FIRE-Final Inspection | 6/26/2020 | 6/29/2020 | 6/29/2020 | P | FAIL |
Troy Cobbley
|
|
|
The only correction item completed was the installation of the sprinklers under the duct work. I found the un-attached permit for that work and it had been finaled. No other items addressed. Jay *screened* Phone #: ###-####
|
BLD-Aging Inspection | 6/17/2020 | 6/17/2020 | 6/17/2020 | | PASS |
Jim Storey
|
|
|
signs that were shown as existing but were not in place. Provide signage on door for anti-freeze sprinkler riser control valves. Provide fire sprinklers under duct work that exceeds 48 inches. Permit for racking, BLD18-02859 needs to be finaled before life fire safety can be signed off. fire sign off required
|
BLD-Aging Inspection | 6/16/2020 | 6/16/2020 | 6/16/2020 | | NR |
Jim Storey
|
|
|
signs that were shown as existing but were not in place. Provide signage on door for anti-freeze sprinkler riser control valves. Provide fire sprinklers under duct work that exceeds 48 inches. Permit for racking, BLD18-02859 needs to be finaled before life fire safety can be signed off. fire sign off required
|
FIRE-Final Inspection | 2/3/2020 | 2/3/2020 | 2/3/2020 | P | FAIL |
Jim Page
|
|
|
Notated city approved drawings with red ink areas where exit signage was shown as new but is not placed, exit signs shown as wall mounts that are pendant style and exit signs that were shown as existing but were not in place. Provide signage on door for anti-freeze sprinkler riser control valves. Provide fire sprinklers under duct work that exceeds 48 inches. Permit for racking, BLD18-02859 needs to be finaled before life fire safety can be signed off.
Jeff Phone #: ###-####
|
Zoning Approval | 12/13/2019 | 12/13/2019 | 12/13/2019 | | PASS |
Josh Wilson
|
|
|
|
BLD-Aging Inspection | 12/12/2019 | 12/12/2019 | 12/12/2019 | | PASS |
Jim Storey
|
|
|
wip
|
FIRE-Final Inspection | 12/11/2019 | 12/12/2019 | 12/12/2019 | P | FAIL |
Troy Cobbley
|
|
|
Left message on contacts voice mail. I went to site and spoke to staff but made no contact with Jefft. No inspection performed.
Jeff Phone #: ###-####
|
BLD-Aging Inspection | 12/11/2019 | 12/11/2019 | 12/11/2019 | | FAIL |
Jim Storey
|
|
|
need insp for three permits// BLD18-02753 Issued (SCANDINAVIAN DESIGN) Permit for exterior improvements and interior service counter to an existing building previously occupied by Office Max per the approved plans. The exterior improvements have been approved by the planning department under DRH18-00251. Interior work for furniture store and layout is being completed under BLD18-02535. This building is fully fire sprinklered for area increase. Any alterations to the sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the fire department. **JHB** BLD18-02859 Issued (SCANDINAVIAN DESIGNS) (Racking) - Installation of (21) bays of pallet racking. NO RACKING APPROVED AT, OVER OR BLOCKING DOORS. Permit to install steel storage racking exceeding 8' (up to 14') in height within the warehouse space per approved plans and structural engineering. (23) bays of 42"x96" bays in two (2) rows with 12'-6" between the rows. Approval of this permit is contingent on adhering to approved plans and engineering. Work to include: installation of prefabricated 16 foot storage racking, including seismic bolting to existing slab, the design, testing and utilization of industrial steel storage racks shall be in accordance with the RMI Specification for the Design, Testing and Utilization of Industrial Steel Storage Racks. The structural design by Rack Design and Engineering. Engineering is attached. ***BJM*** BLD19-03185 Issued (SCANDINAVIAN DESIGN FURNITURE) (CSN19-00220) Permit to install (4) illuminated wall signs. Wall signs: (1) 5'-6" x 35'-4" on the north elevation, (1) 5'-10 x 45'-8" on the east elevation, (2) 9'-0" x 9'-9" on the east elevation. Attachments are required to be sufficient to resist all gravity, snow, wind, and seismic loads with appropriate safety factors included. MDH
|
Print Occupancy Form | | | 12/11/2019 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 7/29/2019 | 7/30/2019 | 7/30/2019 | P | PASS |
Dave Hannah
|
|
|
canopy // Jeff Phone #: ###-#### 2x6 framing to shed water ok
|
BLD-Framing/Rough-in | 7/3/2019 | 7/8/2019 | 7/8/2019 | A | PASS |
Jim Storey
|
|
|
partial // Jeff Phone #: ###-#### exterior entry and fur out as well as ceilling and walls inside ok to cover.
|
Meeting | | | 6/21/2019 | | DONE |
|
|
|
permit went from JR Zar Ince to Canning Construction Inc
|
Telephone call | | | 6/12/2019 | | DONE |
|
|
|
received email from Sarah that they want to hire a new GC for this job. Told her we needed a letter on JR Zar's letter head stating that they are not the GC anymore and who they give permission to use the approved drawings. Itold her the new GC will need to get us a 302 for as well as a fee of $46.31 will need to be paid.
|
Issue PAID IN FULL permit | | | 1/25/2019 | | DONE |
|
|
|
|
Print Occupancy Form | | | 1/25/2019 | | DONE |
|
|
|
|
Telephone call | | | 1/17/2019 | | DONE |
|
|
|
spoke with racheal informing this permit is going to expire in 11 days. she stated she informed the GC
|
Expiration Notice | 1/9/2019 | 1/31/2019 | 1/9/2019 | | DONE |
Brittany Hill
|
|
|
|
Plan assigned to (JHB) | 8/23/2018 | 8/23/2018 | 9/27/2018 | | PASS |
Joe Bruce
|
|
|
(1st Rev Comp) 08/31 (L2) - Scandinavian Designs TI
|
Routing - PLAN CHECK | 9/19/2018 | | 9/27/2018 | | PASS |
Joe Bruce
|
|
|
|
Routing Off Site - STRUCTURAL | 9/19/2018 | | 9/27/2018 | | PASS |
Joe Bruce
|
|
|
Dave Haugland - AHJ
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/27/2018 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/27/2018 | | DONE |
|
|
|
all met-Need
GC Form
Revised Cert Of Value
|
Plan resubmittals received | | | 9/19/2018 | | DONE |
|
|
|
|
Route to Impact Fee Review | 8/29/2018 | 9/1/2018 | 8/29/2018 | | PASS |
Eric Bilimoria
|
|
|
Review requested for Commercial Permit
|
1st review completed | | | 8/29/2018 | | FAIL |
Joe Bruce
|
|
|
|
Plan resubmittals requested | | | 8/29/2018 | | DONE |
Joe Bruce
|
|
|
|
Routing - PLAN CHECK | 8/14/2018 | | 8/29/2018 | | FAIL |
Joe Bruce
|
|
|
|
Routing Off Site - STRUCTURAL | 8/14/2018 | | 8/27/2018 | | FAIL |
Julie Romig
|
|
|
Dave Haugland - AHJ
|
Routing - FIRE | 8/14/2018 | 8/14/2018 | 8/24/2018 | | PASS |
Erika Akin
|
|
|
Attached comments to case
|
Plan assigned to (JAR) | 8/14/2018 | 8/14/2018 | 8/23/2018 | | DEFR |
Julie Romig
|
|
|
08/27 - L2 Scandinavian Designs
|
Routing - Erosion and Sediment | 8/14/2018 | | 8/15/2018 | | PASS |
Michael Zawacki
|
|
|
Minor TI, no ESC or waiver required.
|
Routing - Addressing | 8/14/2018 | | 8/14/2018 | | PASS |
Doug Chausow
|
|
|
|
Routing - PUBLIC WORKS | 8/14/2018 | | 8/14/2018 | | PASS |
Morgan Webb
|
|
|
|
Routing - Design Review | 8/14/2018 | | 8/14/2018 | | PASS |
Andrea Tuning
|
|
|
|
Intake Approval | | | 8/14/2018 | | PASS |
Javier Guzman
|
|
|
|
Application received | | | 8/1/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 1 2018 11:22AM
|