | 10/10/2018 | | 10/11/2018 | | PASS |
Chad Schwendiman
|
|
|
|
Route to Impact Fee Review | 9/13/2018 | 9/16/2018 | 9/14/2018 | | PASS |
Eric Bilimoria
|
|
|
Review requested for Commercial Permit
|
Routing - PLAN CHECK | 8/2/2018 | | 9/13/2018 | | FAIL |
Julie Romig
|
|
|
|
Routing - MECHANICAL | 8/2/2018 | | 9/13/2018 | | PASS |
Chad Schwendiman
|
|
|
|
1st review completed | | | 9/13/2018 | | FAIL |
Julie Romig
|
|
|
|
Routing - FIRE | 8/2/2018 | 8/2/2018 | 8/30/2018 | | PASS |
Erika Akin
|
|
|
Attached comments to case
|
Intake Approval | | | 8/2/2018 | | PASS |
|
|
|
|
Routing - PLUMBING | 8/2/2018 | | 8/2/2018 | | PASS |
Bill VanDegrift
|
|
|
Per plan and ISPC.
|
Routing - Addressing | 8/2/2018 | | 8/2/2018 | | PASS |
Doug Chausow
|
|
|
Suite 350
|
Routing - PUBLIC WORKS | 8/2/2018 | | 8/2/2018 | | PASS |
Morgan Webb
|
|
|
|
Application received | | | 7/30/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 30 2018 8:39AM
|
Agreement of Future work | 6/10/2020 | 3/3/2023 | | | |
Julie Romig
|
|
|
(FIFTY FLOWERS) Upgrade Agreement attached with due date of 3/4/23. Is also tied to Building Permit BLD18-03786.
|
Temporary Occupancy | 1/14/2019 | 4/14/2019 | | | |
|
|
|
|